WIRING CONT.

DIAGRAM FOR BOILER WITH TANKLESS DOMESTIC COIL

X

X

T

1

4

2

3

T

5

6

X

X

TRANS.

HIGH LIMIT

24 VAC

GAS VALVE

Fig. 5a & 6a Diagram for

Gas-Fired System

 THERMOSTAT

TYPE 668 OIL

BURNER CONTROL

(LINE VOLTAGE)

HOT

LINE

     N

TYPE 11B05

CIRCULATOR

CONTROL

BURNER

MOTOR

CIRCULATOR

MOTOR

IGNITION

TRANS.

HIGH
LIMIT

LOW
LIMIT

TYPE

11B30

 THERMOSTAT

TYPE 668 OIL

BURNER CONTROL

(LINE VOLTAGE)

FIELD

INSTALLED

JUMPERS

BURNER

MOTOR

CIRCULATOR

MOTOR

HOT

LINE

 N

IGNITION

TRANS.

CIRCULATOR

CONTROL

HIGH

CONTROL

LOW
LIMIT

Fig. 5 Diagram for System using High Limit-Low Limit
control and Circulator control.

Fig. 6 Diagram for System using High Limit control and
Low Limit-Circulator control.

The low limit control maintains domestic hot water at
desired temperature year-round.

When the thermostat calls for heat, the burner starts. The
circulator also starts if boiler temperature is above setting
of circulator control.

If excessive boiler temperature causes high limit to open,

the circulator continues to run but the burner shuts down
until the high limit recloses.

When low boiler temperature causes the circulator control
to open, burner stays on but the circulator stops until the
circulator control recloses. When thermostat is satisfied,
the circulator stops. The burner also shuts down if boiler
temperature is above setting of low limit control.

T

1

4

2

3

T

5

6

ZC

ZR

B1

B2

C1

C2

1

2

T

T

THERMOSTAT

ZONE 2

THERMOSTAT

ZONE 1

TO CIRCULATOR
ZONE 1

HOT

LINE

N

TO BURNER

TO ADDITIONAL 829A-845 RELAYS

FOR OTHER ZONES

*CIRCULATOR

ZONE 2

JUMPER

*Terminal No. 4 or No. 6 may go to zone 2,

The other terminal then goes to ZR.

DIAGRAM FOR MULTIZONE HYDRONIC HEATING SYSTEM

Fig. 7

FIELD

INSTALLED

JUMPERS

X

X

T

1

4

2

3

T

5

6

Summary of Contents for 829A-845

Page 1: ...240V A C 6F L A 36L R A Pilot Duty 50VA 24 Volts SPECIFICATIONS To prevent electrical shock and or equipment damage disconnect electric power to system at mainfuseorcircuitbreakerbox untilinstallation is complete If in doubt about whether your wiring is millivolt line or low voltage have it inspected by a qualified heating and air conditioning contractor electrician or someone famil iar with basic...

Page 2: ... for heat both the burner and circulator start If excessive boiler temperature causes high limit to open the circulator continues to run but the burner shuts down until the high limit recloses When the thermostat is satisfied both the burner and circulator stop Fig 3a 4a Diagram for Gas Fired System T 1 4 2 3 T 5 6 Fig 2 BURNER MOTOR THERMOSTAT FIELD INSTALLED JUMPERS Fig 3 TRANS HIGH LIMIT 24 VAC...

Page 3: ...ture year round When the thermostat calls for heat the burner starts The circulator also starts if boiler temperature is above setting of circulator control If excessive boiler temperature causes high limit to open the circulator continues to run but the burner shuts down until the high limit recloses Whenlowboilertemperaturecausesthecirculatorcontrol to open burner stays on but the circulator sto...

Page 4: ...celui ci par un électricien par un entrepreneur agréé en chauffage et climatisation ou par une personne qui a des connaissances de base en électricité et en câblage Ne dépassez pas les charges nominales Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques Cette commande est un instrument de précision qui doit être manipulé avec ...

Page 5: ...de d unrelaisunipolaireunidirectionnel SPST detype809Aau lieu d un relais bipolaire unidirectionnel DPST de type 829A Référez vousauschémadecâblagefourniavecles directivesdurelaisdetype809A NOTE CÂBLAGE Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques SOUS TENSION RÉSEAU N VERS LA CHARGE VERS L ALIMENTATION THERMOSTAT À BASS...

Page 6: ...ue de fonctionner mais le circulateur s arrête jusqu à ce que le circuit de la commande du circulateur soit à nouveau fermé Une fois le thermostat satisfait le circulateur s arrête Le brûleur s arrêteaussisilatempératuredelachaudièreestsupérieureau point de consigne du limiteur minimum T 1 4 2 3 T 5 6 ZC ZR B1 B2 C1 C2 1 2 T T VERS LES RELAIS 829A 845 ADDITIONNELS DES AUTRES ZONES CAVALIER Fig 7 M...