background image

Please note: All images shown are for illustration purposes and should be used only for reference. 

 

General Description

 

Florin E3 is a range of stand-alone IP65 LED 
emergency luminaires incorporating a driver and 
battery pack in a plastic housing. The luminaire 
contains a high-power white LED and indicator LED 
for emergency use only. 

The LED control gear has reinforced insulation 
between the supply and the battery circuit, and a 
battery charger with short circuit protection that will 
continue to operate when the short is removed. 

Batteries (where applicable) 

The luminaire includes a 1.5Ah rechargeable 
LiFePO

4

 battery pack for 3 hour operation. When 

the luminaire no longer meets the 3 hours duration 
the battery should be replaced.

 

Relevant Standards 

EN 61347-2-7         Lamp control gear                   
EN 61347-2-13       LED control gear                      
EN 60598-2-22       Luminaire  

IMPORTANT: 

Please ensure that the information contained in this 
leaflet is passed on to the user/maintenance engineer. 

Mark the luminaire with the date of commissioning in 
the space provided on the battery label. 

The battery lead should only be connected at the time 
of commissioning.  

When the supplies and battery leads are connected, 
the white cover should be 

‘clicked’ into place to 

prevent electric shock. 

The LED is non-replaceable. Contact Whitecroft 
Lighting in the unlikely event of a failure. 

Operation 

– integrated battery versions 

Upon connection of a permanent mains supply the 
indicator LED lights to show the battery is receiving 
charge. Following an initial charging period, 
commissioning test and a subsequent charging period 
of 24 hours the unit will be capable of providing 3 
hours emergency duration. 

Operation 

– central battery 

When power is supplied to the luminaire supply inputs, 
the high-power LED will light.  

 

Installation 

The luminaire must be installed by a qualified person 
in accordance with the current building and wiring 
regulations. Luminaires comply with the EMC directive 
in both modes of operation, mains and emergency. 

The luminaire is designed to be surface mounted onto 
a ceiling.  

Automatic Commissioning      
(FLS31EP/65, FLS32EP/65 & FLSH31EP/65 only)                    

 
Please note there is no need to do a manual test on 
this product. 
 
If in the unlikely event a manual test needs to be 
undertaken please ensure it has completed the 
commissioning phase as per the table below. 
 
Do not connect the batteries until there is a

 reliable

 

permanent mains supply present as a mains 
interruption will rest the commissioning test clock. 
 
The commissioning test will start when the permanent 
supply and batteries are connected. 

 
Commissioning phase table  

 

 

 

 

 

Stage 

Hours 

Status 

LED 

Indication 

upto 

24 

Battery 

charging 

Flashing 

green 

Discharge test 

Flashing 

green 

24 

Battery 

charging 

Flashing 

green 

Commissioning 

complete 

Constant 

green 

Total 

51 

  

  

 

Reviews: