Winco DR2014 Installation And Operator'S Manual Download Page 12

12

OPM-109

REV A

TROUBLESHOOTING TABLE

Problem

Possible Causes

Unit will not crank when power fails

Digital genset not in AUTO

Transfer control switch not in 

  AUTOMATIC position

Incorrect wiring between ATS and genset

Defective control relay in ATS

Fuse(s) blown in the DSE7310

Defective DSE7310

Loose or dirty battery terminals

Defective starter

Defective start solenoid

Low/dead battery

Engine won’t crank

Low/dead battery

Blown DC fuses

Defective DSE7310

Defective key switch

Loose or dirty battery terminals

Defective starter

Defective start solenoid

Locked up engine genset

Defective engine harness

Improper battery voltage to start solenoid, 

  fuel pump, or fuel solenoid

Engine cranks but will not start

Improper fuel delivery to the unit

Fuel supply shut off

Fuel tank empty

Air in the fuel system

Engine fuel solenoid has not opened

Defective fuel pump

Defective fuel solenoid

Defective engine harness

Improper battery voltage to fuel pump or 

  fuel solenoid

Engine starts, then stops and alarm 

light comes on

Engine oil pressure is low

Engine has high water temperature

Engine has overspeed

Engine has gone into overcrank

No output from AC generator

Loss of speed signal

Loss of run signal

Engine will not come up to speed 

after it starts

Insufficient fuel volume getting to the unit

  1. Too small of fuel line

    2. Fuel racks not open properly

  Governor is defective

  AC short in generator components

ATS will not transfer to Emergency 

Supply (generator)

No AC generator output

Defective ATS control board. See ATS 

 manual

Circuit breaker open or defective

ATS will not re-transfer to normal 

power

Proper power line not available at line 

  terminals in ATS panel

Defective ATS control board. See ATS 

 manual

No AC output from generator

Defective diode

Defective voltage regulator

Defective rotor

Defective stator

Defective exciter rotor

Defective exciter stator

AC short in the output leads

Defective/open generator output breaker

Wiring error

VOLTAGE REGULATOR WIRING

AS480 Automatic Voltage Regulator

The following is a list of connections on the AVR. These have been 

factory set and other than voltage adjustment, should never be 

changed.

1. Generator AC sensing connection (6,7, & 8)

  Field voltage DC (F1 & F2)

2. Voltage adjustment

3. External voltage treatment rheostat.

  No external rheostat - link 1 & 2

  With external rheostat - 1 & 2 unlinked, connect external rheostat 

    leads to 1 & 2

4. AVR input selection

  High voltage 208/240/277 - no link between 3 & 4

  Low voltage 120 - link 3 & 4

5. Under Frequency Roll Off adjustment

6. Under Frequency Roll Off indication light

7. Frequency selection:

  50 Hz operation - link C to 50

  60 Hz operation - link C to 60

8. Stability control

8

1

2

3

4

50

60

C

7

6 F1 F2

1

3

4

6

7

8

5

2

AR480

Summary of Contents for DR2014

Page 1: ...DESCRIPTION DATE BY APP D A C4023 ORIGINAL 9 15 2016 ASC ZJF NUMBER 08 165 500 ONE MANUAL ONE ONE CHK D BY ENG APPR TITLE DR20I4 AAS J DATE DATE DATE DRAWN BY MODEL PART ASC THIS DRAWING CONTAINS PROP...

Page 2: ...nd maintenance of the generator Read and understand all instructions in the manual before starting and operating the generator USING THIS MANUAL Congratulations on your choice of a WINCO generator You...

Page 3: ...ctions can be found further in this manual The key start version does not have this option SAFETY INFORMATION This engine generator set has been designed and manufactured to allow safe reliable perfor...

Page 4: ...are oriented from a TOP plan VIEW with engine at the FRONT and generator to the REAR WINPOWER uses a common junction box for all customer control and power connections both AC output and DC control T...

Page 5: ...or generator end These lifting points are only for the use during the manufacturing process and are designed for lifting of the individual generator set components WARNING NEVER attempt to lift the f...

Page 6: ...ONAL INJURY Before proceeding with the installation be sure the DSE7310 is in the stop position Before proceeding with the installation be sure the Generator MLCB Main Line Circuit Breaker is in the O...

Page 7: ...l eye protection and protective clothing 2 Where electrolyte contacts skin wash off immediately with water 3 If electrolyte contacts the eyes flush thoroughly and immediately with water and seek immed...

Page 8: ...articular attention to wire size requirement for the amperage of service you are dealing with The table below provides you guidance on wire sizing based on both wire type and amperage Wire amperages h...

Page 9: ...driven into the earth wil provide a proper earth ground labeled START is your remote start lead Closing these two leads together will signal the DSE7310 to go into an autostart mode and start up the g...

Page 10: ...cklist and ensure the generator mainline circuit breaker is in the proper position prior to starting Starting this unit without it properly connected can cause serious personal injury or equipment dam...

Page 11: ...three phase motors to spin backwards possibly damaging them NOTICE If for any reason during the check out procedure the voltage and frequency are not correct depress the STOP RESET button and correct...

Page 12: ...s Insufficient fuel volume getting to the unit 1 Too small of fuel line 2 Fuel racks not open properly Governor is defective AC short in generator components ATS will not transfer to Emergency Supply...

Page 13: ...5 418 431 458 480 519 550 572 585 50 68 86 100 118 137 155 177 205 237 264 291 319 346 391 432 473 487 505 532 560 605 642 669 683 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 1...