6.4 Noise

Pressure-boosting systems are supplied with 

different pump types and a variable number of 

pumps, as listed under point 5.1. No specific over- 

all noise level can therefore be listed here for all 

variants of pressure-boosting systems. In the fol-

lowing overview, pumps of the standard series are 

taken into account at a mains frequency of 50 Hz.

Rated power (kW)

0.37

0.55

0.75

1.1

1.5

1.85

2.5

Max. sound-pr

es

-

sur

e lev

el (*)

Lpa in [dB(A)]

1 pump

55

57

58

58

58

62

63

2 pumps

58

60

61

61

61

65

66

3 pumps

59.5

61.5

62.5

62.5

62.5

66.5

67.5

For motor powers not listed here and/or other 

pump series, see the single pump noise value from 

the installation and operating instructions for the 

pumps or from the catalogue information on the 

pumps. With the following procedure, it is possible 

to approximate the overall noise level of the com- 

plete system using the noise value for a single 

pump of the type supplied.

•The installation surface must be horizontal and 

level. A slight adjustment in height of the vibra-

tion absorber in the base frame may be necessary 

to achieve stabilisation. If necessary, undo the 

counter nut and unscrew or turn in the respective 

vibration absorber slightly. Then re-tighten the 

counter nut.

•The system is designed for a maximum ambient 

temperature of +5 °C to 50 °C at a relative humid- 

ity of 50%.

•Installation and operation in the vicinity of living 

rooms and bedrooms is not recommended.

•To avoid the transmission of structure-borne 

noise and to ensure a stress-free connection to 

upstream and downstream pipes, compensators 

with extension limiters or flexible connection pipes 

must be used!

7

7.1

WARNING! Health hazard!

In the event of sound-pressure levels of above 

80 dB(A), the operating personnel and persons 

who are in the vicinity during operation must 

wear suitable hearing protection!

Setup/installation

Installation site

The pressure-boosting system is installed in the 

technical control room or in a dry, well ventilated 

and frost-proof, separate room that can be locked.

•Adequately dimensioned floor drainage (drain 

connection or similar) must be provided in the 

installation room.

•No harmful gases may enter the room or be pres- 

ent there.

•Ensure adequate space for maintenance work. 

The main dimensions can be found in the supplied 

installation plan. The system should be freely 

accessible from at least two sides.

Calculation
Single pump

....

dB(A)

2 pumps, total

+3

dB(A) (tol0.5)

3 pumps, total

+4.5

dB(A) (tol1)

Overall noise level

....

dB(A)

Example (pressure boosting with 3 pumps)
Single pump

58

dB(A)

3 pumps, total

+4.5

dB(A) (tol1)

Overall noise level

62.5...63.5

dB(A)

Summary of Contents for ISAR MODH1 Series

Page 1: ...WILO ISAR MODH1 SCe EM Pioneering for You CD_TE0080 rev00 en Installation and operating instructions...

Page 2: ...dation bearing surface 9 7 2 2 Hydraulic connection and pipes 9 7 2 3 Hygiene 9 7 2 4 Protection against dry running low water level accessories 9 7 2 5 Diaphragm pressure vessel 9 7 2 6 Non pressuris...

Page 3: ...mplies that damage to the product is likely if this information is disregarded NOTICE Useful information on handling the product It draws attention to possible problems Information that appears direct...

Page 4: ...Improper use The operational reliability of the supplied product is only guaranteed if used as intended and in accordance with section 4 of the installation and operating instructions The limit value...

Page 5: ...d name ISAR Product family pressure boosting systems MOD Application commercial H With horizontal pumps 1 Product level 1 entry 3 standard 5 premium 1 Number of pumps CH1 L Pump series 2 Rated flow ra...

Page 6: ...Safety valve BACnet software GSM module mobile communication Float switch Flexible connection pipes Compensators Threaded flanges 6 6 1 Description of the product and accessories General description T...

Page 7: ...r Draining venting Stop valve 6 3 Function of the pressure boosting system Wilo pressure boosting systems in the ISAR MODH1 series are standard equipped with non self priming multistage horizontal cen...

Page 8: ...en the counter nut The system is designed for a maximum ambient temperature of 5 C to 50 C at a relative humid ity of 50 Installation and operation in the vicinity of living rooms and bedrooms is not...

Page 9: ...ly replaced after a long system standstill 7 2 4 7 2 5 7 2 6 For the simple flushing of the system the installa tion of a T connector on the end pressure side of the pressure boosting system is recomm...

Page 10: ...overed by the pipe insulation NOTICE Flexible connection pipes are subject to wear in operation Regular checks for leakages or other defects are necessary Nominal Diameter connection Thread screwed co...

Page 11: ...uctions and accompanying documents for the control device when making this connection and apply the necessary settings In some cases of low volume a float switch will be used This will be factory set...

Page 12: ...k the motor for defects and replace if necessary Contactor defective Check it and replace it if necessary Turn to turn fault in the motor Check if necessary replace motor or have it repaired Pump s do...

Page 13: ...let pipe installed incorrectly Check the inlet pipe and change the pipe routing if necessary Air in the inlet Check and shut off the piping and vent the pumps if necessary Air in the pump Vent the pum...

Page 14: ...alve if necessary Pump s produce s no or too little power Non return valve clogged Check and remove the clogging or replace the non return valve if necessary Gate valve in the system closed or not suf...

Page 15: ...ation It means that the electrical and electronic products in question must not be disposed of along with domestic waste To ensure proper handling recycling and disposal of the used products in questi...

Page 16: ...16 Fig 1 Fig 1b Fig 1c...

Page 17: ...sed break tank on the inlet side 22 N A 28 Flushing apparatus for inlet connection of thebreak tank 23 Diaphragm pressure vessel on the discharge side 29 Bypass for inspection maintenance not permanen...

Page 18: ...MEDANA CH1 L 207 1 E E 10N EP 4231511 l l MEDANA CH1 L 402 1 E E 10N EP 4231513 l l MEDANA CH1 L 403 1 E E 10N EP 4231515 l l MEDANA CH1 L 404 1 E E 10N EP 4231517 l l MEDANA CH1 L 405 1 E E 10N EP 42...

Page 19: ..._ Pressure Equipment Safety Regulations SI 2016 No 1105 _ Electromagnetic Compatibility EMC Regulations SI 2016 No 1091 amended _ Restriction of the Use of Certain Hazardous Substances RoHS in Electr...

Page 20: ...h hungsanlagen der Baureihen Nous fabricant d clarons sous notre seule responsabilit que les types de surpresseurs des s ries Isar MODH1 1CH1 L SCe EM Isar MODH1 2CH1 L SCe EM Isar MODH1 3CH1 L SCe EM...

Page 21: ...21 NOTES...

Page 22: ...e 100 D 44263 Dortmund Germany T 49 231 4102 0 F 49 231 4102 7363 wilo wilo com www wilo com WILO UK Centrum 100 Second Avenue Burton Upon Trent Staffordshire DE14 2WJ T 44 1283 523 000 F 44 1283 523...

Reviews: