5

WILO SE 02/2016

English

4. Application

The booster is designed for boosting and main-
taining the pressure when the water supply net-
work is not well dimensioned or does not exist.
It is used for water supply in high-rise apart-
ments, hospitals, offices and industrial buildings.
Non aggressive clear fluids (potable water, water
containing glycol...).
A control box is used to control, monitor and
protect the boosting system.
The booster is either supplied from the public
water mains or from a mains collection tank.
In case of pressure deviations more than 1 bar in
the suction pipe it is recommended to use a pres-
sure relief valve. The pressure downstream of the
pressure relief valve (back-pressure) is the basis
for the total head calculation of the booster.

5. Product data

5.1 Type key

Wilo-COE-2-MHIL-304-EM/BC

Booster name
2 : number of pumps
MHIL : Type of pump (MHIL)
304 : nominal output and number

of stages (3 m

3

/h 4 stages)

EM : Single-phase
DM : Three-phase
Control box name

5.2 Technical data

- Maximum operating pressure:

10 bars

- Maximum ambient temperature: 0 à +40°C
- Maximum water temperature:

+55°C

- Three-phase supply voltage:

230/400V

(±10%) - 50Hz

220/380V
(±10%) - 60Hz

- Single-phase supply voltage:

220V (±10%)
50/60Hz
230V (±10%)
50/60Hz

- Nominal current:

see type plate

5.3 Scope of delivery

- Booster.
- Installation and operating instruction of the

booster.

5.4 Accessories

as required

- Diaphragm pressure tank (Fig. 1, pos. 11)
- Dry running kit or tank

as option

- Insulation valves
- Vibration compensators

- Pressure relief valve
- Counterflanges according to manifold diameter

6. Description and operation

6.1 General description

The booster is a compact installation that is sup-
plied completely piped-up and ready to connect.
The only connections that have to be made are
for suction and delivery pipe and also the power
mains.
Every accessory ordered is delivery separately.
The relevant instructions or standards must be
observed for the connection to the public water
supply mains. Regulations from the water com-
panies must be included when appropriate. Local
conditions (e.g. a supply pressure that is too high
or fluctuates considerably and which might
require the installation of a pressure relief valve)
must also be observed.

6.2 Product description

6.2.1 The booster (Fig. 1)

1. Control box
2. Pressure switches
3. Pressure gauge
4. Multistage horizontal pumps MHIL
5. Filling plug
6. Draining plug
7. Support and fixing frame
8. Suction manifold
9. Delivery manifold
10. Non-return valve
11. Tank (not delivered)

NOTE: each pump is fitted with insulation valves
on suction side and insulating valves and non-
return valves on delivery side.

6.2.2 Control box

• Ensure complete automatic operation of the

booster.

• Tightness, protection class IP 54.
• Thermal protection of the motors set in factory

according to nominal voltage mentioned on
motors.

• External safety and starting switch of the booster.

On front side (Fig. 2)

An electronic board:

1. LED power ON.
2. LED pump ON (one per pump).
3. LED pump fault (one per pump).
4. 3-position rotary switch (one per pump): AUTO

– O - HAND.

5. LED dry-running.

Inside (Fig. 3)

1. Main switch with power supply connection terminals.
2. Motor magnetic circuit-breaker.
3. Transmitter with connection block for external

devices (pressure switch, float switch…).

4. Contactor.
5. Motor thermal protection relay.

Summary of Contents for Wilo-COE-2-MHIL

Page 1: ...6 Ed 4 2016 02 Wilo en Installation and operating instructions fr Notice de montage et de mise en service it Istruzioni di montaggio uso e manutenzione es Instrucciones de instalaci n y funcionamiento...

Page 2: ...Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 10 1 2 3 8 9 6 4 5 7 11 4 2 3 5 1 1 3 1 1 2 Fig 6 Fig 7 3 2 5 6 4 2...

Page 3: ...sentenza Presi n desconectada Sem press o 0 0 1 2 3 4 5 6 7 8 9 10 1 1 3 0 3 3 6 10 6 2 3 4 5 6 7 8 9 10 11 12 0 3 0 9 1 8 5 2 2 3 4 5 6 7 1 3 4 6 4 12 bars 10 15 bars Pression arr t Off pressure Pres...

Page 4: ...tant pump or machinery functions failure of the maintenance and repairing process recommended danger to persons due to electrical mechanical and bacteriological influences material damages 2 4 Safety...

Page 5: ...iameter 6 Description and operation 6 1 General description The booster is a compact installation that is sup plied completely piped up and ready to connect The only connections that have to be made a...

Page 6: ...Position O The pump is OFF Position HAND The pump is operating in contin uous mode as long as the switch is maintained in this position When releasing it the switch is back to position O Position AUTO...

Page 7: ...ectly dimensioned according to the total booster power see type plate Connecting the control box on a voltage differ ent from the one mentioned in the description is not possible see chapter 5 2 techn...

Page 8: ...uge Turn the nut item 1 anticlockwise until there is an audible click Open the discharge valve to lower the pressure to the desired pump starting level read on pressure gauge Turn the nut item 2 antic...

Page 9: ...ed Check tightness of the valve replace it if necessary Large losses of head at suction Calculate the losses of head and make sure they are compatible with the pump NSPH Public water pressure too low...

Page 10: ...s obstructed by particles Have the pump dismantled and cleaned Voltage of the motors too low Check the voltage on motor terminals Contactor tripping too frequent starting frequency too high Required p...