en
Operation
50
WILO SE 2020-10
No.
Designation
Type Symbol
Values/explanations
Display conditions
4.4.1.0
Pump name
Example:
GIGA-N 100/250-15/4 (display in ticker
format)
Only the basic pump model ap-
pears on the display; version names
are not shown
4.4.2.0
Software version
of user control-
ler
Displays the software version of the user
controller
4.4.3.0
Software version
of motor con-
troller
Displays the software version of the motor
controller
5.0.0.0
Service
Service menus
5.1.0.0
Multi pump
Twin-head pump
Only displayed when DP is active
(incl. sub-menus)
5.1.1.0
Operating mode
±
Main/standby operation
Only displayed for twin-head pump
master
Parallel operation
Only displayed for twin-head pump
master
5.1.2.0
MA/SL setting
±
Manual switching from master to slave
mode
Only displayed for twin-head pump
master
5.1.3.0
Pump cycling
Only displayed for twin-head pump
master
5.1.3.1
Manual pump
cycling
±
Carries out pump cycling independent of
countdown
Only displayed for twin-head pump
master
5.1.3.2
Internal/external
±
Internal pump cycling
Only displayed for twin-head pump
master
External pump cycling
Shown only for twin-head pump
master, see “AUX” terminal
5.1.3.3
Internal: time in-
terval
±
Can be set between 8 hours and 36 hours
in 4-hour steps
Displayed when internal pump cyc-
ling is activated
5.1.4.0
Pump enabled/
disabled
±
Pump enabled
Pump disabled
5.1.5.0
±
Individual fault signal
Only displayed for twin-head pump
master
Collective fault signal
Only displayed for twin-head pump
master
5.1.6.0
SBM
±
Individual readiness signal
Only displayed for twin-head pump
master and standby/operation SBM
function
Individual run signal
Only displayed for twin-head pump
master
Collective readiness signal
Only displayed for twin-head pump
master
Collective run signal
Only displayed for twin-head pump
master
5.1.7.0
External off
±
Individual External off
Only displayed for twin-head pump
master
Collective External off
Only displayed for twin-head pump
master
5.2.0.0
BMS
Settings for Building Management System
(BMS) – building automation
Including all sub-menus, only dis-