background image

www.white-rodgers.com

MOUNTING AND WIRING

CONTINUED FROM PAGE 2

4

L

R

E/W1

24 VAC

120 VAC

Hot

SYSTEM

MONITOR

SWITCH

Neutral

THERMOSTAT

SYSTEM

G

W2

Figure 2. Typical wiring diagram for single transformer heat pump systems

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

C

Y1

O/B/Y2

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux

Relay

(Stage 2)

Fan

Relay

Emergency

Relay

See Note **

** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency

L

R

E/W1

SYSTEM

MONITOR

SWITCH

G

W2

Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems

Changeover

Relay*

C

Y1

O/B/Y2

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux

Relay

(Stage 2)

Fan

Relay

Emergency

Relay

TWO COMMONS MUST
BE JUMPERED TOGETHER!

24 VAC

120 VAC

HOT

NEUTRAL

THERMOSTAT

SYSTEM

HOT

NEUTRAL

120 VAC

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

24 VAC

Limit or

Safety

Switches

COMMON

COMMON

Auxiliary

Heating

Transformer

(Class II

Current Limited)

Heat Pump Transformer

(Class II Current Limited)

24 VAC

ACCESSORY

RELAY N.O.

CONTACT

Polarity must be observed. If the HOT side of the second transformer 
is jumpered to the COMMON side of the first transformer a short will 
be made. Damage to equipment will occur when power is restored.

NOTE

The  accessory relay scheme 
is required when safety 
circuits exist in both systems.

NOTE

See Note **

** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency

L

R

E/W1

24 VAC

120 VAC

Hot

SYSTEM

MONITOR

SWITCH

Neutral

THERMOSTAT

SYSTEM

G

W2

Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

C

Y1

O/B/Y2

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux

Relay

(Stage 2)

Fan

Relay

Emergency

Relay

Limit or

Safety

Switches

TWO COMMONS MUST
BE JUMPERED TOGETHER!

HOT

NEUTRAL

120 VAC

24 VAC

CUT AND

TAPE OFF!

If safety circuits are in only one of the systems, remove 
the transformer of the system with NO safety circuits.

NOTE

** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency

See Note **

Summary of Contents for IF73

Page 1: ...at a time DO NOT LET WIRES FALL BACK INTO THE WALL 6 Install new thermostat using the following procedures To prevent electrical shock and or equipment damage disconnect electrical power to the system...

Page 2: ...ch require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay...

Page 3: ...y Switches 24 VAC Limit or Safety Switches COMMON COMMON Auxiliary Heating Transformer Class II Current Limited Heat Pump Transformer Class II Current Limited 24 VAC ACCESSORY RELAY N O CONTACT Polari...

Page 4: ...s for specific sys tem wiring informtion You can configure the thermostat for use with the following heat pump system types HEAT PUMP TYPE 1 Single stage compressor system gas or electric backup This...

Page 5: ...ate The Flame icon will display flashing to indicate that the Aux system is operating 3 Press to adjust the thermostat below room temperature The Aux heating system should stop operating To prevent co...

Page 6: ...tes 6 Select Compressor Lockout CL OFF or ON Selecting CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power It will also wai...

Page 7: ...ction to thermostat or system Verify thermostat and system wires are securely attached 3 Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement con...

Page 8: ...and the size The cycle rate for cooling is fixed and can not be narrow or wide temperature swing of the Cooling System can influence the adjusted Contact a local service person for cycle rate suggest...

Reviews: