5.4 Accessories 

Accessories must be ordered separately:
(see also Wilo-Select)

6 Description and function

6.1 Description of the product (Fig. 1)

6.1.1 Function description 

The Comfort switchgear, controlled by a program

-

mable logic controller (PLC), is used to control 
pressure-boosting systems with up to 6 single 
pumps. The pressure of a system is controlled as a 
function of the load with appropriate signal trans

-

mitters. The controller acts on a frequency con

-

verter (CC-FC version), which in turn influences 
the speed of the base-load pump. A modification 
of the speed changes the volume flow and thus 
the rated power of the pressure-boosting system.
Only the base-load pump is speed-controlled. 
Uncontrolled peak-load pumps are switched on 
and off automatically according to load require

-

ments, while the base-load pump handles 
fine-tuning to the pre-set setpoint.
In the CCe version, each pump has an (integrated) 
frequency converter. 

6.1.2 Set-up of the switchgear

The set-up of the switchgear is dependent on the 
performance of the pumps that are to be con

-

nected, and the version (CC, CC-FC, CCe) (see: 
Fig. 1a CC direct starting; Fig. 1b CC star-delta 
starting, Fig. 1c CC-FC direct starting; Fig. 1d 
CC-FC star-delta starting, Fig. 1e CCe). It consists 
of the following main components:

• Main switch: Switches the switchgear on/off 

(item 1).

• Touch display: Display of operating data (see 

menus) and the operating status. Menu selection 
and parameter input possible via touch sensitive 
surface (item 2).

• Programmable logic controller: Modular design 

PLC with power supply unit. The configuration 
depends on the system (item 3).

• Frequency converter: Frequency converter for 

load-sensitive speed control of base-load pump - 
only available for CC-FC version (item 4).

• Motor filter: Filter for ensuring a sinusoidal motor 

voltage and for suppressing voltage peaks - only 
in the CC-FC version (item 5).

• Fuse protection for drives and frequency con

-

verter: Fuse protection for the pump motors and 
the frequency converter. For devices with 
P

2

 ≤ 4.0 kW: Motor protection switch. On the CCe 

version: Circuit breaker for the fuse for the pump 
mains supply cable (item 6).

• Contactors/contactor combinations: Contactors 

for switching on the pumps. In devices with 
P

2

 ≥ 5.5 kW, including the thermal tripping 

devices for excess current protection (default 
value: 0.58 * IN) and the time relay for the star-
delta switchover (item 7).

• Manual-0-Automatic switch: Switch for selecting 

the pump operating modes "manual" (emergency/
test operation on the mains; motor protection 
available), "0" (pump switched off – no activation 
possible via PLC) and "auto" (automatic mode 
enabled via PLC) (item 8).
The speed of every pump (0 – 100 %) can be set 
in manual mode with the manual control in the 
CCe version.

6.2 Function and operation

DANGER! Risk of fatal injury!
When working on the open switchgear, there is 
a danger of electric shock from touching the live 
components. 
The work must only be carried out by qualified 
personnel!

Option

Description

Signal module

Relay output module for outputting individual operation 
signals and fault signals

DDC and control module

Input terminal assembly for switching potential-free control 
contacts

GSM module

Mobile radio module for dialling into GSM networks

GPRS module

Mobile radio module for dialling into GPRS networks

WebServer

Controller module for connection to Internet or Ethernet data 
transmission

Communication module "ProfiBus DP"

Bus communication module for "Profibus DP" networks

Communication module "CanOpen"

Bus communication module for "CanOpen" networks

Communication module "LON"

Bus communication module for "LON" networks

Communication module "ModBus RTU"

Bus communication module for "ModBus" networks

Communication module "BACnet"

Bus communication module for "BACnet" networks

Mains switching

External auxiliary device for switching to redundant supply 
network

Other options on request

Summary of Contents for Control Booster CC

Page 1: ...Pioneering for You 2 552 577 Ed 01 2020 12 Wilo Wilo Control CC Booster CC CC FC CCe en Installation and operating instructions...

Page 2: ...Fig 1a Comfort Control 6 1 7 8 2 3 1 Fig 1b Comfort Control 6 1 7 8 2 3 1...

Page 3: ...Fig 1c Comfort Control 4 1 6 8 2 3 1 6 7 5 Fig 1d Comfort Control 4 1 8 2 3 1 6 7 5...

Page 4: ...Fig 1e Comfort Control 8 1 2 3 6 1 Fig 2 Fig 3...

Page 5: ...Fig 4a Fig 4b Fig 4c...

Page 6: ...a 5 5 3 Scope of delivery 5 5 4 Accessories 6 6 Description and function 6 6 1 Description of the product Fig 1 6 6 1 1 Function description 6 6 1 2 Set up of the switchgear 6 6 2 Function and operati...

Page 7: ...al voltage NOTICE Signal words DANGER Acutely dangerous situation Non observance will result in death or extremely serious injuries WARNING The user could suffer serious injuries Warning implies that...

Page 8: ...must be put back in position and or recommissioned 2 7 Unauthorised modification and manufacture of spare parts Unauthorised modification and manufacture of spare parts will impair the safety of the p...

Page 9: ...ing application 4 x Number of pumps 1 6 10 Max rated current per pump in amperes A T Mains connection M alternating current 1 T three phase current 3 34 Rated voltage 2 220 230 V 34 380 400 V DOL Pump...

Page 10: ...sing voltage peaks only in the CC FC version item 5 Fuse protection for drives and frequency con verter Fuse protection for the pump motors and the frequency converter For devices with P2 4 0 kW Motor...

Page 11: ...d peak filters can be undertaken in 4 3 5 1 page 2 Normal operation of switchgears without frequency converter CC version see Fig 3 The controlled variable is taken from comparison of the setpoint act...

Page 12: ...adjustment Remote adjustment of the setpoint is possible using an analogue current signal optional voltage signal by means of the corresponding terminals acc to circuit diagram Constant speed Constant...

Page 13: ...splay graphics capable shows the operating statuses of the pumps the controller and the frequency converter Additionally all switchgear parameters can be set using the display The relevant operating e...

Page 14: ...is is done using 4 screws 8 mm Suitable measures should be used to ensure the protection class Floor model BM base mounted The floor model is set up free standing on a level surface with sufficient be...

Page 15: ...terminal strips in accordance with the circuit diagram the PE is connected to the earth rail Power kW Column 1 System impedance Column 2 Connections per hour Column 3 3 400 V 2 2 0 257 12 2 pole 2 2 0...

Page 16: ...nnection cables are extended beyond the dimension supplied ex works it is necessary to comply with the EMC note in the operatingmanualofthefrequencyconverter only CC FC version Connection of excess te...

Page 17: ...means of a potential free contact normally closed contact after removing the converter bridge pre assembled as a factory setting CAUTION Risk of damage to the product Do not connect any external volt...

Page 18: ...switchgear is pre set at the factory The factory settings can be restored by Wilo Service 8 2 Checking the motor direction of rotation By briefly switching on each pump in the Manual mode operating mo...

Page 19: ...ntact material The charge level of the real time clock backup battery is registeredbythesystem andreported if necessary In addition we recommend replacing it every 12 months For this purpose change th...

Page 20: ...ing fins motors are designed for an ambient temperature of 40 C see also installation and operating instructions of the pump Motor protection triggered excess current or short circuit in the supply li...

Page 21: ...cation Bit 3 6 8 15 are 1 all others are 0 The sum is then 23 26 28 215 8 64 256 32768 33096 It is also possible to do the calculation the other way round Based on the bit with the highest index check...

Page 22: ...UINT16 0 1 CCe only RW 31 000 40020 19 Pump speed manual 5 UINT16 0 1 CCe only RW 31 000 40021 20 Pump speed manual 6 UINT16 0 1 CCe only RW 31 000 40024 23 FC ON OFF BOOL CC FC only R 31 000 40025 24...

Page 23: ...40049 48 Pump operating mode ENUM 0 Cascade 1 Vario R 31 000 40050 49 Current speed pump 1 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40051 50 Current speed pump 2 UINT16 0 1 CCe 1 rpm CC FC R 31 000 40052...

Page 24: ...ating hours of pump 2 UINT32 1h R 31 000 40101 40102 100 101 Total operating hours of pump 3 UINT32 1h R 31 000 40103 40104 102 103 Total operating hours of pump 4 UINT32 1h R 31 000 40105 40106 104 1...

Page 25: ...l R 31 000 40240 40241 239 240 Fault status 2 BITMAP32 R 31 000 40141 140 Acknowledge BOOL W 31 000 40159 158 System control BITMAP 0 Ext Off 1 Pump cycling 2 Start pump 3 Stop pump 4 Constant speed a...

Page 26: ...Pioneering for You WILO SE Wilopark 1 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Local contact at www wilo com contact...

Reviews: