![Wilo Yonos GIGA-N 125-5,5 Installation And Operating Instructions Manual Download Page 69](http://html1.mh-extra.com/html/wilo/yonos-giga-n-125-5-5/yonos-giga-n-125-5-5_installation-and-operating-instructions-manual_983047069.webp)
Faults, causes and remedies
en
Installation and operating instructions Wilo-Yonos GIGA-N
69
Classification
No.
Fault
Cause
Remedy
Error type
Electronic
module error
E030
Excess elec-
tronic module
temperature
Restricted air
supply to heat
sink of elec-
tronic module
Provide unob-
structed air ac-
cess
B
A
E031
Hybrid/power
section excess
temperature
Ambient tem-
perature too
high
Improve room
ventilation
B
A
E032
Intermediate
circuit under-
voltage
Voltage fluctu-
ations in the
mains
Check elec-
trical installa-
tion
F
D
E033
Intermediate
circuit over-
voltage
Voltage fluctu-
ations in the
mains
Check elec-
trical installa-
tion
F
D
E035
DP/MP: mul-
tiple instances
of same iden-
tity
Multiple in-
stances of
same identity
Reallocate
master and/or
slave (see
“Twin-head
pump installa-
tion/Y-pipe in-
stallation”
chapter)
E
E
Communica-
tion errors
E050
BMS commu-
nication
timeout
Bus commu-
nication inter-
rupted or timed
out, cable
breakage
Check cable
connection to
building auto-
mation
F
F
E051
Impermissible
DP/MP com-
bination
Different
pumps
Contact cus-
tomer service
F
F
E052
DP/MP com-
munication
time-out
MP communic-
ation cable de-
fective
Check cable
and cable con-
nections
E