Installation and operating instructions Wilo-TOP-S/-SD/-RL/-I
31
English
The assignment of terminal boxes to the individual pump types is described
in the section "Terminal boxes" (chapter 6.2).
TOP-SD:
For a double pump the two motor impeller units are fitted identically and
accommodated in a common pump housing.
6.2 Terminal boxes
There are nine terminal boxes (fig. 4) covering all the pump types. Table 1 lists
the assignment of terminal boxes to pump types:
Table 1: Assignment of terminal box types to pump types (see also fig. 4)
The fittings for the terminal boxes can be found in Table 2:
Table 2: Fitting of terminal boxes
1) The light indicator signals are carried by a common fibre optic cable to the cover, so that the signals are visible
from outside.
2) When mains voltage is present, the lamp lights up green
• The direction of rotation indicator light lights up green when mains voltage is
present and the direction of rotation is correct; if the direction of rotation is
incorrect, the control lamp goes out (see the chapter "Commissioning").
• The fault signal light lights up red if the integral motor protection has tripped.
Mains
connection
Max. power consumption P
1
(see rating plate data)
Terminal box type
TOP-RL, TOP-I
TOP-S, TOP-SD
1~
95 W
≤
P
1
max
≤
265 W
1
1/2
320 W
≤
P
1
max
≤
400 W
-
3/4/5
650 W
≤
P
1
max
≤
960 W
-
5
3~
95 W
≤
P
1
max
≤
270 W
6
6
305 W
≤
P
1
max
≤
3125 W
-
7
Terminal box
type
Direction-
of-rotation
control lamp
Fault signal
light
Variable speed control
(fig. 4, item 1)
(fig. 4, item 2)
(fig. 4, item 3)
1
-
-
Speed selection switch, 3-step
2
-
-
Internal/external
Jumpering of contacts
"x1-x2"
or "x1-x3" or "x1-x4"
3
-
-
Speed selection switch, 3-step
4
-
-
Internal/external
Jumpering of contacts
"x1-x2"
or "x1-x3" or "x1-x4"
5
-
2)
X
1)
Switching plug, 2-step
6
X (internal)
-
Switching plug, 3-step
7
X
1)
X
1)
Switching plug, 3-step
Summary of Contents for TOP-I