- Position the switch of pump 1 on “HAND", the

pump shall start (LED lit on the control box);
check the correct sense of rotation of the motor.

- Proceed in the same way for pump 2.
- In case of wrong direction, reverse 2 wires of the

phase.

WARNING!

Before changing over the phases,

switch off the installation main switch.

- After this operation, position the pump switches

on “OFF“.

8.4 Setting description

8.4.1 Pressure switch setting (Fig. 8)

The adjustment is made by turning the nut
(pos. 1) to set the high point (stopping of pump)
and the nut (pos. 2) to adjust the low point
(starting of pump).

- Turning the nut (pos. 1) clockwise increases the

value of the hight point.

- Turning the nut (pos. 2) clockwise decreses the

value of the low point (the difference increases).
Before adjusting pressure switches PR1 and PR2 ,
choose the starting and stopping pressures (if nec-
essary, use the nomographs).

Proceed as follows:

Remove the cover of contactor PR1.

Turns the nuts (item 1 & 2)

fully clockwise without tightening them.

Set the switch of on pump to “MANU” and hold to

increase the pressure in the installation.

Release the switch at the desired pump stopping pressure

(read on pressure gauge).

Turn the nut (item 1) anticlockwise until there

is an audible click.

Open the discharge valve to lower the pressure

to the desired pump starting level

(read on pressure gauge).

Turn the nut (item 2) anticlockwise.

If there is a click.

Set the switch of one pump to

“AUTO” and hold to check

you adjustments.

adjustment OK

Put the cover

back on.

Remove the

cover of

contactor

PR2.

Commission

Adjustments

imprecise.

See § "prin-

ciple" and refi-

ne the

Adjustments.

adjustment OK

If no click.

Check your operating points

and the tank pre-pressuri-

zation pressure

(it must be 0,3 bar

less than the pump

starting pressure).

If necessary, choose 2 new

points and adjust the pre-

pressurization pressure.

NOTE : the high points (pressure – stop) of both
pumps are similar. The low points (pressure –
start) show a deviation of 0.5 bar Pf from PR2
< 0.5 Pf from PR1.

8.4.2 Setting of the motor protection

Check voltage set on thermal relays
(Fig. 3, pos. 5) by comparing with the data men-
tioned on the pump type plates. If need be reset
the value by turning the thumb wheel.

8.4.3 Float switch for connection to a tank

Set the float switch in order to keep a minimum
water level about 40 cm over the booster inlet
port to be able to resist to the strainer foot-
valve.
Be sure the electric connection is right by activat-
ing the float switch per hand to generate the
lighting of the dry running LED on the control box.

Summary of Contents for Wilo-COE-2-MHIL

Page 1: ...6 Ed 4 2016 02 Wilo en Installation and operating instructions fr Notice de montage et de mise en service it Istruzioni di montaggio uso e manutenzione es Instrucciones de instalaci n y funcionamiento...

Page 2: ...Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 10 1 2 3 8 9 6 4 5 7 11 4 2 3 5 1 1 3 1 1 2 Fig 6 Fig 7 3 2 5 6 4 2...

Page 3: ...sentenza Presi n desconectada Sem press o 0 0 1 2 3 4 5 6 7 8 9 10 1 1 3 0 3 3 6 10 6 2 3 4 5 6 7 8 9 10 11 12 0 3 0 9 1 8 5 2 2 3 4 5 6 7 1 3 4 6 4 12 bars 10 15 bars Pression arr t Off pressure Pres...

Page 4: ...tant pump or machinery functions failure of the maintenance and repairing process recommended danger to persons due to electrical mechanical and bacteriological influences material damages 2 4 Safety...

Page 5: ...iameter 6 Description and operation 6 1 General description The booster is a compact installation that is sup plied completely piped up and ready to connect The only connections that have to be made a...

Page 6: ...Position O The pump is OFF Position HAND The pump is operating in contin uous mode as long as the switch is maintained in this position When releasing it the switch is back to position O Position AUTO...

Page 7: ...ectly dimensioned according to the total booster power see type plate Connecting the control box on a voltage differ ent from the one mentioned in the description is not possible see chapter 5 2 techn...

Page 8: ...uge Turn the nut item 1 anticlockwise until there is an audible click Open the discharge valve to lower the pressure to the desired pump starting level read on pressure gauge Turn the nut item 2 antic...

Page 9: ...ed Check tightness of the valve replace it if necessary Large losses of head at suction Calculate the losses of head and make sure they are compatible with the pump NSPH Public water pressure too low...

Page 10: ...s obstructed by particles Have the pump dismantled and cleaned Voltage of the motors too low Check the voltage on motor terminals Contactor tripping too frequent starting frequency too high Required p...

Page 11: ...wilo it Kazakhstan WILO Central Asia 050002 Almaty T 7 727 312 40 10 info wilo kz Korea WILO Pumps Ltd 20 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 522...

Page 12: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: