background image

English

8

WILO SE 12/2020

Fault-actuated switchover of multi-pump 
system

Switchgears with frequency converter – CC-FC 
version:

If the base-load pump has a fault, it is switched off 
and another pump is switched onto the frequency 
converter. If the frequency converter has a fault, 
the switchgear switches to "auto without fre

-

quency converter" operating mode with the asso

-

ciated control characteristics.

Switchgears without frequency converter – 
CC version:

If the base-load pump has a fault, it is switched off 
and one of the peak-load pumps is managed by 
the switchgear as a base-load pump.

Switchgears in the CCe version:

If the base-load pump has a fault, it is switched off 
and another pump takes over the control function.
As a result of a fault of the peak-load pump, it is 
always switched off and a further peak-load pump 
(if necessary, also the standby pump).

Low water

A low water signal can be sent to the switchgear 
via a normally closed contact based on the signal 
from a suction-side pressure switch, break tank 
float switch or optional level relay.

Monitoring of maximum and minimum pressure

Limit values for safe system operation can be set. 

Ext. Off

It is possible to deactivate the switchgear exter

-

nally using a normally closed contact. This func

-

tion takes precedence; all pumps are deactivated.

Operation in the event of a sensor fault

In the event of a sensor fault (e.g. wire break), the 
behaviour of the switchgear can be defined.

Operating mode of the pumps

The operating mode of the respective pump can 
be specified with the PLC (manual, off, auto) dur

-

ing activation.

Emergency operation

In the event of the control failing, there is the 
option to commission the pumps individually by 
means of the manual-0-auto switch (Fig. 1a-e; 
item 8) on the mains (or per manual control with 
individually settable speed for each pump – only 
CCe version). This function takes precedence over 
pump activation by the control.

Setpoint changeover

The switchgear can work with 3 different set

-

points.

Remote setpoint adjustment

Remote adjustment of the setpoint is possible 
using an analogue current signal (optional voltage 
signal) by means of the corresponding terminals 
(acc. to circuit diagram).

Constant speed

Constant speed mode is possible via an analogue 
current signal (optional voltage signal) using the 
corresponding terminals (according to circuit 
diagram).

Logic reversal of the collective fault signal (SSM)

The required logic of the SSM can be set.

Function of the collective run signal (SBM)

The required function of the SBM can be set.

Fieldbus connection

The switchgear is prepared for connection
via ModBus TCP as standard. Connection is estab

-

lished via an Ethernet interface (electrical connec

-

tion as per chapter 7.2).
The switchgear works as a Modbus slave. Basic 
settings are adjusted on the user interface.
Different parameters can be read and also 
changed to some extent via the Modbus interface. 
An overview of individual parameters and a 
description of the data types used are shown in 
the appendix.

Pipe filling

The pipe filling function can be activated to avoid 
pressure peaks when filling empty pipelines or 
pipelines under low pressure.

6.2.2 Motor protection

Excess temperature protection

Motors with an WSK (thermal winding contact) 
signal an excess winding temperature to the 
switchgear by opening a bimetal strip contact. The 
connection of the WSK is carried out according to 
the circuit diagram.
Faults on motors that are equipped with a tem

-

perature-dependent resistor (PTC) for excess 
temperature protection can be detected using 
optional evaluation relays. 

Excess current protection

Motors on switchgears up to and including 4.0 kW 
are protected by motor protection switches with 
thermal and electromagnetic trip triggers. The 
trigger current must be set directly.
Motors on switchgears from 5.5 kW are protected 
by thermal motor protection relays. These are 
installed directly on the motor protections. The 
trigger current must be set and is 0.58 * I

nom

 with 

the Y-∆ starting of the pumps used.
All motor protection devices protect the motor 
during operation with the frequency converter or 
in mains operation. Pump faults which reach the 
switchgear result in deactivation of the corre

-

Summary of Contents for Control Booster CC

Page 1: ...Pioneering for You 2 552 577 Ed 01 2020 12 Wilo Wilo Control CC Booster CC CC FC CCe en Installation and operating instructions...

Page 2: ...Fig 1a Comfort Control 6 1 7 8 2 3 1 Fig 1b Comfort Control 6 1 7 8 2 3 1...

Page 3: ...Fig 1c Comfort Control 4 1 6 8 2 3 1 6 7 5 Fig 1d Comfort Control 4 1 8 2 3 1 6 7 5...

Page 4: ...Fig 1e Comfort Control 8 1 2 3 6 1 Fig 2 Fig 3...

Page 5: ...Fig 4a Fig 4b Fig 4c...

Page 6: ...a 5 5 3 Scope of delivery 5 5 4 Accessories 6 6 Description and function 6 6 1 Description of the product Fig 1 6 6 1 1 Function description 6 6 1 2 Set up of the switchgear 6 6 2 Function and operati...

Page 7: ...al voltage NOTICE Signal words DANGER Acutely dangerous situation Non observance will result in death or extremely serious injuries WARNING The user could suffer serious injuries Warning implies that...

Page 8: ...must be put back in position and or recommissioned 2 7 Unauthorised modification and manufacture of spare parts Unauthorised modification and manufacture of spare parts will impair the safety of the p...

Page 9: ...ing application 4 x Number of pumps 1 6 10 Max rated current per pump in amperes A T Mains connection M alternating current 1 T three phase current 3 34 Rated voltage 2 220 230 V 34 380 400 V DOL Pump...

Page 10: ...sing voltage peaks only in the CC FC version item 5 Fuse protection for drives and frequency con verter Fuse protection for the pump motors and the frequency converter For devices with P2 4 0 kW Motor...

Page 11: ...d peak filters can be undertaken in 4 3 5 1 page 2 Normal operation of switchgears without frequency converter CC version see Fig 3 The controlled variable is taken from comparison of the setpoint act...

Page 12: ...adjustment Remote adjustment of the setpoint is possible using an analogue current signal optional voltage signal by means of the corresponding terminals acc to circuit diagram Constant speed Constant...

Page 13: ...splay graphics capable shows the operating statuses of the pumps the controller and the frequency converter Additionally all switchgear parameters can be set using the display The relevant operating e...

Page 14: ...is is done using 4 screws 8 mm Suitable measures should be used to ensure the protection class Floor model BM base mounted The floor model is set up free standing on a level surface with sufficient be...

Page 15: ...terminal strips in accordance with the circuit diagram the PE is connected to the earth rail Power kW Column 1 System impedance Column 2 Connections per hour Column 3 3 400 V 2 2 0 257 12 2 pole 2 2 0...

Page 16: ...nnection cables are extended beyond the dimension supplied ex works it is necessary to comply with the EMC note in the operatingmanualofthefrequencyconverter only CC FC version Connection of excess te...

Page 17: ...means of a potential free contact normally closed contact after removing the converter bridge pre assembled as a factory setting CAUTION Risk of damage to the product Do not connect any external volt...

Page 18: ...switchgear is pre set at the factory The factory settings can be restored by Wilo Service 8 2 Checking the motor direction of rotation By briefly switching on each pump in the Manual mode operating mo...

Page 19: ...ntact material The charge level of the real time clock backup battery is registeredbythesystem andreported if necessary In addition we recommend replacing it every 12 months For this purpose change th...

Page 20: ...ing fins motors are designed for an ambient temperature of 40 C see also installation and operating instructions of the pump Motor protection triggered excess current or short circuit in the supply li...

Page 21: ...cation Bit 3 6 8 15 are 1 all others are 0 The sum is then 23 26 28 215 8 64 256 32768 33096 It is also possible to do the calculation the other way round Based on the bit with the highest index check...

Page 22: ...UINT16 0 1 CCe only RW 31 000 40020 19 Pump speed manual 5 UINT16 0 1 CCe only RW 31 000 40021 20 Pump speed manual 6 UINT16 0 1 CCe only RW 31 000 40024 23 FC ON OFF BOOL CC FC only R 31 000 40025 24...

Page 23: ...40049 48 Pump operating mode ENUM 0 Cascade 1 Vario R 31 000 40050 49 Current speed pump 1 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40051 50 Current speed pump 2 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40052...

Page 24: ...ating hours of pump 2 UINT32 1h R 31 000 40101 40102 100 101 Total operating hours of pump 3 UINT32 1h R 31 000 40103 40104 102 103 Total operating hours of pump 4 UINT32 1h R 31 000 40105 40106 104 1...

Page 25: ...l R 31 000 40240 40241 239 240 Fault status 2 BITMAP32 R 31 000 40141 140 Acknowledge BOOL W 31 000 40159 158 System control BITMAP 0 Ext Off 1 Pump cycling 2 Start pump 3 Stop pump 4 Constant speed a...

Page 26: ...Pioneering for You WILO SE Wilopark 1 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Local contact at www wilo com contact...

Reviews: