white
green
brown
white
green
brown
User Manual 5.12 (2019-09) 11
Subject to change
Series FR92K
Assembly:
The connection cable must
be routed towards the
outside on the operation
side (release element side)
of the fire damper. It must
not obstruct the cover level
or the damper blade.
FR90 fire dampers
in short lengths
Optional
accessories, installation, maintenance-free, functional test and servicing
Installation
•
FR90 fire dampers, series FR92K, must be installed
according to the instructions in this user manual.
Structural requirements for walls, ceilings, ventilation
ducts etc. must be met by the customer.
The technical regulations and national statutory
regulations must be observed during installation.
In Germany, this means the “Technical Building
Regulations” (VV TB) and the “Guideline on Fire
Protection Requirements Pertaining to Ventilation
Systems” (Lüftungsanlagenrichtlinie - LüAR).
•
FR90 fire dampers, series FR92K, may be connected
to ventilation ducts made of non-combustible and
combustible materials. Thermal expansion in case
of fire must not subject the fire dampers to notable
forces. Compensatory measures must be provided as
required. In general, the compensation is achieved by
routing ducts appropriately.
•
FR90 fire dampers, series FR92K
•
Do not need spacing to separate from combustible
materials.
•
Are suitable for all installation positions.
•
Can be installed with a minimum distance of 15 mm,
also in metal stud walls.
•
Electric wiring
must be performed on site.
Maintenance-free
•
FR90 fire dampers, series FR92K, are maintenance-
free as a result of the full enclosure, corrosion-resistant
materials and precise manufacture.
The stainless steel operation mechanics are situated in
an enclosure, not in the air flow. There is no requirement
for recurrent cleaning and lubrication.
Damper blades are break-proof. Seals and other
materials are engineered to be durable.
Functional testing and servicing
•
Fire dampers must be maintained by the owner.
Functional checks should be performed periodically
and depend largely on operation of the system. The
regulations must be adhered to.
•
Repairs or service work are required in the event of
malfunctions. Original spare parts must be used.
•
Cleaning work required in ventilation systems for
hygiene reasons must be performed in an operation-
dependent manner, and also includes the fire dampers.
Limit switches
for signalling the damper position
CLOSED can be retrofitted and must be installed on site.
Pack:
Limit switch, cable tie, end nipple for casing wall
installation, strain relief, installation instructions.
Electrical connection:
Limit switch is not actuated
Limit switch is actuated
Connection cable colour coding
Operating instructions
for FR92K series FR90 fire dampers available for download at www.wildeboer.eu