Page 7: ...ta 16 5 4 Min inlet pressure 17 5 5 Scope of delivery 18 5 6 Accessories 18 5 7 Functional extension 18 6 Installation 19 6 1 Personnel qualifications 19 6 2 Operator responsibilities 19 6 3 Safety 19...

Page 8: ...Subject to change Wilo shall reserve the right to change the listed data without notice and shall not be liable for technical inac curacies and or omissions The illustrations used may differ from the...

Page 9: ...and damage to property which are displayed in different ways Safety instructions relating to personal injury start with a signal word and are preceded by a corresponding symbol Safety instructions rel...

Page 10: ...ified technician who is trained in the use of the necessary tools and fixation materials The product must be operated by persons who are instructed on how the complete system functions Definition of q...

Page 11: ...Train personnel with regard to the operating principles of the sys tem Provide the necessary protective equipment and make sure that personnel wear it Eliminate any risk from electrical current Equip...

Page 12: ...oducts falling out may cause personal injury 3 1 Transport inspection Check delivery immediately for damage and completeness Where necessary make a complaint immediately 3 2 Transport and storage cond...

Page 13: ...y de pending on the mixing ratio percentage NOTICE Use other fluids only after approval by WILO SE Permitted temperatures 20 C 110 C WARNING Health hazard due to materials not approved for drinking wa...

Page 14: ...rised conversions Never operate with phase angle control Use authorised Wilo accessories and genuine spare parts only 4 3 Safety instructions Electrical current DANGER Electric shock The pump is opera...

Page 15: ...efficiency pumps Wilo Yonos MAXO Wilo Yonos MAXO D and Wilo Yonos MAXO Z in the version with flange or threaded pipe union are glandless pumps with a permanent magnet rotor and integrated differ enti...

Page 16: ...e connection DN 32 0 5 11 0 5 Minimum delivery head in m 11 Maximum delivery head in m at Q 0 m h 5 3 Technical data Technical data Yonos MAXO D Specification Value Permissible fluid temperature 20 C...

Page 17: ...5 Mains voltage 1 230 V 10 50 60 Hz Residual current I 3 5 mA Electromagnetic compatibility Interference emission in acc with EN 61800 3 2004 A1 2012 residential environment C1 Interference immunity i...

Page 18: ...pe of delivery Pump 8x washer M12 only flange end pump 8x washer M16 only flange end pump 2x flat gasket only threaded pipe union pump Installation and operating instructions 5 6 Accessories Wilo Conn...

Page 19: ...e associations Provide protective equipment and ensure that the protective equip ment is worn by personnel Observe all regulations for working with heavy loads 6 3 Safety WARNING Risk of burns from ho...

Page 20: ...nd downstream of the pump 7 Comply with the inlet and outlet sections in front of and behind the pump 8 Make sure that the pump can be installed free of mechanical stresses 9 Allow a 10 cm distance ar...

Page 21: ...eaded pipe unions 2 Close the shut off valves in front of and behind the pump Fig III 3 Insert the pump into the pipe together with the supplied flat gaskets 4 Screw together the pump with the union n...

Page 22: ...thread must project by at least one pitch of screw thread from the screw nut Perform leakage test at maximum permissible operating pressure Screws and tightening torques Flange end pump PN 6 DN 32 DN...

Page 23: ...on positions see chapter Permissible installation positions 2 Dismantle motor head and carefully turn Do not remove the motor head from the pump housing 3 Subsequently tighten motor fastening screws d...

Page 24: ...uch as cardiac pacemakers insulin pumps hearing aids implants or similar are at risk Death severe injury and damage to property may be the result A professional medical assessment is always necessary...

Page 25: ...es via mains voltage 100 24 h 20 h for a switching frequency of 1 min between switching on off via mains voltage If a residual current device RCD is used it is recommended to use an RCD type A pulse c...

Page 26: ...of fatal electrical shock Danger to life through voltage transmission if mains and SSM pipe are led together through a 5 wire cable Do not connect SSM pipe to protective low voltage Connection values...

Page 27: ...uids with admixtures property damage can occur due to the accumulation of chemicals Flush system before commissioning Flush out the pump before pouring in refilling or replacing fluid Remove the pump...

Page 28: ...losses p v Heating ventilation air condi tioning Constant volume flow Hot water priority c3 Manual night setback via speed stage alignment c1 Constant speed c1 c2 c3 Heating ventilation air condi tion...

Page 29: ...d is preset to of the maximal re quired delivery head see pump data in the catalogue Adjust operating mode and pump output according to system requirements Adjust the settings In the design the system...

Page 30: ...ich is also present at the motor contacts Close the existing shut off valves in front of and behind the pump If the control module Wilo plug is damaged the pump must not be put into operation In case...

Page 31: ...c field When dismantled the permanent magnet rotor inside the pump can pose a risk of fatal injury for people with medical implants e g pacemakers Never remove the rotor If the unit consisting of impe...

Page 32: ...reverse order of dismantling 1 Insert the motor into the centring of the pump housing and insert the four motor fastening screws into the threaded holes 2 Tighten motor fastening screws diagonally Obs...

Page 33: ...Check the delivery head and adjust where necessary Hot water does not get warm within a short period of time Setpoint set too low Increase setpoint Hot water does not get warm within a short period of...

Page 34: ...fluid running through them Check system E11 Pump running dry Air in the pump Check fluid pressure and volume E21 Overload Slow motor Pump is operated beyond its specifications e g high module temperat...

Page 35: ...ts in question Hand over these products at designated certified collection points only Observe the locally applicable regulations Please consult your local municipality the nearest waste disposal site...

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......