Operating instructions model OLS-C20
5.2 Electrical connection
The electrical connection of the switches can be found in the following
connection diagrams.
Electrical connection diagram
6. Faults
The following table contains the most frequent causes of
faults and the necessary countermeasures.
Faults
Causes
Measures
No function
Failure in power supply
Measure voltage, check
cable or plug connection
Despite a change in
level, no alteration
in the display and
no switching of the
output
Glass tip dirty
Clean the glass tip
(introduce service intervals)
Glass tip too close to an
opposite surface
Increase the distance,
change the mounting
location
Glass tip defective
Return to the manufacturer
Instrument responds
inversely
Wrong switching function
(normally open, normally
closed)
Replace instrument
Connector assignment
brown
green
white
Output
Load
24 V
0 V
Output
24 V
0 V
5. Commissioning, operation / 6. Faults