2270-00
8
60706-229
Shown below is a diagram of a natural gas (NG)
installation.
Reference numbers 2 through 4 in the diagram
above are system parts supplied by the customer.
Reference number 4 is on the generator.
Below are tables of the fuel pressure readings at
each reference in the system.
FUEL PRESSURE TABLES
Single Low Pressure Regulator (LP Vapor only)
REF #
1
3
4
UNIT OFF
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
STARTING
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO LOAD
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
Two (2) Regulator System (LP Vapor only)
REF #
1
2
3
4
UNIT
OFF
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
START-
ING
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO
LOAD
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
Natural Gas
REF #
2
3
4
UNIT OFF
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
STARTING
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO LOAD
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal
operating at various outside temperatures given in
degrees Fahrenheit (Celsius).
TANK TEMPERATURE
TANK SIZE
60° F (16° C)
150 GALLON
32° F (0° C)
250 GALLON
0° F (18° C)
500 GALLON
-20° F (-29° C)
1000 GALLON
NG/LP FUEL CONVERSION
These generator sets are factory tested on Natural
Gas and will require no modifications for normal
operation on Natural Gas. The carburetion system
has been preset and anti-tamper plugs have been
installed in the carburetor as required by the EPA.
To make a fuel conversion you will have to first
remove the left side door. Looking down to your left
you will see a decal and a plug. Remove the plastic
plug with a screwdriver. Using a 5mm or 3/6” hex
allen wrench turn
LEFT
about /4 turn until you feel
a click and it will stop turning.
No other modifications to the unit are necessary. To
switch from LP to NG you turn the selector to the
right (NG) position.
Summary of Contents for ULPSS20B2W/A
Page 1: ...12270 00 60706 229 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS20B2W A...
Page 10: ...12270 00 10 60706 229...
Page 18: ...12270 00 18 60706 229...
Page 22: ...12270 00 22 60706 229 ENGINE GENERATOR SET LAYOUT ULPSS20B2W A...
Page 23: ...23 12270 00 60706 229 ENGINE GENERATOR SET PAD LAYOUT...
Page 25: ...25 12270 00 60706 229 AC AND DC GENERATOR SCHEMATIC...
Page 26: ...12270 00 26 60706 229 AC WIRING SCHEMATICS ULPSS20 17 A ULPSS20 3 A...
Page 27: ...27 12270 00 60706 229 AC WIRING SCHEMATICS ULPSS20 18 A ULPSS20 4 A...