6. Commissioning

6.1 System filling and venting

Ensure that the pipe system is

properly filled. The pump vents itself

automatically after a short operational

period. Short-term dry-running will not

harm the pump. If necessary, the

pump can be directly vented in ac-

cordance with the following procedure:
– Switch-off pump,
– close discharge isolating valve,
– Carefully slacken and remove the

central access plug using screw-

driver (Fig. 3).

– Depending on liquid tempe-

rature and system pressure,

hot liquid or vapour can be

releases when undoing the

central access plug.

Beware!
Danger of scalding!

– Protect electrical parts from leaking

water,

– switch-on pump again,
– after 15 … 30 secs close access

plug again,

– open isolating valve again.

It is possible that the pump shaft jams

with the access plug open, depending

on system pressure.

ATTENTION!

– The pump can become

extremely hot, depending

on the operating state of

pump or pipe system (fluid

temperature).

Beware of scalding when
touching the pump!

6.2 Pre-Start Adjustments

– Direction of rotation check

on

3-phase motors:
Remove central access plug at the

non-drive end of the motor. Briefly

switch on motor and check

whether sense of rotation corre-

sponds to the arrow on the name

plate; if necessary, change any two

phase wires.

7. Maintenance

Prior maintenance or repair

work switch off the pump and

secure against unauthorized

switching.

Summary of Contents for Star Z 20/1

Page 1: ...au und Betriebsanleitung GB Installation and Maintenance Instructions F Notice de mise en service et de montage I Istruzioni di montaggio uso e manutenzione E Instrucciones de instalaci n y funcionami...

Page 2: ...Fig 1 Fig 2 3 400 V Fig 4 Fig 3...

Page 3: ...N L N L N L N L 1 230 V 50 Hz N L Fig 5 Fig 5 Fig 5 b Fig 5 a Fig 5 c...

Page 4: ......

Page 5: ...2 ZD 25 6 R 1 DN 28 G R 1 The minimum inlet pressure at the pump suction port must be maintained to avoid cavitation noise 2 Safety These instructions contain basic refe rence to safety aspects which...

Page 6: ...on Work It is the Operator s responsibility to ensure that inspections and installa tion work are carried out by authorized and qualified personnel only having themselves made fully conversant with th...

Page 7: ...heads can be selected of different capacities Double pumps are suita ble of adapting a pipe system to suit individual load characteristics 4 2 Scope of Supply Pump complete Installation and Operating...

Page 8: ...2 Pos 2 ATTENTION ATTENTION ATTENTION 5 2 Electrical wiring Electrical work to be car ried out by qualified and licensed electricians in strict conformity to ruling national conditions and local regul...

Page 9: ...alding Protect electrical parts from leaking water switch on pump again after 15 30 secs close access plug again open isolating valve again It is possible that the pump shaft jams with the access plug...

Page 10: ...e respectively at the slotted shaft end by means of a screw driver Observe safety procedures as for 6 1 At high water temperatures and system pressures close isolating valves at both pump ports First...

Page 11: ...rective Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant national legislation et aux l gislations nationales les transposant Angewendete harmonisierte Normen in...

Page 12: ...nvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vastaa seuraavia asiaankuuluvia m r yksi S hk magneettinen soveltuvuus 2004 108 EG Matalaj nni...

Page 13: ...0 591 5 7 81 B58 51 85 8 1 451 91 58 B58 5 85 B58 5 1 8 5 89 D 5 2 B58 7E 9 0 594 1 D1 3 9 B58 B58 7 8 5 53 9 58 B58 8A 1 8 1 B 8 D 1 5 1 8 51 A 58 5 9 58 B58 8 B58 9 101 8 0 A 1 E 5 2 B58 8 31 8 B58...

Page 14: ...58 86 8 43 2 7 D 8 6 7 4 80 361 7 D 80 8 43 2 7 D 8 6 7 I I I I I I I I I I 4 7 7 3 7 358 86 E153 2 2 3 2 7 7 273 2 8 0 55 7 G B 71 H 7 7 3 7 708 71 H 4 9 7 H B 350 1 7 H 7 3 7 26 H 7 9 4 387 H 273 2...

Reviews: