Winco W15PTOS/E Operator'S Instruction Manual Download Page 7

Page 5

60706-180

0310-00

A properly rated and installed double throw manual power
isolation transfer switch must be used with a standby genera-
tor.  The transfer switch isolates the load from the power line
and allows you to safely operate your loads without endanger-
ing the power line repair crew.  See page 4.

  The load, connected to the normal terminals of the transfer
switch, is energized by the normal power line when the switch
is in the normal position.  The generator, connected to the
emergency terminals of the switch, furnishes power when the
switch is in the emergency mode position.

There are two ways to install a manual transfer switch.  The
first shown on the left side of page 4 is to install the switch
between the watt-hour meter and the normal distribution panel.
As with any system you must install an entrance rated breaker
before the manual transfer switch.  The manual transfer switch
must in all cases be equal to or greater than the rating of the
entrance rated breaker.

The second way to install the system is to purchase and install
an emergency distribution panel and move the circuits you
wish  to back up to the new distribution panel.  In this case the
manual transfer switch only has to be sized to the amperage of
the circuit breaker in the main distribution panel that is feeding
it.  See the right hand drawing on page 4

Before deciding which system to install, first determine which
loads you can safely run on your PTO generator and the cost
of  buying a large manual transfer switch versus the cost of a
smaller  switch and the additional distribution panel.

The final item that you are going to have to assembly/wire is
the plug that will be used to connect the generator to the
manual transfer switch.  You should have found this load plug
in a small box when you unpacked the PTO generator.  If you
need additional plugs for multiple sites you can order additional
plugs from your Winco dealer, the part number is “300137”.

WARNING:  Personal Injury
DISCONNECT POWER BEFORE WIRING

IMPORTANT:  Use copper wire only.  Do not use tinned
conductors.  Sizing cable - see NEC 400-5.

CORD SIZE:  #4/4 conductor cord SO, 1.25 inch dia. max.

Figure 2

To assemble and wire the load disconnect plug, proceed as
follows:
1.

Strip outer jacket 2-3/4”.

2.

Cut and strip leads to lengths specified for the
particular plug.

3.

Disassemble cable clamp and top cover.

4.

Remove one blade at a time, insert the stripped end
of the appropriate colored wire designated above,
and tighten the set screw.

5.

Fit blades through slots in bottom cover and push
down until home.  Please note:  Make sure blades
are in correct slots and oriented in accordance with
the diagram above or you will not be able to close
the top cover fully.

6.

Place top plastic cover over assembly and partially
tighten the bakelite assembly screw.  Realign
blades straight (so they fit into the top bakelite
housing properly) and tighten the assembly screw.

7.

Assemble cable clamp over the outer jacket of the
wire and tighten the two clamp screws.

Special Note:  For small size round (less than 3/4”) and flat
cables, the wire clamp may be inverted.

WARNING:  Failure to wire as instructed may cause
personal injury or damage to device or equipment.  To be
installed or checked by an electrician or qualified person
only.

PRE-START CHECKS

WARNING:  Personal Injury

When working on or around these generators, do not wear
loose fitting clothing or any articles that may get caught in
moving parts.

1. Visually inspect the generator. Check for:

a

Correct mounting

b. Physical damage
c. Debris in cooling vents and screens (could

cause generator to overheat).

IMPORTANT: The manufacturer recommends that, if the gen-
erator has been stored for any length of time, before using it,
the operator remove the control box cover and cooling fan
screen, then inspect the generator for rodent nests or other ob-
jects that could cause generator binding and/or overheating.
See “Cleaning” portion of Maintenance section.

2. Check gear case oil level. (See

Figure 4.) Case should be filled
with oil to plug marked “OIL
LEVEL.” Fill or remove oil as
required.

NOTE: EITHER TOO LITTLE OR
TOO MUCH OIL CAN HARM THE
EQUIPMENT.

See “Lubrication” portion of
Maintenance for oil specifications.

Summary of Contents for W15PTOS/E

Page 1: ...OPERATOR INSTRUCTION MANUAL COMPACT PTO GENERATORS COMPACT SERIES TRACTOR DRIVE GENERATOR W15PTOS E ...

Page 2: ... YOUR PTO GENERATOR IS IN OPERATING CONDITION AND READY FOR USE WHEN THE NEED ARISES PARTS LIST PARTS DRAWINGS AND WIRING DIAGRAM PERTAINING TO YOUR UNIT ARE ENCLOSED WITH THIS MANUAL This manual covers the latest compact portable tractor driven Power Take Off PTO generator model from Winco This 15 000 watt generator is designed to provide120 240V single phase electrical power for standby and util...

Page 3: ...nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring but continual exposure can lead to loss of hearing a Use...

Page 4: ...UTION Equipment Damage DO NOT invert generator during unpacking The Gearcase contains oil which will leak out if inverted during unpacking Unpack the generator as follows 1 Remove the carton 2 Examine the unit for damage 3 Find the small subpack carton packed in the large carton Be careful not to throw away the subpack carton with the large carton 4 Open the subpack carton and make sure it contain...

Page 5: ... generator on the trailer should enable aligning the drive shaft tumbling bar in a straight or nearly straight line between the power take off and generator input shafts Misalignment must be less than 10 degrees during generator operation even though the mechani cal design of the tumbling bar would allow greater misalign ment D The generator mounting area of the trailer bed should be flat All four...

Page 6: ...ional Electrical Code DANGER PERSONAL INJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A MANUAL TRANSFER SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE SWITCH MUST ISOLATE THE GENERATOR FROM THE COM MERCIAL POWER LINES AND THE LOAD WHEN THE GENERATOR IS ON STANDBY AND MUST ISOLATE THE COMMERCIAL POWER LINES FROM THE LOAD AND THE GENERATOR WHEN ...

Page 7: ...R BEFORE WIRING IMPORTANT Use copper wire only Do not use tinned conductors Sizing cable see NEC 400 5 CORD SIZE 4 4 conductor cord SO 1 25 inch dia max Figure 2 To assemble and wire the load disconnect plug proceed as follows 1 Strip outer jacket 2 3 4 2 Cut and strip leads to lengths specified for the particular plug 3 Disassemble cable clamp and top cover 4 Remove one blade at a time insert the...

Page 8: ...he output reaches approximately 240 to 245 volts in green portion of voltmeter scale 5 Plug 4 wire load cord set into receptacle Place transfer switch in the emergency position 6 Place the load circuit breaker in the on position If the breaker trips move manual transfer switch to off or normal position Check for short circuit or grounded connection in the load cable to the double throw switch and ...

Page 9: ...ling causes overheating and oil seal failure 2 The generator bearings are factory lubricated and sealed and require no further lubrication 3 The splined generator input shaft should be cleaned and lubricated with a thin film of grease before and after each use of the generator See Figure 6 for lubrication sched ule 4 The drive shaft tumbling bar requires greasing Keep the universal joints in the c...

Page 10: ...ace if defective Low Speed High line loss Indicated by lower voltage at load than at generator terminals 1 Undersized overloaded 2 Defective governor 3 Low power worn engine LOW OUTPUT VOLTAGE POSSIBLE CAUSE Loss of residual magnetism Usually occurs only after disassembly of field frame or severe mechanical stress abuse Grounded or shorted rotor winding Open excitor circuit in stator Defective dio...

Page 11: ... Control Box Sheet Metal 2 91370 000 1 Voltmeter 0 300 VAC 3 300136 1 Receptacle NEMA 14 60R 4 50766 000 1 Receptacle NEMA 5 20R 5 91286 001 1 Circuit Breaker 20 AMP 120 VAC 6 63708 000 1 Ground Lug 7 57030 005 1 Circuit Breaker 60 AMP 240 VAC NI 300137 1 Plug NEMA 14 60P Supplied with the Unit ...

Page 12: ...80 2 1 Receptacle Box Cover 6 300086 1 1 Safety Shield 7 15209 000 1 Safety Decal 8 Z 2516 1 Warning Decal 9 Z2553 1 Operating Instructions Decal REF PART QTY DESCRIPTION 10 Z9941 1 Oil Fill Hole Decal 11 Z2568 1 PTO Danger Decal 12 91369 003 1 515 RPM Decal 13 53113 001 1 WINCO Decal 14 62487 003 2 5 Loom 5 8 NI 300323 112 1 Capacitor 31 5 mf 425 V NI 300323 212 2 Capacitor 35 mf 450 V NI 300153 ...

Page 13: ...RANSPORT DESCRIPTION PART NO 1 SUPPORT TONGUE QTY 2 300081 2 HITCH TONGUE QTY 2 300082 3 TONGUE 300083 4 AXLE QTY 2 300085 5 SUPPORT AXLE 300164 6 SUPPORT PTO SHAFT 300161 1 7 SUPPORT PTO SHAFT 300161 2 8 TIRE RIM PNEUMATIC QTY 2 43657 000 ...

Page 14: ...allow the exclusion or limitation of incidental or consequential damages so that above limitation or exclusion may not apply to you This warranty gives you specific legal rights you may have other rights which vary from state to state This warranty is limited to bench labor and parts only no allowance will be made for travel time or removal and reinstallation of the PTO unit WINCO does not warrant...

Page 15: ...60706 180 0310 00 ...

Page 16: ...60706 180 0310 00 225 SOUTH CORDOVA AVE LE CENTER MN 56057 1 507 357 6831 ...

Reviews: