gesisNRG

 GST18i5 

EN 

 

 

INFO 

 

All gesisNRG system components may only be installed, commissioned and maintained by 
qualified electricians. 

 

Personnel who install, program, operate or maintain this device must have read and 
understood these instructions. 

 

The relevant standards, guidelines, regulations and provisions of the respective country 
must be observed. 

 

Protective measures and mechanisms must correspond to applicable regulations.  

 

Damaged products may neither be installed nor operated. 

 

In case of a defect, please return the component to Wieland Electric. 

 

Never use components from third-party manufacturers. No guarantee shall be offered for 
damage resulting from a combination with third-party components. 

 

Please keep these instructions in a safe place for later reference. 

 

 

CAUTION! 

 

Use only blue system components for blue flat cables (DIMM).  

 

Use only black system components for green and black flat cables (BASIC). 

 

No hazardous interchangeability with systems based on IEC 60309, IEC 60320, IEC 60906 
and with national connector and socket systems for home use. 

 

Interchangeability between installation connector systems from different manufacturers is 
not automatically prevented by compliance with EN 61535. 

 

Compatibility with products from other manufacturers cannot be guaranteed. 

 

Installation connectors do not replace national connector/socket systems for home use.  

 

Unused connectors must be provided with closures in easily accessible areas. 

 

WARNING 

 

If the feed-in module is later shifted on the flat cable, then the contact openings in the 
cable must be closed by cable patches! 

 

Never install or remove while energized. 

 
The components of the GST18

® 

system are used to distribute energy and/or data in building 

interiors. 
 

1

 

Scope of supply (pre-assembled) 

The supplied components and cables may neither be changed nor modified.  

 

Baseplate 1x 

 

Equipped connecting module 1x 

 

Cover 1x 

 

2

 

Borehole dimensioning 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3

 

Mounting 

1.

 

Lay the flat cable in a suitable 
cable routing system. Note the 
laying direction for the outlet di-
rection of the connectors. Insert 
the flat cable concisely into the 
coded baseplate  
(92.050.1553.1 for green/black 
cable, 92.051.5553.0 for blue ca-
ble).  

 

 
 
 
 
2.

 

Use the two mounting holes to 
attach the optional baseplate to 
the desired subsurface. 

 
 

 
 
 

 
 
 

 
 
 

 

 

3.

 

Close the connecting module and 
latch it with a clearly audible 
click. 

 
 
4.

 

Tighten all of the contact screws 
consecutively (0.5 Nm). 

 
 
 
 
 
 
 
 
 
 
 
5.

 

Close the cover and latch it with a 
clearly audible click. 
 
Caution: 
The screws are not all correctly 
tightened if the cover does not 
completely close! 
 
 

6.

 

Attach GST18i5 connector and latch it with a clearly audible click. 

 
 
 

4

 

Removal 

1.

 

Use a tool (screwdriver) to release 
the connector interlock and re-
move the connector. 
 
 
 
 
 
 

2.

 

Use a screwdriver to press the interlock lugs 
in the direction of the arrow and open the 
cover. 

 
 
 
 
 
 
 
 
 
 
 
3.

 

Loosen the contact screws. 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
4.

 

Use a tool (screwdriver) to 
unlatch the baseplate interlock 
and to release the module from 
the flat cable. Use cable patch to 
seal openings in the insulation. 

 
 
 
 
 
 
 
 

5

 

Technical data 

Rated voltage  

250 / 400 V 

Rated current  

20 A 

Protection class 

Protection type  

IP20 (inserted IP40) 

Tightening moment of the 
contact screws 

0.5 Nm 