26
WILO SE 03/2021
en
The sync function is completed for the pump to be
replaced (example of Wilo-Star RS 15/4).
• Compare the setting to the LED code.
• To finish, simultaneously press and hold the upper and
lower operating buttons 1x briefly.
The LED coding applied is displayed for 5 seconds
All LEDs flash 3x
The new setting is applied and the sync function
finished. The pump returns to normal control mode.
NOTICE
If all 9 LEDs are run through, the LED selection
automatically begins again with the 1st LED.
Simultaneously press the two buttons to cancel
the mode.
NOTICE
Upon completing the sync function, check and, if
necessary, set the set control modes and pump
curves again.
1
2
3
4
8
7
6
5
9
NOTICE
In the event of an incorrect input during the sync
function, the LED settings have to be repeated/
corrected clockwise.
If an incorrect LED coding is entered and con
-
firmed, the central LED remains red during the
flashing phase. This incorrect coding is not taken
into account, the pump exits the sync function
and retains the previous configuration.
If the Varios PICO-STG is to be reset to its original
profile, the sync function has to be restarted with
the LED code of the Varios PICO-STG (all LEDs
ON).