Additional operating instructions TC82, TC83, intrinsically safe designs (Ex i)
5
Models series TC82-F-*IO or TC83-F-*IO (gas and dust application)
Variant
Electrical
data
Temperatures
Marking
Ambient
1)
Temperature
class
Variant 1:
Empty
enclosure
U
i
= DC 30 V
I
i
= 110 mA
P
i
= 500 mW
L
i
, C
i
= negligible
-40 … +85 °C
-60 … +85 °C
N/A
II 2/-G Ex ia IIC T*(2) Gb/-
II 2/-D Ex ia IIIC T135 °C Db/-
Variant 2:
Empty
enc
electronic
See electronics
3)
See electronics
3)
See electronics
3)
II 2/-G Ex ia IIC T*(2) Gb/-
II 2/-D Ex ia IIIC T* Db/-
Variant 3:
Field
transmitter
See transmitter
3)
See transmitter
3)
See transmitter
3)
II 2/-G Ex ia IIC T*(3) Gb/-
II 2/-D Ex ia IIIC T*(3) Db/-
1) For variant 1 and 2: The low ambient temperature -40 °C applies to models with Limatherm or Rosemount cases. The low ambient
temperature of either -40 °C or -60 °C applies to models with WIKA connection head series 1/4000, 5/6000, 7/8000. For explanation
of symbols for low temperature range see chapter 2.5 “Labelling, safety marks”
2) The temperature class depends on the ambient temperature.
3) The parameters for variant 2 and variant 3 Transmitters have to be taken out of the related operating instructions.
When there is a built-in transmitter and/or a digital display, the special conditions from the
type examination certificate (see chapter 4 “Special conditions for use (X conditions)”)
apply.
1. Ex marking