Operation
en
Installation and operating instructions Wilo-Yonos GIGA-N
51
No.
Designation
Type Symbol
Values/explanations
Display conditions
5.2.1.0
LON/CAN/IF-
Module Wink/
Service
±
The wink function permits the identifica-
tion of a device in the BMS network. A
“wink” is executed by confirmation.
Only displayed when LON, CAN or
IF module is active
5.2.2.0
Local/remote
operation
±
BMS local operation
Temporary state, automatic reset
to remote operation after 5 min
BMS remote operation
5.2.3.0
Bus address
±
Setting of bus address
5.2.4.0
IF gateway val A
±
Specific settings of the IF module, de-
pending on protocol type
Further information can be found
in the installation and operating in-
structions of the IF modules
5.2.5.0
IF gateway val C
±
5.2.6.0
IF gateway val E
±
5.2.7.0
IF gateway val F
±
5.3.0.0
In1 (sensor in-
put)
Settings for sensor input 1
Not displayed in constant speed
mode (incl. all sub-menus)
5.3.1.0
In1 (sensor value
range)
Display of sensor value range 1
Not displayed with PID-Control
5.3.2.0
In1 (value range)
±
Setting of value range; possible values:
0...10 V/ 2...10 V/0...20 mA/4...20 mA
5.4.0.0
In2
Setting for external setpoint in-
put 2
5.4.1.0
In2 active/inac-
tive
±
ON
External setpoint input 2 active
OFF
External setpoint input 2 inactive
5.4.2.0
In2 (value range)
±
Setting of value range; possible values:
0...10 V/ 2...10 V/0...20 mA/4...20 mA
Not displayed when In2 = inactive
5.5.0.0
PID parameters
Settings for PID-Control
Only displayed when PID-Control is
active (incl. all sub-menus)
5.5.1.0
P parameter
±
Setting of the proportional term of the
control
5.5.2.0
I parameter
±
Setting of the integral term of the control
5.5.3.0
D parameter
±
Setting of the derivative term of the con-
trol
5.6.0.0
Fault
Settings for behaviour in the event of a
fault
5.6.1.0
HV/AC
±
HV (“heating”) mode
AC (“cooling/air-conditioning”) mode
5.6.2.0
Emergency op-
eration speed
Displays emergency operation speed
5.6.3.0
Auto reset time
±
Time until automatic acknowledgement of
an error
5.7.0.0
Other settings 1