INSTALLATION R
REQUIREMENTS
This appliance MUST NOT be installed into a room containing a bath or shower, or where steam may be
present. The fire has been designed to fit into a pupose made builders’ opening meeting certain dimensional
requirements.
The flue must have an effective height of at least three meters, as measured from the hearth to the top of the flue.
Any flue damper plates or restrictors should be removed and no other restriction fitted to the flue. Where removal
is not practical, the restriction must be fixed in the fully open position.
A natural draught flue system is required, and if previously used for solid fuel or oil burning, the flue and chimney
must be swept prior to appliance installation. The flue must be checked before installation by using a smoke pel-
let or similar to ensure proper draw and that leakage is not evident at any joints. Repair and re-test as necessary
before the appliance is installed.
2
APPLIANCE D
DATA
Manual Control Versions
Log Version
Glass and Pebble Version
Gas Group
G20 Natural Gas CAT I2H
G20 Natural Gas CAT I2H
Inlet Pressure
20 mbar
20 mbar
Max Energy Input (gross)
6.8 kW
6.8 kW
Min Energy Input (gross)
3.5 kW
4 kW
Pilot Energy Input (gross)
166 W
166 W
Setting Pressure - High (cold)
16.25 mbar (+/- 0.75mbar)
*****mbar (+/- 0.75mbar)
Setting Pressure - High (hot)
16.5 mbar (+/- 0.75mbar)
*****mbar (+/- 0.75mbar)
Setting Pressure - Low (hot)
5.5 mbar (+/- 0.5mbar)
*****mbar (+/- 0.5mbar)
Main Injector Burner
Bray cat. 82/440
Bray cat. 82/440
Gas Inlet Connection
8mm compression
8mm compression
Ignition
Integral Piezo spark
Integral Piezo spark
Spark Gap
3.5 to 4.5mm
3.5 to 4.5mm
Weight
40 Kg
40 Kg
Please see Data Badge affixed to appliance for current data.
This aappliancce iis ffor uuse oonlyy w
with tthe ggas ttyype, aand aat tthe ppressure sstated oon tthe aappliancce
Data BBadge, aand iis ffor ddeccorative ppurposes.
2.0
3.0
‘A’
‘B’
‘C’
A. Opening height:
670mm Min. / 710mm Max.
B. Opening width:
785mm Min/865mm Max.
C. Opening depth: 350 mm Min.
D. This area must be flat and ver-
tical to ensure a good seal.
‘D’