Electrical connection
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
167
Fig. 18:
Threaded cable glands/cable bushings
Connection
Threaded cable gland
Cable
bushing
Fig. 18,
Item
Terminal
no.
Electrical mains connection
3~380 V AC ...
3~440 V AC
Plastic
1
1 (Fig. 19)
SSM
1~220 V AC ...
1~240 V AC
12 V DC
Plastic
2
2 (Fig. 19)
SBM
1~220 V AC ...
1~240 V AC
12 V DC
Plastic
3
3 (Fig. 19)
Digital input EXT. OFF
(24 V DC)
Metal with shielding
4, 5, 6
11 ... 14
(Fig. 20)
(DI1 or DI2)
Digital input EXT. MAX/EXT.
MIN
(24 V DC)
Metal with shielding
4, 5, 6
11 ... 14
(Fig. 20)
(DI1 or DI2)
Bus Wilo Net
(Bus communication)
Metal with shielding
4, 5, 6
15 ... 17
(Fig. 20)
Analogue input 1
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Metal with shielding
4, 5, 6
1, 2, 3
(Fig. 20)
Analogue input 2
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Metal with shielding
4, 5, 6
4, 5
(Fig. 20)
Analogue input 3
PT1000
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Metal with shielding
4, 5, 6
6, 7, 8
(Fig. 20)
Analogue input 4
PT1000
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Metal with shielding
4, 5, 6
9, 10
(Fig. 20)
CIF module
(Bus communication)
Metal with shielding
4, 5, 6
4 (Fig. 25)
Electrical connection of the
fan
assembled at the factory
(24 V DC)
7
4 (Fig. 19)
Table 9:
Cable connections
Cable requirements
Terminals are intended for rigid and flexible conductors with or without ferrules.
If flexible cables are used, the use of ferrules is recommended.
Summary of Contents for Stratos GIGA2.0-D
Page 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Page 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Page 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Page 548: ......
Page 549: ......
Page 550: ......
Page 551: ......