background image

10

REV B

OPM-111

Wire Temperature Rating

Cu Conductor

Al Conductor

kW

Volts

PH Amp

75°C

90°C

75°C

90°C

21

120/240

1

90

#2 AWG #3 AWG 1/0 AWG #2 AWG

21

120/208

3

80

#3 AWG #4 AWG #2 AWG #3 AWG

21

120/240

3

80

#3 AWG #4 AWG #2 AWG #3 AWG

22

277/480

3

35

#8 AWG #8 AWG #4 AWG #6 AWG

30/27 120/240

1

125 1/0 AWG #1 AWG 3/0 AWG 2/0 AWG

30/28 120/208

3

100 #2 AWG #3 AWG 1/0 AWG #1 AWG

30/28 120/240

3

100 #2 AWG #3 AWG 1/0 AWG #2 AWG

30/28 277/480

3

45

#6 AWG #8 AWG #4 AWG #6 AWG

For additional information on wire sizing refer to table 310-16 of the 

National Electrical Code ANSI/NFPA 70.

C - Ground Lug, These ground lugs are bonded to ground and are 

provided for you to connect your ground wire from the transfer switch 

to. The lugs on the 21/30 kW will accommodate #6 AWG to 250 MCM 

and should be torqued to 50 in. lbs.

D. 120 Volt Terminal Block. These terminals are for shore power. For a 

power line with one lead, plug into either terminals, ensuring the jumper 

is still connected. To isolate two leads for use of two separate circuit 

breakers, the jumper must be removed.

WARNING: EQUIPMENT DAMAGE:

When installing a three-phase 240 Volt system, be sure you know 

which lead is the high voltage “wild” leg (208 Volt to neutral). The 

generator normally carriers the high voltage on the G2 lead.

The load current carrying wires (L) and (T) must be sized to handle 

the maximum load current without excessive voltage drop. By code, 

the wire must be heavy enough to handle the full current rating of 

the mainline circuit breaker (or fuse) in the entrance (or sub-panel) 

protecting the contactor switch.

All wires should be installed in rigid or flexible conduit. (knockouts are 

provided in the control box).

GROUNDING

A grounding lug has been provided on the engine generator set. Check 

your local codes for proper grounding requirements.

AC ELECTRICAL CONNECTIONS

NOTICE:  

CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD 

WIRING CONNECTIONS TO TERMINAL OF A CLASS 2 CIRCUIT.

WARNING:

A mainline circuit breaker has been provided inside the generator 

housing. During all wiring installation, make sure the breaker is in the 

off position and the generator operators switch is in the off position. 

A - Neutral Lugs, These neutral lugs are isolated from ground and 

provided for you to connect your neutral wire from the transfer 

switch. The lugs on the 21 kW will handle wire sizes #12 AWG to 2/0 

AWG and should be torqued to 50 in lbs. The lugs on the 30 kW will 

accommodate #12 AWG to 2/0 AWG and should be torqued to 50 in 

lbs.

B - Generator Circuit Breaker, This circuit breaker provides overload 

protection for the generator. Your power feeds from the transfer switch 

will connect to the bottom lugs on the circuit breaker. The generator 

power feeds have already been wired into the upper lugs.

The table below gives you the circuit breaker size, lug wire sizes and 

torque specification. (see the actual breaker for additional information 

and restrictions)

kW

Volts

PH

Amp

Wire Capability

Lug Torque

21

120/240 1

90

#12 AWG-2/0 AWG

50 in lbs

21

120/208 3

80

#12 AWG-2/0 AWG

50 in lbs

21

120/240 3

80

#12 AWG-2/0 AWG

50 in lbs

22

277/480 3

35

#14-#10 AWG

80 in lbs

30/27 120/240 1

125

#12 AWG-2/0 AWG

50 in lbs

30/28 120/208 3

100

#12 AWG-2/0 AWG

50 in lbs

30/28 120/240 3

100

#12 AWG-2/0 AWG

50 in lbs

30/28 277/480 3

45

#14-#10AWG

80 in lbs

The previous table shows the minimum conductor sizes between the 

generator and the ATS, based on wire type and temperature rating. 

Wire has been derated 40° C ambient temperatures.

 A

 

C

 

B

 

D

Summary of Contents for PSS21/F

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS21 F PSS30 F GENERATOR MANUAL...

Page 2: ...ting instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in the manual describes what you can expect fr...

Page 3: ...d container and only in a well ventilated area F Follow local codes for closeness to combustible material 3 DEADLY EXHAUST GAS Exhaust fumes from any internal combustion engine contain carbon monoxide...

Page 4: ...er Rotor L N 0 106 Ohms Per Ph 22 C Exciter Stator L N 15 42 Ohms 22 C Aux Winding 2 570 Ohms 22 C Voltage Regulator L N AS540 PSS30 F LP Gas Wattage 30 000 30 000 30 000 30 000 Volts 120 240 120 208...

Page 5: ...osure for outside installation Connection boxes are provided to all customer connections both AC output and DC control A customer supplied 12 Volt 650 CCA BCI group 24 battery is required to complete...

Page 6: ...high as long as they are structurally sound supporting the weight of the unit and preventing movement during operation The mounting holes on the base of this unit is 0 625 in diameter The engine gene...

Page 7: ...ructions in the regulator or fuel valve The results could range from inoperative engine to hazardous fuel leaks CAUTION Be careful when sealing gas joints Excessive sealing compound can be drawn into...

Page 8: ...11 in 4 6 oz 7 11 in 4 6 oz No load Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Two regulator system LP vapor only Ref 1 2 3 4 Unit off Line PSI 10 15 lbs...

Page 9: ...negative battery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically...

Page 10: ...rovided in the control box GROUNDING A grounding lug has been provided on the engine generator set Check your local codes for proper grounding requirements AC ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIR...

Page 11: ...ring instructions can be provided It is recommended that only copper wire be used In all cases it is essential that while the load is connected to the generator there can be absolutely no feedback fro...

Page 12: ...ints in the ASCO 300 ATS are terminals DQG HSHQGLQJ RQ WKH VL H RI WKH VZLWFK WKH DUH located in different locations TB7 removable terminal block TB7 4 TB7 5 TB7 6 1 2 3 4 5 6 7 8 9 Figure 4 TB7 gener...

Page 13: ...ency on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next ste...

Page 14: ...ect speed 7 Defective ECU on the engine ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS 1 Insufficient fuel volume getting to the unit a Fuel line too small b Low fuel pressure 2 AC short circuit 3 D...

Page 15: ...elector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm with a reliable meter that all power has been disconnected AUTOMATIC TRANSFER...

Page 16: ...16 REV B OPM 111 PSS21 AND PSS30 OUTLINE DRAWING ENCLOSED OPEN SKID...

Page 17: ...H AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING DELT...

Page 18: ...111 ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 35...

Page 19: ...7 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 8...

Page 20: ...enance consumables or labor This warranty only covers travel time that has been pre approved by the WINCO Service Department Mileage or labor for removal or re installation of WINCO product from its a...

Reviews: