10.3 Error messages: Error LED “permanent light“
Problem
cause
remedies
Pump does not run
with switched on
power
Electric fuse faulty,
Check fuse
Pump has no power
Rectify interruption to power
Noisy pump operation
Cavitation due to insufficient
admission pressure
Increase system admission
pressure within permissible
range
Code
No.
Symbol
flashing
Problem
cause
remedies
E04
Supply
terminal
Mains undervoltage
Mains overloaded Check
electrical
installation
E05
Supply
terminal
Mains overvoltage
Check electrical
installation
E10
Motor
Pump blocked
e.g. sedimentation
De-blocking routine
starts automatically.
Should this not remove
the blockage, the
pump switches off
after 10 sec.
Call customer services
E20
Motor
winding overheated
Motor overloaded
Let motor cool down,
check the settings
Ambient
temperature to high
Reduce water
temperature
E21
Motor
Motor overload
Sediment in the
pump
Call customer services
E23
Motor
Short circuit/contact
fault
Motor defect
Call customer services
E25
Motor
Contact error
Module not correctly
installed
Reinstall module
E30
Module
Excess temperature
module
Air intake to module
heat sink is blocked
Free air intake
E31
Module
Excess temperature
power component
Ambient
temperature to high
Improve ventilation in
room
E36
Module
Module faulty
Electronic
components faulty
Call customer service /
swap module