CHECK THERMOSTAT OPERATION

CONTINUED FROM PAGE 4

5

1

Step

Press Button(s)

Displayed 

Press         or

(Factory Default)

to select:

2

HP

4*

Configuration Menu

3

Set SYSTEM

switch to OFF

no HP

and

for at least 2 seconds

and

momentarily

and

momentarily

SL

FA

OFF

L

˚C

˚F

5

OFF

7

6

CL

(OFF)

3 LO TO

3 HI

FA

(ON)

and

momentarily

and

momentarily

and

momentarily

ON

0 HI

(0)

8

and

momentarily

* Not available on this model

ELECTRICAL DATA

Electrical Rating:

20 to 30 VAC 50/60 Hz.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)

THERMAL DATA

Setpoint Temperature Range:

45

°

F to 90

°

F (7

°

C to 32

°

C)

Operating Ambient Temperature Range:

32

°

F to 105

°

F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-40

°

F to 150

°

F

SPECIFICATIONS

6

Configuration Menu

The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal requirements.

The menu mode may be exited by pressing the system key to
change from the OFF mode or after 15 minutes has elapsed with
no keypad activity.

2.   Multi-stage or Heat Pump Output Configuration – This control

can be configured for Heat Pump or two stage heat/two stage
cool multi-stage operation. The display indicates no HP (de-
fault for multi-stage mode) in the display. The Multi-stage
configuration can be toggled to HP (Heat Pump mode) by
pressing the Temperature Up or Temperature Down key. In
Multi-stage configuration, system key selection will skip
EMERgency mode.

3.   Fast or Slow Cycle Selection – The factory default setting is

fast cycle, which cycles 1st stage at approximately 1.2˚F and
2nd stage 0.75˚F. If you prefer slow cycle, press the tempera-
ture key to change to SL. The 1st stage and 2nd stage would
be 1.5˚F and 1.2˚F respectively.

4.   Display light – Not available on this model.

5.   In the run mode, if the setpoint temperature is manually raised

by 3

°

F (2

°

C) or more above the actual temperature with the

TEMPERATURE UP key, and the fast second stage feature is
enabled, FA on, the second stage will energize immediately.
With FA off, second stage will not energize until the setpoint
temperature is 1

°

F or more above actual temperature for more

than ten minutes.

6.  Select Compressor Lockout CL OFF or ON – Selecting CL

ON will cause the thermostat to wait 5 minutes before turning
on the compressor if the heating and cooling system loses
power. It will also wait 5 minutes minimum between cooling and
heating cycles. This is intended to help protect the compressor
from short cycling. Some newer compressors already have a
time delay built in and do not require this feature. Your com-
pressor manufacturer can tell you if the lockout feature is
already present in their system. When the thermostat compres-
sor time delay occurs it will flash the Snowflake and Flame
Icons
 for about five minutes.

7.  Select Temperature Display Adjustment 3 LO to 3 HI 

Allows you to adjust the room temperature display up to 3

°

 higher

or lower. Your thermostat was accurately calibrated at the
factory but you have the option to change the display temperature
to match your previous thermostat. The current or adjusted
room temperature will be displayed on the left side of the display.

8.  ˚F or ˚C Selection – The factory default setting for temperature

display is Fahrenheit. If you want the temperature in Celcius,
press temperature key to change to ˚C.

9 Displays currently programmed set temperature (this is blank

when SYSTEM switch is in the OFF position).

10 Stage 1 & 2 Indicators: The thermostat shall indicate when

the first and second stage is energized except in emergency
mode. The icon is STG 1 for the first stage energized. The
icons for the first and second stage energized are STG1+2
located in the lower right side of the display.

OPERATION

The system “mode” is selected by pressing the system key. Icons
on the bottom right corner of the display will indicate the mode;
COOL ( ), AUTO (   ), HEAT ( ), EMER, or OFF. In any mode
except OFF, the setpoint temperature will be shown on the right
side of the display. In OFF, this area will be blank. The current
temperature will be displayed on the left side of the display.

To operate properly in the AUTO mode, the heat setpoint tempera-
ture cannot be the same as or higher than the cool setpoint
temperature. The heat setpoint must be at least 1˚ lower than the
cool setpoint. If you are unable to raise the setpoint temperature
in HEAT or lower the setpoint temperature in COOL, you may be
at the 1˚ difference. To obtain the temperature you wish to set,
change to the opposite mode and move that setpoint away from
your temperature.

7

www.white-rodgers.com

Summary of Contents for IF73

Page 1: ...at a time DO NOT LET WIRES FALL BACK INTO THE WALL 6 Install new thermostat using the following procedures To prevent electrical shock and or equipment damage disconnect electrical power to the system...

Page 2: ...ch require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay...

Page 3: ...y Switches 24 VAC Limit or Safety Switches COMMON COMMON Auxiliary Heating Transformer Class II Current Limited Heat Pump Transformer Class II Current Limited 24 VAC ACCESSORY RELAY N O CONTACT Polari...

Page 4: ...s for specific sys tem wiring informtion You can configure the thermostat for use with the following heat pump system types HEAT PUMP TYPE 1 Single stage compressor system gas or electric backup This...

Page 5: ...ate The Flame icon will display flashing to indicate that the Aux system is operating 3 Press to adjust the thermostat below room temperature The Aux heating system should stop operating To prevent co...

Page 6: ...tes 6 Select Compressor Lockout CL OFF or ON Selecting CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power It will also wai...

Page 7: ...ction to thermostat or system Verify thermostat and system wires are securely attached 3 Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement con...

Page 8: ...and the size The cycle rate for cooling is fixed and can not be narrow or wide temperature swing of the Cooling System can influence the adjusted Contact a local service person for cycle rate suggest...