Description and function
en
Installation and operating instructions Wilo-CIF-Module
19
Technical data
Cable length
900 m with bus topology (with terminator) and
max. 3 m long spur lines
450 m with free topology, with max. 250 m
between 2 inter-communicating nodes
PLR interface
Interface
Current loops (≅ 5 mA)
Cable length
200 m (max. / 0.5 mm
²
)
Table 3:
Technical data
5.3
Standards
The CIF modules with BACnet protocol comply with ISO 16484-5:2017. Details can be
found in the PICS Statement (English).
The CANopen CIF modules correspond to the following CAN in Automation standards:
ƒ
CiA 301 Version 4.2.0: CANopen application layer and communication profile
The LON CIF modules correspond to the following LonMark International standards:
ƒ
Application Layer Interoperability Guidelines Version 3.2
ƒ
Layers 1-6 Interoperability Guidelines Version 3.2
ƒ
node object 0000_20
ƒ
pump controller object 8120_10
ƒ
Resource Files Version 13.04
The Modbus RTU CIF modules correspond to the MODBUS APPLICATION PROTOCOL
SPECIFICATION V1.1 and Modbus over Serial Line protocol V1.02 in the module with
Modbus RTU, available at modbus.org.
6
Description and function
The CIF modules enhance the device with communication interfaces for various
standards.
For more information visit www.wilo.de/automation (German), www.wilo.com/auto-
mation (English).
7
Installation and electrical connection
Electrical connection may only be carried out by a qualified electrician and in accord-
ance with the applicable regulations!