Navigation key “UP”

Acceptance key

Navigation key “DOWN”

1.5.2.  Control lights

Yellow control light – permanently on:

The pump works in either automatic or manual 

mode.

Yellow control light – flashing:

Additional pump operation after liquid level in the 

tank falls below the switch off level. This time is 

set up in the control menu.

Red control light:

Indication of emergency status. Turned on until 

the cause for alarm is eliminated.

1.5.3.  LCD display

In the normal course of work the upper line of 

the display shows the level value or status of 

float switch contacts. If the pump is off, then the 

down line displays the total time of the pump’s 

operation. If the pump is on, then the down line 

displays the motor’s current value. If you press 

the ▲ navigation key on the display once, then it 

will display the total number of times the pump 

has turned on since it was started.

NOTE!

It is impossible to reset the indications of work-

time and the number of the pump’s starts.

In the case of state of alarm the display will show 

appropriate messages, alternating with normal 

indications.

2. Assembly and operation

• The device can be assembled and operated only 

by a person who possesses appropriate and valid 

qualifications empowering them to use devices, 

installations and networks at least in the field 

of assembly of control-measurement devices, 

as well as devices and installations of automatic 

adjustment.

• When connecting the device to the wiring 

system or introducing any modifications in the 

connection system, the power supply should be 

turned off. Power supply can be turned on after 

connecting the wires and replacing the terminal 

cover. During operation, employees authorized to 

operate the device can have access to connection 

terminals only, or else the power supply will be 

turned off. Under no circumstances should the 

insulation outside cover (front panel) of the elec

-

tronic and electric part be taken off the device.

2.1.  Assembly

The device should be assembled in an upright po-

sition, in a place free from direct contact with rain 

or sunlight. Application of an additional protec-

tion box is useful. In places where the tempera

-

ture often falls below -20°C it might be necessary 

to provide heating. 

The casing shall be fixed to a vertical base using 

three screws or bolts of diameter 4 - 5mm. The 

arrangement of fixing bolts is shown on the back 

wall of the housing. Dependent on the conditions 

you may use the catch included in the set. First, 

fix it to the upper part of the casing with enclosed 

screw. In this case the middle fixing screw must 

be placed 40 mm higher than the value specified 

on the casing.

The MR-Lift device has no anti-explosion 

protection. Therefore, it can be installed only 

outside explosion hazard areas.

2.2.  Wiring

• The type of current and voltage must be identical 

to data specified on the data plate of the device.

• Protection on behalf of the network must be 

applied (max. 16A).

• Ground the pump / device according to regula-

tions.

• Let in endings of wires through relevant cable 

glands in the lower part of the casing and connect 

them in accordance with markings on the termi-

nal block.

• Unused cable glands must clog.

2.2.1.  Delivering power to the control and connecting 

pump

Three-phase motor wiring

Single-phase motor wiring

Summary of Contents for Control MR-Lift

Page 1: ...o nl Inbouw en bedieningsvoorschriften da Monterings og driftsvejledning sv Monterings och sk tselanvisning fi Asennus ja k ytt ohje el hr Upute za ugradnju i uporabu sr Uputstvo za ugradnju i upotreb...

Page 2: ......

Page 3: ......

Page 4: ......

Page 5: ...fication 6 1 5 Control elements 6 2 Assembly and operation 7 2 1 Assembly 7 2 2 Wiring 7 2 3 Level measurement 8 2 4 Test run without pump 8 2 5 Settings 9 2 6 Additional information 10 3 Troubleshoot...

Page 6: ...ht This operating and maintenance manual has been copyrighted by the manufacturer The operating and maintenance manual is intended for use by installation operating and maintenance person nel It conta...

Page 7: ...ly should be turned off Power supply can be turned on after connecting the wires and replacing the terminal cover During operation employees authorized to operate the device can have access to connect...

Page 8: ...bbles generated by the membrane pump 2 3 1 2 External pressure sensor 4 20mA External two wire sensor must be connected to terminals 30 i 31 The sensor is powered by stabilized voltage of 20V 2 3 2 Fl...

Page 9: ...o communication High level 9 100 cm When the set level value is exceeded relay contacts of the collective failure report system and high level relay are switched on Minimum current 0 12 A When the pum...

Page 10: ...values e g minimum current value higher than maximum current value 2 6 3 LCD contrast setting The default contrast setting is optimum and there is usually no need to change it However if such a necess...

Page 11: ...k exceeded value set in menu Check if the device works in automatic mode or if the pump is not turned off as a result of over temperature overcurrent or a dry run After all check if the delivery pipel...

Page 12: ...he pump is ready to work again Thermal fault 1 Signal of failure The pump is stopped After the fault is removed the state of failure is deleted au tomatically Acceptable temperature for the pump has b...

Page 13: ...ing checks at intervals of 6 month 1 Check the state of electrical connections and if necessary tight connection terminals 2 Check the state and sealing of the pressure line 3 If a sparge pipe compres...

Page 14: ...rev01 Wilopark 1 D 44263 Dortmund DECLARATION OF CONFORMITY KONFORMIT TSERKL RUNG We the manufacturer declare under our sole responsibility that these electronic control panel types of the series Als...

Page 15: ...EU BASSE TENSION 2014 30 EU COMPATIBILITE ELECTROMAGNETIQUE 2014 53 EU EQUIPEMENTS RADIOELECTRIQUES 2011 65 EU 2015 863 LIMITATION DE L UTILISATION DE CERTAINES SUBSTANCES DANGEREUSES EN 60730 1 2016...

Page 16: ...altuudet koota tekninen tiedosto on noudattamaan my s seuraavia asiaankuuluvia standardeja WILO SE Group Quality Wilopark 1 D 44263 Dortmund uppfylla einnig eftirfarandi vi eigandi sta la WILO SE Grou...

Page 17: ...visse farlige stoffer EN 60730 1 2016 EN 60730 2 15 2010 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Vedkommendesom er autorisert til sammens...

Page 18: ...Smjernica o niskom naponu 2014 30 EU Elektromagnetna kompatibilnost smjernica 2014 53 EU Radio oprema 2011 65 EU 2015 863 ograni enju uporabe odre enih opasnih tvari EN 60730 1 2016 EN 60730 2 15 2010...

Page 19: ...6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Oseba poobla ena za sestavo tehni ne datoteke je Mi kot proizvajalci z polno odgovornostjo izjavljamo da te vrste elektronski...

Page 20: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: