background image

Page 6

3113-00

60706-156

Notice the preceding tables give two (2) different units of measur-
ing fuel pressure.  The first is with a pressure gauge calibrated in
ounces per square inch.  The second and most accurate is the
use of a simple water manometer.  A manometer is calibrated in
inches of water column.

LP LIQUID WITHDRAWAL SYSTEMS

When installing a unit equipped the LP liquid withdrawal a
primary regulator is not required on the supply tank.   The supply
line is connected to a liquid withdrawal valve on the supply tank
and run directly to the fuellock strainer mounted on the engine
generator set.  Normally a 3/8 inch copper line is acceptable for
this type of fuel installation.  You must be sure that the valve you
have connected to on the supply tank is in fact a liquid supply
valve and has a drop tube inside the tank that is pulling fuel from
the bottom of the supply tank.  Before starting the unit you must
confirm that you have a good liquid supply at the unit.  Engine
generator sets equipped for liquid withdrawal will not run
properly when supplied with high pressure vapor fuel.

LUBRICATION

Before starting the engine, check the oil level in the crankcase. If
it is low, refill to the full mark with the proper weight/grade of oil as
recommended by the engine manufacturer’s maintenance
instructions.  The necessity of using the correct oil, and keeping
the crankcase full cannot be over emphasized.  Failure to use the
proper oil and keep the crankcase properly filled will cause
excessive engine wear and shorten its useful life.

COOLANT

Before starting the engine, check the coolant level in radiator. If it
is low, refill as specified in the engine manufacturer’s mainte-
nance instructions.  The radiator should be filled to about 1 inch
below the filler neck. For additional information on engine coolant
requirements see engine manufacturer’s maintenance instruc-
tions.

INSTALLING THE BATTERY

****  CAUTION  ****

EQUIPMENT DAMAGE - In the following battery installation
procedure, check to be sure the selector switch remains in the
“stop” position.

A customer supplied twelve-volt BCI group 24 battery rated 650
CCA  (minimum) is required to complete the installation. Install
the highest CCA rated battery available for best cold weather
starting performance.

****WARNING*****

EQUIPMENT DAMAGE - Always connect the positive battery
cable first and the negative cable last.  When disconnecting a
battery always disconnect the negative cable first and the positive
cable last.  Failure to follow these steps can cause arcing at the
battery post which can cause damage to both the engine and the
engine control module.

Observe polarities:  Connect the positive (+) battery terminal to
the (+) cable from the control panel; the negative (-) battery
terminal is connected to the negative cable (ground) from the
engine  generator assembly.

NOTE: Always make sure that a new battery is fully charged
before installing it on a generator set.  Failure to do so can cause
damage to the engine control module in the generator set.

All connections must be clean and tight.  Check the electrolyte
(fluid) in the battery periodically to be sure it is above the plates.
Never allow the battery to remain in a discharged condition.

CONNECTING THE BATTERY CHARGER &
BLOCKHEATER

A two-stage battery tender is provided on all PSS series genera-
tors.  This battery tender charges at a rate of 750 mA until the
battery is fully charged and then automatically switches to a 13.2
VDC float charger.  The charger has an indicator light on it, red
indicates it is charging, and green indicates it is in the storage
mode (float charge).  This charger is mounted on the engine
generator set just below the engine control panel.

** NOTICE **

The trickle charger is not intended to recharge a battery which
has  become completely discharged.  It is designed to produce
just enough current to maintain a fully charged battery.

This battery tender requires a circuit breaker protected AC circuit
from your distribution panel be run out to the engine generator
set.  These AC wires can be run in the same conduit as the other
AC leads from the generator.  It is suggested that this circuit be
fused for 15 amps, then both the battery charger and the block
heater can be connected to the same circuit.  A 120 volt duplex
receptacle is mounted on the generator just below the engine
control panel, the battery tender is shipped already plugged into
the receptacle.

The engine frost plug heater has been prewired with a 120 volt
plug which can be plugged into the other side of the duplex
receptacle after wiring 120 volt power feed to the receptacle. The
frost plug heater has been prewired through a temperature
sensor which will turn the heater on when the air temperature
drops to  22 degrees F. and off when the air temperature reaches
30 Degrees F.

MOUNTING THE AUTOMATIC TRANSFER SWITCH
(WINCO Non-UL only)

The automatic transfer switch (A.T.S.) connects the load (lights,
furnace, outlets, etc.) to the normal power line.  When normal
power fails, the A.T.S. starts the engine generator set, discon-
nects the power line and then connects the load to the standby
generator set.  When normal power is restored, the automatic
switch retransfers the electrical load to the normal service and
stops the engine.  The A.T.S. panel should be mounted as close
to the distribution panel as possible.

Summary of Contents for PSS50LC

Page 1: ...ine Generator Set 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507 357 6831 PACKAGE STANDBY SYSTEMS PSS50LS C PSS75LS A INSTALLATION AND OPERATIONS MANUAL for UNITS EQUIPPED WTH BASLER DIGITAL GENSET CONTROLS ...

Page 2: ...ed electrician Operated only for its designed purposes Used only by operators who understand its operation Properlymaintained Read and understand all instructions in the manual before starting and operating the generator set USING THIS MANUAL Congratulations on your choice of a Winco generator set You have selected a high quality precision engineered generator set designed and tested to give you y...

Page 3: ...rts They all can cause severe burns instantly f Installing a generator set is not a do it yourself project Consult a qualified licensed electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or water hoses SAFETY INFORMATION This engine generator set has been...

Page 4: ...cessary to send a start stop signal to the engine generator set 2 ENGINE GENERATOR PSS50LS The engine generator set consists of a GM 5 7L V 8 industrial liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The 50 000 watt 50kW generator is a single ...

Page 5: ...er Failure Enabled Magnetic Pickup Failure Enabled During normal operation the DGC will continuously display the engine oil pressure coolant temperature and the battery voltage reading By pressing the Phase Toggle push button you can toggle through the different phases checking the generator output and amperage reading on each phase The DGC has three operational push buttons You can tell which pos...

Page 6: ...it under the unit may cause the unit to overheat from lack of proper air flow Before beginning the installation process recheck the rating of the generator set and its transfer switch rating Be certain they can handle the intended load and are compatible with the entrance voltage phase and current ratings Plans for installation should be prepared with proper attention to mechanical and electrical ...

Page 7: ...ange the fuel type in the field see information on page 10 Line Size vapor system Unit location will determine the size of fuel line that is required to supply the engine with a constant fuel pressure Refer to the tables below for fuel line size fuel consumption and recom mended tank size For distances of 25 feet and over a two regulator fuel system is recommended This is accomplished by installin...

Page 8: ...e damage to both the engine and the engine control module Observe polarities Connect the positive battery terminal to the cable from the control panel the negative battery terminal is connected to the negative cable ground from the engine generator assembly NOTE Always make sure that a new battery is fully charged before installing it on a generator set Failure to do so can cause damage to the eng...

Page 9: ... instruments before proceeding A C ELECTRICAL CONNECTIONS WINCO Non UL Only Single Phase The standby generator terminals in the A T S are marked GENERATOR G1 G N G3 The hot leads G1 and G3 wire directly to the top lugs on the generator side contactor terminals G1 and G3 The G N connection is made to the lug on the standoff just to the right of the generator side contactor The line terminals in the...

Page 10: ...ed under emergency power failure conditions an additional distribution panel designated emergency distribution panel must be installed All selected emergency circuits are removed from main distribu tion panels and installed in the emergency distribution panel The A T S is then installed between the main panel and the emer gency distribution panel Suggested circuits freezer refrigerator furnace eme...

Page 11: ...he same as it was on the generator front panel The voltage should also be checked between the hot terminals G1 and G3 and the G N to be certain of a balanced voltage output and a solid neutral connection The voltage between G1 and G N should be about 120 volts AC 277 on 480 units The same approximate voltage should be found between terminals G3 and G N 120 volts AC On three phase panels the G2 vol...

Page 12: ...tart up 6 Press the Program Select Button until number 2 is dis played on the clock 7 Push the Day Select Button to select the day you want the engine to stop This must be the same day you selected in step 4 above 8 With the Hour and Minute buttons select the time you want the engine to stop It is recommended you let the engine run at least 15 minutes during any exercise period 9 Position the top ...

Page 13: ...ror between generator and transfer switch 5 Defective start stop relay ATS PANEL WILL NOT RETRANSFER TO NORMAL POWER 1 Proper normal line power not available at line terminals in ATS panel 2 Defective holding coil in line side contactor 3 Broken or defective mechanical electrical interlocks 4 Defective start stop relay NO AC OUTPUT FROM GENERATOR 1 Defective diode 2 Defective voltage regulator 3 D...

Page 14: ...E LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS Lead Cross Ref U L1 V L2 W L3 N N U1 T1 U2 T4 U5 T7 U6 T10 V1 T2 V2 T5 V5 T8 V6 T11 W1 T3 W2 T6 W5 T9 W6 T12 Lead Cross Ref U L1 V L2 W L3 N N U1 T1 U2 T4 U5 T7 U6 T10 V1 T2 V2 T5 V5 T8 V6 T11 W1 T3 W2 T6 W5 T9 W6 T12 ...

Page 15: ...ELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS Lead Cross Ref U L1 V L2 W L3 N N U1 T1 U2 T4 U5 T7 U6 T10 V1 T2 V2 T5 V5 T8 V6 T11 W1 T3 W2 T6 W5 T9 W6 T12 Lead Cross Ref U1 L1 U6 L3 N N U1 T1 U2 T2 U5 T3 U6 T4 ...

Page 16: ...Page 14 3113 00 60706 156 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE ...

Page 17: ...60706 156 Page 15 3113 00 DC SCHEMATIC ...

Page 18: ...Page 16 3113 00 60706 156 PSS50 75LS OUTLINE DRAWING AND WIRING ENTRANCE ...

Page 19: ...l warranties including those of merchantability and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limita tions m...

Page 20: ...225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone 507 357 6831 Fax 507 357 4857 Website www wincogen com 60706 156 3113 00 ...

Reviews: