Winco PSS50LS-*/A Series Installation And Operation Manual Download Page 5

60706-144

Page 3

1017-10

The engine manufacturer has established an excellent

world-wide engine service organization; engine service is
available from a nearby authorized dealer or distributor;
check the yellow pages of the telephone directory under
“engines,” or ask the dealer from whom you purchased the
power plant.

The rated power of each engine-generator is limited by

the temperature, altitude and all other ambient conditions
specified by the engine manufacturer.  Engine power will
decrease 3-1/2% for each 1000 ft. above sea level, and
will decrease an additional 1% for each 10 degrees Fahr-
enheit above 60 degrees Fahrenheit.

UNPACKING INSTRUCTIONS

** NOTICE **

When unpacking the generator set, be sure to inspect it

carefully for freight loss or damage.  If loss or damage is
noted at the time of delivery, require that the person mak-
ing the delivery make note of the loss or damage on the
freight bill, or affix his signature under the consigner’s
memo of the loss or damage.  Contact the carrier for claim
procedures.

When loss or damage is noted after delivery, segregate

the damaged material, and contact the carrier for claim
procedures.

“Concealed Damage” is understood to mean damage to

the contents of a package which is not in evidence at the
time of delivery by the carrier, but which is discovered
later.  The carrier or carriers are responsible for merchan-
dise lost or damaged in transit.  The title to goods rests
with the consignee when generators are shipped FOB fac-
tory, and only the consignee can legally file a claim.

****  CAUTION  ****

EQUIPMENT DAMAGE - The  PSS50000 and the

PSS65000 are shipped with oil, and a 50/50 mix of cool-
ant.  Be sure to check all fluid levels before operating.  See
engine manufacturer’s instruction manual for recom-
mended oil requirements before initial starting.

UNPACKING:

1. Carefully remove the carton.
2. After inspecting the engine-generator for external

physical damage, check for the following items packed
inside the carton.
a. Owner’s manual, wiring diagram, and parts list.
b. Engine manufacturer’s instruction manual.

3. Remove main frame hold down bolts (4).
4. Unit can now be lifted from shipping rails.

water temperature shutdown has a 60 to 90 second lock-
out, allowing the engine time to clear the hot water out of
the block in case of a hot restart.   In addition if the genera-
tor should lose output during a run cycle the engine will
continue to run for about 60 seconds and then shutdown
and display an overcrank light. The starter will not reen-
gage during this time or until the generator selector switch
has been cycled off and back on.  This is the only way to
clear a fault light.

** NOTICE **

These units will automatically transfer if a power outage

occurs while running in an exercise mode.

SPECIFICATIONS

GENERATOR

MODEL

 WATTS

VOLTS

AMP

HZ

PH

RPM

PSS50000

50,000

120/240

208

60

1

1800

PSS50000-4

50,000

120/208

174

60

3

1800

PSS50000-17

50,000

120/240

151

60

3

1800

PSS50000-18

50,000

277/480

72

60

3

1800

PSS65000

65,000

120/240

271

60

1

1800

PSS65000-4

65,000

120/208

226

60

3

1800

PSS65000-17

65,000

120/240

196

60

3

1800

PSS65000-18

65,000

277/480

98

60

3

1800

*Derate 10% for Natural Gas operation.  Derate 3.5% per
1000 feet elevation above sea level.

FUEL CONSUMPTION

         NG  (1,000 BTU/CU FT)    L.P. VAPOR  (2,520 BTU/CU FT)
MODEL

CF/HR

BTU/HR

#/HR GAL/HR CF/HR BTU/HR

PSS50000

725

725,000

42.3

10.0

353

889,560

PSS65000

940

940,000

48.7

11.5

406

1,024,000

L.P. TANK SIZING

Minimum required L.P. Tank size for L.P. Vapor with-

drawal operating at various outside temperatures given in
degrees Fahrenheit (Celsius)

         TANK TEMPERATURE

MODEL

60 F(16 C) 30 F(0 C)

 0 F(-18 C)

-20 F(-29 C)

PSS50000

500 Gal.

1000 Gal.

1500 Gal.*

9000 Gal.*

PSS65000

500 Gal.

1000 Gal.

2500 Gal.*

9000 Gal.*

  *Recommend liquid withdrawal at these temperatures.

ENGINE SPECIFICATIONS:

  Refer to engine operating and maintenance instructions

** NOTICE **

Regarding Engines - This manual covers the generator

portion of these units.  See the separate engine instruction
manual for engine-related problems, detailed engine infor-
mation and engine warranty.

**  CAUTION  **
EQUIPMENT DAMAGE - 
Be sure to check the engine oil

level frequently as specified in the engine manual.

Summary of Contents for PSS50LS-*/A Series

Page 1: ...Engine Generator Set 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507 357 6831 PACKAGE STANDBY SYSTEMS Automatic Transfer Switch PSS50LS A PSS65LS A PSS50LS B PSS65LS B INSTALLATION AND OPERATIONS MANUAL...

Page 2: ...understand all instructions in the manual before starting and operating the gen erator set USING THIS MANUAL Congratulations on your choice of a Winco generator set You have selected a high quality p...

Page 3: ...jury or death e Always avoid hot mufflers exhaust manifolds and engine parts They all can cause severe burns instantly f Installing a generator set is not a do it yourself project Consult a qualified...

Page 4: ...engine operates at 1800 rpm and frequency regulation is maintained by the engine governor within 5 cycles variation from no load to rated load The 50 000 watt 50kW generator is a single bearing direct...

Page 5: ...s manual wiring diagram and parts list b Engine manufacturer s instruction manual 3 Remove main frame hold down bolts 4 4 Unit can now be lifted from shipping rails water temperature shutdown has a 6...

Page 6: ...tion in this manual is offered to assist you in providing the proper fuel for your engine However this information is only provided to inform you of the engine s requirements and assist in making you...

Page 7: ...nit En gine generator sets equipped for liquid withdrawal will not run properly when supplied with high pressure va por fuel The following is a block diagram of a typical L P Liquid Withdrawal fuel sy...

Page 8: ...s connected to the negative cable ground from the engine generator assembly NOTE Alway make sure that a new battery is fully charged before installing it on a generator set Failure to do so can cause...

Page 9: ...ngle phase units have 400 Amp line side contactors installed to handle your normal power needs and a 320 Amp generator side contactor to handle the emergency generator output For the three phase 240 v...

Page 10: ...1 G2 G3 and G N on the three phase units WARNING EQUUIPMENT DAMAGE When installing a Three Phase 240 volt system be sure you know which lead is the high voltage wild leg 208Volt line to neutral The ge...

Page 11: ...L START UP WARNING EQUIPMENT DAMAGE DO NOT jump start these en gine generator sets Starting these units on a low battery or jump starting them will cause damage to the engine control module Use the fo...

Page 12: ...h the generator set and transfer selector switches in the AUTOMATIC position SETTING THE EXERCISER CLOCK Setting the current time and date 1 Position the top right hand RUN slide switch to the left po...

Page 13: ...rminals 7 Defective Run Auto switch on generator 8 Defective starter 9 Defective start solenoid 10 Defective remote start solenoid 11 Locked up engine genset ENGINE CRANKS BUT WILL NOT START 1 Imprope...

Page 14: ...ormally require no adjustment If for some unforeseen reason the machine should require adjustment follow the above procedure FUEL TYPE CONVERSION If it should be necessary to change the type of fuel b...

Page 15: ...fuel line at the regulator 8 Remove the 1 8 NPT plug the one closest to fuel solenoid located on what is now the bottom of the regulator Connect a fuel pressure meter or a monometer where the plug ha...

Page 16: ...LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS Lead Cross Ref U L1 V L2 W L3 N N U1 T1 U2 T4 U5 T7 U6 T10 V1 T2 V2 T5 V5 T8 V6 T11 W1 T3 W2 T6 W5 T9 W6 T12 Lead Cross Ref U L1 V L2 W L3 N N...

Page 17: ...LTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS Lead Cross Ref U L1 V L2 W L3 N N U1 T1 U2 T4 U5 T7 U6 T10 V1 T2 V2 T5 V5 T8 V6 T11 W1 T3 W2 T6 W5 T9 W6 T12 Lead...

Page 18: ...Page 16 1017 10 60706 144 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE CONTROL PANEL WIRING THREE PHASE AND SINGLE PHASE SINGLE PHASE THREE PHASE...

Page 19: ...60706 144 Page 17 1017 10 DC SCHEMATIC...

Page 20: ...Page 18 1017 10 60706 144 CONTROL PANEL WIRING THREE PHASE CONTROL PANEL WIRING SINGLE PHASE...

Page 21: ...60706 144 Page 19 1017 10 CONTROL PANEL...

Page 22: ...including those of merchantability and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some sta...

Reviews: