5 Connecting to power supply
WIKA Operating Instructions - Process pressure transmitter CPT-2x
5.2 Connecting
The connection to the Master sensor is carried out through spring-
loaded terminals in the respective housing. For this, use the supplied,
confectioned cable. Solid cores as well as flexible cores with cable
end sleeves are inserted directly into the terminal openings.
In case of flexible cores without end sleeves, press the terminal from
above with a small screwdriver, the terminal opening is then free.
When the screwdriver is released, the terminal closes again.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.
You can find further information on the max. wire cross-section under
"
Technical data - Electromechanical data
".
Proceed as follows:
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) insulation from the individual wires or use supplied
connection cable
4. Insert the cable into the sensor through the cable entry
Fig. 21: Connection steps 5 and 6
5. Insert the wire ends into the terminals according to the wiring plan
6. Check the hold of the wires in the terminals by lightly pulling on
them
7. Connect the shielding to the internal ground terminal, connect the
external ground terminal to potential equalisation
Connection technology
Connection procedure