8
This is indicated by 3 dashes "---" appearing for a few seconds after
which OuX appears, standing for "Output signal X", where "X" stands for
figures 1 to 3 as explained below. Change this value as desired by hitting
the (
) and (
) keys.
X = 1:
Ou1
= Output signal voltage 0 ... 10 V
X = 2:
Ou2
= Output signal current 0 ... 20 mA
X = 3:
Ou3
= Output signal current 4 ... 20 mA
Press PROG once more: The new value will be memorised .This is
indicated by 3 dashes "---" appearing for a few seconds.
Subsequently "-d- (damping)" appears automatically. After hitting the
key once more the current setting of the damping is displayed. The
damping can be set within a range of 0.1 s ... 50.0 s. The damping can
be changed in 0.1 s steps using the (
) and (
) keys.
The damping is adapted from the behaviour of a capacitor. After the set
time (=t) has passed, approx. 63% of the changed value is applied. After
5 x t has passed, approx. 97% of the changed value is applied.
Press PROG once more: The new damping value will be memorised.
This is indicated by 3 dashes "---" appearing for a few seconds.
Then dXX (reference of damping) is displayed. XX stands for the selected
setting. The damping can be activated for the display, the analogue
output signal, the alarm contacts and the MIN / MAX memory in any
combination as specified in the following table:
Summary of Contents for A-RB-1
Page 1: ...Operating Instructions Digital Indicator Model A RB 1 ...
Page 34: ...34 89 5 47 5 95 7 173 5 Appendix C Dimensions Dimensions in mm ...
Page 35: ...35 8 9 42 3 45 0 6 92 0 8 Panel cutout in mm Dimensions in mm ...
Page 36: ...36 A B C D E F G H I d e h Appendix D Layout of front and back panel ...
Page 38: ...38 For your notes ...
Page 39: ...39 For your notes ...