60706-229
DSE 3110 ENGINE CONTROL
PROTECTIONS
When an alarm is present, the Common alarm LED
(if configured) will illuminate.
The LCD display will
show an icon to indicate the failure.
WARNINGS
Warnings are non-critical alarm conditions and do
not affect the operation of the generator system;
they serve to draw the operators attention to an un-
desirable condition. Warning alarms are self-reset-
ting when the fault condition is removed. The icon
will appear steady in the display.
SHUTDOWNS
Shutdowns are critical alarm conditions that stop the
engine and draw the operator’s attention to an un-
desirable condition. Shutdown alarms are latching.
The fault must be removed and the STOP/RESET
button pressed to reset the module.
The icon will
appear flashing in the display.
MODULE DISPLAY
TIMER ICON
When the module is controlling the engine (start-
ing and stopping), an animated timer icon will be
displayed in the icon area to indicate that a timer is
active. For example, cranking time, crank rest, etc.
STOPPED ICON
When there are no alarms present, an icon will be
displayed to indicate the engine is stopped and what
mode the unit is in.
Stop Mode Auto Mode Manual Mode
RUNNING ICON
When there are no alarms present, an animated icon
is displayed to indicate the engine is running.
USB ICON
When a USB connection is made to the module the
USB icon is displayed.
MEMORY CORRUPTION
If either the config file or engine file becomes cor-
rupted, the unit will display the following icon.
PREVENTIVE
MAINTENANCE
Reasonable care in preventive maintenance will
insure high reliability and a long life for the engine
generator set and Automatic Transfer Switch.
*****************
***** WARNING *****
*****************
When performing any type of maintenance on this
equipment, make sure the selector switch on the en-
gine generator is in the off position. If you are work-
ing in the Automatic Transfer Switch, confirm with a
reliable meter that all power has been disconnected.
AUTOMATIC TRANSFER SWITCH
Clean and inspect the switch once a year. De-ener-
gize all power sources, both line and engine genera-
tor set, then brush and vacuum away any excessive
dust or dirt accumulation. At this time, with the
contactor de-energized, you can remove the contact
covers and check the contacts. Make sure contacts
are clean and not burned or pitted.
ENGINE GENERATOR SET
Service the engine in accordance with the engine
manufacturer’s manual provided with your new
equipment. Routinely remove debris and dirt from
around the inside generator enclosure. Insure that
the air intakes are free from leaves and other debris
at all times.
Clean and inspect battery terminals a least twice
a year. Also Check the battery water level at least
twice a year.
Other than keeping the generator clean and free
of debris, there is no other routine or preventative
maintenance required as long as the generator is
run biweekly to keep it dry and in good working
order.
COLD WEATHER OPERATION
Extreme cold weather operation requires special
considerations. Higher CCA batteries are required
for cold weather starting; 650 CCA or larger are rec-
ommended. In addition you should consider install-
ing an oil heater kit and a battery warmer for reliable
starting during cold weather.
Summary of Contents for ULPSS20B2W/A
Page 1: ...12270 00 60706 229 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS20B2W A...
Page 10: ...12270 00 10 60706 229...
Page 18: ...12270 00 18 60706 229...
Page 22: ...12270 00 22 60706 229 ENGINE GENERATOR SET LAYOUT ULPSS20B2W A...
Page 23: ...23 12270 00 60706 229 ENGINE GENERATOR SET PAD LAYOUT...
Page 25: ...25 12270 00 60706 229 AC AND DC GENERATOR SCHEMATIC...
Page 26: ...12270 00 26 60706 229 AC WIRING SCHEMATICS ULPSS20 17 A ULPSS20 3 A...
Page 27: ...27 12270 00 60706 229 AC WIRING SCHEMATICS ULPSS20 18 A ULPSS20 4 A...