Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
225
Select type of use
Analogue input (AI2)
Set analogue input
as setpoint controller,
e.g. for delivery head
Setpoint controller
Differential pressure sensor
Temperature sensor
External sensor
Not configured
Fig. 73:
Settings dialogue
Select “Setpoint sensor” as setpoint source.
NOTICE
If another type of use has been set to “Not configured” in the “Select type of use”
menu, check whether the analogue input is already used for another type of use.
If necessary, select a different source.
Select the “Signal type” after selecting the type of use.
Signal type analogue input (AI2)
For setpoint sensor
Set analogue input to the
signal type 0…10 V.
0 – 10 V
2 – 10 V
0 – 20 mA
4 – 20 mA
PT1000
Fig. 74:
Signal type
After selecting the signal type, it is defined how standard values are used.