6 Description and function

6.1 Description of the unit 

The main unit is a self-priming, horizontal, multi-
stage rotary pump.The pump sucks the rainwater 
direct from the cistern or any storage tank for 
rainwater, and drives the water to the points of 
use via the pressure and flow controller.
The replenishment reservoir with a capacity of 
11 litres (fig. 5, item 22) is used by the RCB 
switchgear (fig. 1, item 7) to ensure that the water 
supply is not interrupted even if the level of water 
in the cistern is low. The pressure and flow con-
troller Ecocontrol (fig. 1, item 9) automatically 
switches the pump on or off, thus protecting the 
pump when there is low water.

6.2 Function of the product

Pressure and flow controller Ecocontrol 
(fig. 1, item 9; fig. 4)  

The pressure and flow controller Ecocontrol auto-
matically switches the pump on or off depending 
on the pressure. When the unit is ready for opera-
tion and the points of view are closed, the pump is 
at a standstill and the green LED light (fig. 4, 
item 9a) on the front side of the pressure and flow 
controller Ecocontrol lights up. 
If a point of use is opened, the pressure within the 
system will drop. The pump will start as soon as 
the start-up pressure reaches 1.5 bar. The 
orange-coloured LED light (fig. 4, item 9b) lights 
up. 
If the point of use is closed, the pressure increases 
and the volume flow drops. If the volume flow 
drops below approx. 3 l/min. the pump will switch 
off automatically. 
The pump will automatically switch off if the pres-
sure is too weak or there is zero flow (low water or 
dry run). An error will be indicated by the red LED 
light (fig. 4, item 9c).
Once the fault has been remedied, the operator 
will have to keep the fault acknowledgement con-
trol button (fig. 4, item 9d) pressed down until the 
pressure in the system is restored. If the pressure 
cannot be restored with sufficient speed, a fault 
will be indicated by the red LED display.

Replenishment reservoir (fig. 5, item 22)

A replenishment reservoir is arranged next to the 
pump. It provides the system will water from the 
public water supply when there is a low water level 
in the cistern. The separation between the public 
water supply and the installation on the rain water 
side required to safeguard the potable water in the 
system is ensured by means of an overflow of type 
AB (fig. 5, item 19) in accordance with the 
EN 1717 standard.
Water is fed from the public water supply to the 
replenishment reservoir via a float valve in the 
tank (fig. 5, item 18). The overflow (fig. 5, item 19) 
enables defined channelling of water, in the event 
of a fault in the float valve, into an overflow chan-

nel to be established onsite. A direct connection 
between overflow and the connection to the 
sewer must be made impossible.
When the water reserve in the cistern has fallen 
below the minimum level, the float switch signal 
(fig. 5, pos. 2) in the cistern activates the switch-
ing valve (fig. 5, pos. 16), switching it to operate 
from the rainwater storage tank. The system is 
now operated via the replenishment reservoir 
using water from the public water supply. If the 
water falls below the minimum level in the cistern 
again, a signal from the float switch in the cistern 
will trigger the switching value to return to oper-
ate from the cistern.

RCB switchgear (fig. 1, item 7)

The conversion of the float valve signal into the 
switching commands for the switching valve takes 
place in the RCB control device (fig. 2, and 3). The 
operational state of the control device and cistern 
operation is indicated by the permanent green 
LED light. If the rainwater utilisation system is 
supplied with water from the public water supply 
(feed mode), this is indicated by a permanent 
orange LED light. 
Pressing the control button (combination of mul-
ticoloured LED light and button) on the RCB 
switchgear switches the rainwater utilisation sys-
tem from automatic mode to manual operation 
(permanent use of water from the public water 
supply). Manual operation is indicated by a flash-
ing orange LED light. Pressing the control button 
again deactivates manual operation once again 
and the rainwater utilisation system runs in auto-
matic mode. The rainwater utilisation system will 
continue to work in feed mode if the cistern is not 
fed enough water.
NOTE:  The switch to the cistern only works when 
there is enough water in the cistern. The feed 
mode will not be switched off automatically if it is 
activated via the control switch. Accordingly, the 
unit can be permanent switched to operation with 
water from the public water system. 
After an operating time of 3 weeks in cistern oper-
ation, the system will automatically switch to feed 
mode operation from the replenishment reservoir 
until the pump has run in this mode for 3 min-
utes.This ensures that the water in the replenish-
ment reservoir is regularly exchanged. Every time 
a switch is made to feed mode operation from the 
replenishment reservoir, this resets the 3-week 
counter.

Summary of Contents for Wilo-RainSystem AF Comfort MC 304 EM

Page 1: ...nbau und Betriebsanleitung GB Installation and operating instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften Wilo Rain System AF Basic 2 533 217 Ed 01 2010 11 W...

Page 2: ...Fig 1 Fig 2...

Page 3: ...Fig 3 Fig 4...

Page 4: ...Fig 5 Fig 6...

Page 5: ...Fig 7 Fig 8...

Page 6: ......

Page 7: ...D Einbau und Betriebsanleitung 2 GB Installation and operating instructions 12 F Notice de montage et de mise en service 22 NL Inbouw en bedieningsvoorschriften 32...

Page 8: ...Anschluss Saugleitung 17 Rp 1 Anschluss druckseitig 18 G 3 4 Anschluss zur ffentlichen Wasserversor gung 19 berlauf 20 Anschlusskabel zur Stromversorgung L nge 1 80 m 21 Bef llung der Pumpe 22 Nachspe...

Page 9: ...FAHR Akut gef hrliche Situation Nichtbeachtung f hrt zu Tod oder schwersten Verletzungen WARNUNG Der Benutzer kann schwere Verletzungen erleiden Warnung beinhaltet dass schwere Personensch den wahrsch...

Page 10: ...nd Zwischenlagerung Bei Erhalt die Regenwasser Nutzungsanlage sofort auf Transportsch den berpr fen Bei Feststellung von Transportsch den die erforderli chen Ma nahmen mit dem Spediteur unter Ein halt...

Page 11: ...04 Stufenzahl Hydraulik EM Wechselstrom 1 230 V 5 2 Technische Daten Max F rdermenge max 4 m h Max F rderh he Siehe Typenschild Zul ssiger Betriebsdruck 8 bar Zul ssiger Zulaufdruck 1 2 bar Einschalt...

Page 12: ...gungsnetz in den Nachspeisebeh lter erfolgt durch ein Schwimmerventil im Beh lter Fig 5 Pos 18 Der berlauf Fig 5 Pos 19 erm glicht bei St rungen am Schwimmerventil ein definier tes Abflie en des Wasse...

Page 13: ...Saugleitung zur Zisterne Fig 1 Pos 5 und Fig 5 Pos 16 Anschluss an die Verteilung Regenwasser Fig 1 Pos 12 und Fig 5 Pos 17 Anschluss an die ffentliche Wasserversorgung Fig 1 Pos 6 und Fig 5 Pos 18 V...

Page 14: ...Zisterne voll Fig 6 Die freie L nge des Kabels mu mindes tens 100 mm betragen Die Fixierung kann mit hilfe eines Kabelbinders an einem Fixpunkt innerhalb der Zisterne oder einem Gewicht erfol gen Bitt...

Page 15: ...ige ste tig Zisternenbetrieb HINWEIS Enth lt die Zisterne nicht gen gend Wasser so arbeitet die Regenwasser Nutzungs anlage weiter im Nachspeisebetrieb und es leuch tet die Orangefarbene LED Anzeige s...

Page 16: ...en lassen Pumpe l uft aber f rdert nicht Versorgungsspannung zu niedrig Netzspannung Kondensator und Kabel berpr fen Saug Druckleitung oder Teile der Pumpe sind mit Fremdk rpern verstopft Saug Druckle...

Page 17: ...asserversorgung korrigie ren befestigen Den Beh lter und oder das Schwimmer ventil reinigen Das Dreiwege Umschaltventil ist blo ckiert Die Blockierung ist durch Ablagerungen auf dem Ventilsitz bedingt...

Page 18: ...N25 G1 connection suction line 17 Rp 1 connection on the pressure side 18 G 3 4 connection to public water supply 19 Overflow 20 Connecting cable to power supply length 1 80 m 21 Filling the pump 22 R...

Page 19: ...oints 2 1 Indication of instructions in the operating instructions Symbols General danger symbol Danger due to electrical voltage NOTE Signal words DANGER Acutely dangerous situation Non observance re...

Page 20: ...he catalogue data sheet 3 Transport and interim storage Upon arrival Immediately check the rainwater uti lisation system for transport damage If you dis cover transport damage discuss with the courier...

Page 21: ...flow Q in m h 04 Number of hydraulic stages EM AC 1 230 V 5 2 Technical data Max volume flow max 4 m h Max delivery head See rating plate Permissible operating pressure 8 bar Permissible inlet pressur...

Page 22: ...717 standard Water is fed from the public water supply to the replenishment reservoir via a float valve in the tank fig 5 item 18 Theoverflow fig 5 item 19 enables defined channelling of water in the...

Page 23: ...m 11 and fig 5 item 19 Float switch fig 1 item 2 and fig 5 item 2 The float switch which is packed separately must be fitted in the cistern as shown fig 6 The cable must be installed up to the rainwat...

Page 24: ...ust be installed before laying the cable NOTE The float switch must be at least 100 mm above the foot valve The cable must be able to move freely to ensure that no air or particles can be sucked in fr...

Page 25: ...n receives enough water cistern operation NOTE if the cistern does not receive enough water the rainwater utilisation system will con tinue to operate in feed mode The orange LED light lights up perma...

Page 26: ...ping Supply voltage too low Check mains voltage capacitor and cables Suction pressure line or parts of the pump are blocked by foreign bodies Check suction pressure line and pump clean Air in suction...

Page 27: ...mechanically stuck Carry out a visual inspection Where necessary adjust secure the con nection to the public water supply Clean the tank and or the float valve The switching valve is blocked The block...

Page 28: ...Capot 16 DN25 G1 Raccordement conduite d aspiration 17 Rp 1 Raccordement c t refoulement 18 G 3 4 Raccordement au r seau d eau de ville 19 Trop plein 20 C ble de raccordement au r seau lectrique long...

Page 29: ...ux DANGER Situation extr mement dangereuse Le non respect entra ne la mort ou des bles sures graves AVERTISSEMENT L utilisateur peut souffrir de blessures graves Avertissement implique que des dommage...

Page 30: ...up ration d eau de pluie contr ler s il y a des dommages dus au transport En cas de dommages dus au trans port entamer les proc dures n cessaires aupr s du transporteur en respectant les d lais corres...

Page 31: ...Q en m h 04 Nombre d tages partie hydraulique EM Courant monophas 1 230 V 5 2 Caract ristiques techniques D bit max max 4 m h Hauteur manom trique max Voir plaque signal tique Pression de service auto...

Page 32: ...stockage s effectue via une vanne flotteur situ e dans la b che fig 5 pos 18 En cas de d faillance de la vanne flot teur un trop plein fig 5 pos 19 permet l va cuationd une certainequantit d eauparun...

Page 33: ...eau de ville fig 1 pos 6 et fig 5 pos 18 Le raccord entre le trop plein et le raccordement la canalisation d eaux us es au moyen d un enton noir fig 1 pos 11 et fig 5 pos 19 L interrupteur flotteur fi...

Page 34: ...est pleine fig 6 La longueur du c ble libre doit mesurer au moins 100 mm Le c ble de l interrup teur flotteur peut tre fix au moyen d un serre c bles plac un endroit fixe l int rieur de la citerne ou...

Page 35: ...mode automatique S il y a assez d eau dans la citerne la LED verte s allume en continu mode citerne REMARQUE S il n y a pas assez d eau dans la citerne la station de r cup ration d eau de pluie conti...

Page 36: ...ation le condensateur et le c ble La conduite de refoulement d aspiration ou des l ments de la pompe sont obs tru s par des corps trangers Contr ler et nettoyer la conduite de refoulement d aspiration...

Page 37: ...La vanne flotteur s est desserr e ou le m canisme s est bloqu Effectuer un contr le visuel Si n cessaire corriger fixer le branche ment au r seau d eau de ville Nettoyer la b che et ou la vanne flot t...

Page 38: ...16 DN25 G1 aansluiting aanzuigleiding 17 Rp 1 aansluiting aan de perszijde 18 G 3 4 aansluiting op het openbare waterleiding net 19 Overloop 20 Aansluitkabel voor de stroomvoorziening lengte 1 80 m 21...

Page 39: ...rden gelezen Niet alleen de algemene veiligheidsaanwijzingen in de paragraaf Veiligheid moeten in acht wor den genomen maar ook de specifieke veiligheids aanwijzingen onder de volgende punten die met...

Page 40: ...n kan de aansprakelijkheid van defabrikant voor daaruit voortvloeiende gevolgen vervallen 2 7 Ongeoorloofde gebruikswijzen De bedrijfszekerheid van het geleverde product kan alleen bij gebruik volgens...

Page 41: ...ntal trappen van het hydraulisch systeem EM Wisselstroom 1 230 V 5 2 Technische gegevens Max debiet max 4 m h Max opvoerhoogte zie typeplaatje Toegestane bedrijfsdruk 8 bar Toegestane toevoerdruk 1 2...

Page 42: ...een gedefinieerde hoeveel heid water te laten afvloeien in een overloopka naal dat lokaal moet worden aangebracht Een directe verbinding tussen de overloop en aanslui ting naar het afvalwaterriool mo...

Page 43: ...nzuigleiding naar de regenwatertank fig 1 pos 5 en fig 5 pos 16 Aansluiting op de verdeling van regenwater fig 1 pos 12 en fig 5 pos 17 Aansluiting op het openbare waterleidingnet fig 1 pos 6 en fig 5...

Page 44: ...gewicht en de vlot terschakelaar bepaalt het schakelniveau voor de herkenning van Regenwatertank leeg Regen watertank vol fig 6 De vrije lengte van de kabel moet ten minste 100 mm bedragen De bevesti...

Page 45: ...rend regenwatertankbedrijf AANWIJZING Als de regenwatertank niet genoeg water bevat blijft de installatie voor regenwater hergebruik verder in het suppletiebedrijf werken en brandt de oranje LED indic...

Page 46: ...transporteert geen vloeistof Voedingsspanning te laag Netspanning condensator en kabel con troleren Aanzuig persleiding of onderdelen van de pomp zijn verstopt door vreemde voorwerpen Aanzuig persleid...

Page 47: ...waterleidingnet corrigeren beves tigen De tank en of de vlotterkraan reinigen De driewegomschakelklep is geblok keerd De blokkering is veroorzaakt door afzet tingen op de ventielzitting Een visuele co...

Page 48: ...nnex I No 1 5 1 of the EC Machinery directive 2006 42 EC Les objectifs protection de la directive basse tension 2006 95 CE sont respect es conform ment appendice I n o 1 5 1 de la directive CE relativ...

Page 49: ...s especialmente till mpade harmoniserade normer i synnerhet anvendte harmoniserte standarder s rlig ver p gina anterior se f reg ende sida se forrige side FIN DK H CE standardinmukaisuusseloste EF ove...

Page 50: ...Mather and Platt Pumps Ltd Pune 411019 T 91 20 27442100 service pun matherplatt co in Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 citrawilo cbn net id Ireland WILO Engineering...

Page 51: ...henstra e 100 44263 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 kundendienst wilo com T glich 7 18 Uhr erreichbar 24 Stunden Technische Notfallunterst tzung Kundendienst...

Reviews: