Subject to change

Series FR92K

FR90 fire dampers 

in short lengths

Description

  1  Casing
  2  Damper blade
  3  Damper blade seal
  4  Release element with 

pipe fusible link 70°C

  5  Fusible link holder 

 

on the casing 

 

  6  Enclosed    

closing spring actuator

  7  Bearing axis
  8  Plug connection with 

lip seal

  9  Limit switch (optional)
10   Fusible link holder on 

damper blade

DN

Fire damper

Protective 

grille

A

free

[m

2

]

 d

[mm]

U

[mm]

A

A

[m

2

]

A

free

[m

2

]

Weight

[kg]

100 99.3

0

0.0068

0.004

0.565

0.0049

125 124.3

0

0.0110

0.008

0.685

0.0081

160 159.3

5

0.0185

0.014

0.865

0.0138

200 199.3 25

0.0293

0.024

1.105

0.0221

250 249.3 50

0.0465

0.038

1.715

-

315 314.3 85

0.0747

0.064

2.415

-

Maintenance-free 

FR90 fire dampers according to EN 15650: FR92K series, short length 150 mm 

Fire classification:  

  EI 30/60/90/120 (v

e

 - h

o

, i 

 o) S

Declaration of performance:  DoP no.: CPR/FR90/003

 FR90 fire dampers are essentially made from non-combustible building 

materials. Certification:   Certificate MPA-BS 6000/593/18

  Use in air transfer applications is based on compatibility for approval in accordance 

with the building code in each individual case. Approvals are no longer issued.

Optional accessories:

 

Connecting piece AS 

with traverses for screw fastening 

the protective grille SG1 or SG2 to the operation side 

L1 or non-operation side L2. Sizes DN 100 to DN 200.

   

  

 see pages 2 and 8 to 10

• 

Connecting piece AR 

with 

non-return valve

 and trav

-

erse for screw fastening the protective grille SG1 or SG2 

on the non-operation side L2. Sizes DN 160 to DN 200.

     

 see pages 2, 8 to 10

 

Protective grille SG1

  with  wide  edge  for  installation 

flush with the wall or in combination with the duct frame 

RB. Sizes DN 100 to DN 200

.

  

  

 see pages 2 and 8 to 10

 

Protective grille SG2

 with narrow edge for installation 

flush  with  the  connecting  piece AS.  Sizes  DN  100  to 

DN 200.

    

 see pages 2, 8 to 10

 

Duct frame RB 

for covering connecting piece and pro

-

tective  grille  SG1  which  protrude  from  the  wall.  Sizes 

DN 100 to DN 200.

    

 see pages 2 and 8 to 10

Single-piece casing made of galvanized sheet steel with 

plug connections and lip seals on both sides.
Release element for 70°C nominal temperature. 
Casing leak tightness class C according to EN 1751.

 

Enclosed,  maintenance-free  drive  mechanism  outside 

the  casing  wall,  sealed  drive  axles  made  of  stainless 

steel, with red metal bearings.
For installation in rigid walls and ceilings with a thickness 

of at least 100 mm and in metal stud walls with a thick

-

ness of 95 mm or more.

  

 Installation can be carried out 

with the damper blade axis in the vertical or horizontal 

position, or anywhere in between. Installation with the 

connecting piece AR and non-return valve must be in a 

vertical axis position.
Connection to ventilation ducts made from non-combus

-

tible or combustible materials, or with protective grille.

Optional accessories:

 

Limit switch

 for damper blade position CLOSED. 

 

 see page 11

Nominal sizes DN [mm] 

100 - 125 - 160 - 200 - 250 - 315

Summary of Contents for FR90

Page 1: ...d walls Sizes DN 100 mm to DN 315 mm Fire classification EI 30 60 90 120 ve ho i o S Options Protective grille DN 100 to DN 200 for air transfer applications Non return valves DN 160 and DN 200 Limit...

Page 2: ...esistant damper blade with elastomer lip seal Leak tightness class 3 according to EN 1751 Large free cross section enables Maximum volume flows Minimum pressure loss Minimum sound levels Release eleme...

Page 3: ...DN 100 to DN 200 see pages 2 and 8 to 10 Connecting piece AR with non return valve and trav erse for screw fastening the protective grille SG1 or SG2 on the non operation side L2 Sizes DN 160 to DN 2...

Page 4: ...ers series FR92K can be used at a velocity of up to 15 m s in the inflow cross section AA and up to 2500 Pa operating pressure FR90 fire dampers in short lengths Dimensioning 1 pressure drop sound pow...

Page 5: ...User Manual 5 12 2019 09 5 Subject to change Series FR92K FR90 fire dampers in short lengths Dimensioning 2 pressure drop sound power level with protective grilles connection Installation on one side...

Page 6: ...metal stud walls each with the appropriate fire resistance period The circumferential gap s and the installation gaps between fire dampers must be 15 mm wide The fillings or mortaring must be made as...

Page 7: ...fire walls shaft walls shafts or ducts Required minimum thicknesses for installation of the fire damper W D mm Fire resistance period in minutes 30 60 90 120 Rigid walls 100 Rigid ceilings 100 The met...

Page 8: ...rten on site to 60 mm 235 75 Shorten on site to 60 mm 75 100 L2 L1 Installation opening DN 50 W D1 SG1 SG1 AS AS The damper blade can be installed with the axis in the vertical or horizontal position...

Page 9: ...non return valve must be installed with vertical axes All longitudinal pipe cuts are then horizontal A maximum deviation of 5 is permissible Install connecting piece AR with the non return valve on no...

Page 10: ...flow Sizes DN 100 DN 125 DN 160 DN 200 D1 mm 125 145 185 235 Connecting pieces AS made of galvanized sheet steel are for fitting onto the fire damper plug connections fitted with lip seals Traverses a...

Page 11: ...ate from combustible materials Are suitable for all installation positions Can be installed with a minimum distance of 15 mm also in metal stud walls Electric wiring must be performed on site Maintena...

Page 12: ...00 125 160 200 250 315 10 12 16 20 25 31 pcs limit switch ES FR92K ES pcs connecting piece AS without non return valve FR92K AS DN size 100 125 160 200 10 12 16 20 55 5 5 5 75 7 7 7 7 100 10 10 10 10...

Page 13: ...anized sheet steel on one side on both sides and with a traverse for screw fastening a protective grille With connecting piece made of galvanized sheet steel on one side with metal non return valve an...

Page 14: ...WEENER EMS Utrecht K LN Factory Administration Telephone 49 0 4951 950 0 Fax 49 0 4951 950 27120 E mail info wildeboer de Internet www wildeboer eu Utrecht office Telephone 31 30 767 0150 E mail info...

Reviews: