Fault
With the power switched on, the pump does not run.
Cause
Motor protection has switched the pump off, because:
a)
Switch off
because of
hydraulic over-
loading of the
pump.
b)
Switch off because of
obstruction within the
pump.
c)
Switch off
because of
excessive fluid
temperature.
d)
Switch off
because of
excessive
ambient tem-
perature.
Remedy
a)
Throttle the
pump at the
pressure side to
a duty point on
the pump
curve.
b)
If necessary remove
the venting screw (visi-
ble from outside) from
the pump and check the
free running of the pump
rotor by turning the
slotted shaft end, using
a screwdriver; unblock if
necessary.
Alternatively:
Dismantle the motor
head and check; if nec-
essary unblock by turn-
ing the impeller. If the
obstruction cannot be
cleared, contact cus-
tomer service.
c)
Reduce the
temperature of
the fluid, see
rating plate
data.
d)
Reduce the
ambient tem-
perature , e.g.
by insulating
the piping and
fittings.
Display
Displays of the lights in the terminal box type
1
2
3
4
5
6
7
-
-
-
-
red
green
red
Fault acknowl-
edgement
Terminal box type 1/2
Auto-reset; after the motor has cooled down, the pump restarts automatically.
Terminal box type 5/7
After the motor has cooled down, press the reset button for a manual reset of
the fault. The pump will restart.
Terminal box type 3/4
It the thermal winding contact was connected to an external switchgear SK602/
SK622, this must be reset. With the switchgear SK602N/SK622N, acknowledge-
ment is made automatically after the motor has cooled down.
Terminal box type 6:
After the motor protection has tripped, switch off the mains voltage. Allow the
pump to cool down approx. 8 to 10 min, then switch the power supply on again.