Mounting, wiring and demounting
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
25
5.3
Wiring
Consider temperature for external cables!
Cables may experience temperature increase due to system heat dissipation. Thus the cabling speci-
fication must be chosen 5 °C above ambient temperature!
Separate insulation areas!
The system is specified for SELV/PELV environment. Devices, which are attached to the system must
meet theses specifications. Installation and cable routing other than SELV/PELV specification must
be separated from the system’s equipment!
5.3.1
Wiring bus coupler
Terminal module terminals
The
ricos
FLEX bus couplers have an integrated power module. Terminals with spring clamp technol-
ogy are used for wiring. The spring clamp technology allows quick and easy connection of your sig-
nal and supply lines. In contrast to screw terminal connections this type of connection is vibration
proof.
Data
U
max
DC 30 V
I
max
10 A
Cross-section
0.08 … 1.5 mm² (AWG 28 … 16)
wire strip length 1000 mm
Wiring procedure
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
Insert a suited screwdriver at an angel into the square opening as shown.
Press and hold the screwdriver in the opposite direction to open the contact spring.
Insert the stripped end of wire into the round opening. You can use wires with a cross section of
0.08 mm² up to 1.5 mm².
By removing the screwdriver, the wire is securely fixed via the spring contact to the terminal.