Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON
60
English
Pump override active
network output SNVT_switch nvoPumpOverride
This optional output network variable provides the status of the overriding
settings.
Value range
Transmission
This value is transmitted whenever a change is made.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Current error master
network output SNVT_count nvoCurrentErrorM
This optional output network variable specifies the current error code of the
master pump.
Value range:
0 - 65534, see Wilo error codes list.
Transmission:
This value is transmitted whenever a change is made.
Transmission frequency:
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock pulse.
Preset service type: unacknowledged
Status
Value
Function
0
0
NORMAL
1
200
OVERRIDE
255
0 – 255
Invalid