background image

GSA

 

Gas-Fired Steam Boilers – 

User’s Information Manual

8

Part Number 550-110-739/0703

W-T

8201 W. Calumet Rd.
Milwaukee, WI 53223

  Troubleshooting

Shutdown procedure

1. Follow “TO TURN OFF GAS TO APPLIANCE” on the

 

"Lighting

Instructions"

 

on the inside of the jacket panel. You will also find

these instructions on pages 4 and 5 of this manual.

Use the "Lighting Instructions" for the gas valve model installed
on the boiler.

  End of season

2. Do not drain system unless exposure to freezing temperatures

will occur.

3. Do not drain the system if it is filled with an antifreeze solution.

4. Do not shut down boilers used for domestic water heating. They

must operate year-round.

Troubleshooting — Common problems and possible solutions

Symptom

Common Causes

Possible Corrections

Rapid cycling — boiler 
turns on and off 
frequently

Thermostat installed where drafts or 
heat affect reading

Locate thermostat on inner wall away from heat sources or cool drafts.

Heat anticipator in thermostat 
adjusted incorrectly

Adjust thermostat per manufacturer's instructions.

Incorrect limit setting

Set limit according to system needs. Maximum setting is 15 psig. Increase limit setting to 
decrease cycling.

Main air vent not working (one-pie 
steam) or trap not working (two-pipe 
steam)

Contact service technician to check/replace main air vent or trap

Frequent release of 
water through relief 
valve

Inoperative limit control

Call qualified service technician to replace limit control.

Need to frequently add 
makeup water

Leaks in boiler or piping

Have qualified service technician repair leaks at once to avoid constant use of makeup 
water. Makeup water can cause mineral deposits which, in turn, can cause boiler section 
failure.

Black water condition

Oxygen corrosion due to leaks in 
boiler and piping

Have qualified service technician repair at once. Keep pH of water between 7.0 to 8.5.

Popping or percolating 
noise heard in boiler

Mineral deposits in sections due to 
constant use of makeup water

Call qualified service technician to de-lime boiler, if necessary. In some cases, deposits will 
be too heavy to remove with de-liming procedures.

Have qualified service technician repair leaks to eliminate need for constant makeup water.

Incorrect pH of boiler water

Call qualified service technician to check pH level and correct. pH should be maintained 
between 7.0 to 8.5.

Water disappears from 
gauge glass and back 
out into system through 
return piping

Incorrect piping in Hartford loop

Call qualified service technician to inspect. Correct piping, if necessary, to agree exactly with 
Boiler Manual. Clean or replace check valve or vacuum breaker if required.

Check-valve inoperative or leaking

Vacuum breaker inoperative

Metal flakes found in 
vent outlet or vent — 
flueway corrosion

Contaminated combustion air supply 
— See page 2 in this manual.

Remove any contaminating products. See page 2 in this manual.

Provide outside air for combustion. Kit available through local distributor. Have qualified 
service technician pipe-up kit.

Condensation of combustion gases 
in boiler sections

Have qualified service technician inspect system piping and controls to verify proper 
regulation of return water temperature.

Some radiators or 
baseboard units do not 
heat

Main (or radiator) air vents (one-pipe 
steam) or traps (two-pipe steam) not 
operating correctly

Call qualified service technician to inspect/replace air vents or traps

High limit set too low

Adjust high limit to higher setting.

Violent waterline 
fluctuations or surging

Dirt, oil or other impurities in water

Call qualified service technician to skim boiler, referring to Boiler Manual for procedure.

Waterline too high

Correct waterline to maximum height of gauge glass, minimum height of ¼” above bottom 
of gauge glass.

Water passing into 
steam mains — priming

Incorrect piping

Call qualified service technician to inspect piping, correcting to exactly as shown in Boiler 
Manual, if not as shown.

Sudden release of boiler steam 
pressure by action of zone valves

Call qualified service technician to inspect, adjusting valves or replacing with slow-opening 
valves if necessary.

Summary of Contents for RVGP

Page 1: ...e gas odorant Propane boilers only Your propane supplier mixes an odorant with the propane to make its pres ence detectable In some instances the odorant can fade and the gas may no longer have an odo...

Page 2: ...5 Should overheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to pump Instead shut off the gas supply at a location external to the appliance 6 DO NOT use t...

Page 3: ...75 through GSA 250 4 Robertshaw 7200 GSA 075 through GSA 175 5 Service technician covered in Boiler Manual for use only by a qualified service technician Owner maintenance see pages 6 8 for instructio...

Page 4: ...to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob cl...

Page 5: ...n to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to l...

Page 6: ...ing section failure Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler and system components can occur resulting in possible severe personal injury death...

Page 7: ...g the heating season to verify the valve and discharge piping flow freely If corrosion and or deposits are noticed within the valve body testing must be performed more often A try lever test must also...

Page 8: ...ant use of makeup water Call qualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove with de liming procedures Have qualified service technician...