NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
18
IMPORTANT NOTES:
A fl exible corrugated chimney liner has much greater resistance to
the fl ow of fl ue gases than does a rigid liner. For this reason we
recommend that a larger, 4” liner be used on vertical runs exceeding
15 feet or that rigid venting be used as illustrated on this page (see
Full Chimney Reline).
If a fl exible corrugated chimney liner is used, it must be fully extended
to eliminate any sagging and to improve the exhaust fl ow.
Do not block opening at front of insert (below door).
Figure 30 - Full Chimney Reline
Full Chimney
Reline (required when
installing into a Factory
Built Fireplace)
Approved Liner for Factory Built
(ZC) Fireplaces and Masonry
Fireplaces is 2100HT (degree
F.) liner listed to UL 1777 or
ULC S635. The liner must be
securely attached to the insert
fl ue collar and the chimney top.
Positive Flue
Connection
Recommended
6”
Min.
Clean-Out
Tee
Listed Pellet
Vent Cap
Standard Installation Confi gurations Into an Existing Fireplace
Model: Profi le
®
30 INS-2
IMPORTANT
Make sure the chimney and fi rebox are clean and free of soot and ashes before installation begins. Failure
to do so may result in the transfer of soot into the room by way of the room air blower.
U.S.A. – The insert may be
installed as a Direct Vent (hori-
zontal vent through the chimney
structure) in masonry fi replaces
if local codes will permit.
Canada – Installing an insert a s
a Direct-Vent is not allowed. The
fi replace chimney must be fully
relined from the insert outlet to
termination.
IN CANADA – Installing as a Horizontal
Vent is not allowed. The fi replace
chimney must be fully lined.
Horizontal Vent
(Direct Vent)
Figure 31 - Horizontal Direct Vent
Listed Pellet Vent
Termination Cap
Chase Cover
1 foot Section of PL
Vent (listed to UL 641
or ULC S609)
3” or 4” liner
(listed to UL 1777
or ULC S635)
Figure 32 - Existing Chimney Termaination
18” Min.
(457 mm)
to Mantel
1” Min.
(25 mm)
to Trim
Model: Profi le 30 INS-2
Model: Profi le 30 INS-2
18” Min.
(457 mm)
to Mantel
1” Min.
(25 mm)
to Trim
6”
Min.
Termination When
Connected to
Masonry Chimney
or
Existing Class
A Chimney