background image

33740-9-1015

Page 53

33740-9-1015

Page 52

CONTROL SYSTEM TROUBLESHOOTING

2

Main burner lights

when the pilot only

should light.

Pilot holds the flame?

Main burner ignites?

Main burner remains

ON?

1.

Replace IFC board.

2.

Replace the gas valve.

1.

Verify the pilot flame fully engulfs the tip of the sense electrode. If not, replace the pilot

assembly.

2.

Replace the pilot assembly.

3.

Carefully clean the electrical connections of the sense cable and the IFC board sense cable

connection.

4.

Replace the sense cable, the cable-sense electrode assembly, or the pilot assembly.

5.

Verify the pilot is properly grounded.

6.

Replace the pilot orifice with a new orifice of correct size and type or replace the pilot

assembly.

7.

If pilot flow adjuster screw is not sealed, correct it.

1.

Verify the electrical connections’ integrity and make sure they are in accordance with the

relevant system wiring diagram. If necessary, replace the wire harness.

2.

Check if the optional remote transmitter is in “thermostat” or “on” mode and verify there is a

call for heat (if using a thermostat remote). Adjust the setting for heat.

3.

Verify that the pilot hood is properly fitted and a pilot flame is directed to properly ignite the

main appliance burner.

4.

Replace the main burner orifice with a new orifice of correct size and type or replace the

pilot assembly. Under all circumstances, follow the service instructions.

5.

Remove the provided wiring harnesses from EV2 of gas valve (red base) and verify voltage

at ignition between the EV1 terminal and the ground connection on the valve body.
5.1

If the voltage is greater than 0, then replace valve.

5.2

Or Replace IFC.

6.

Check the pressure at the outlet pressure test point out according to the manufacturer’s

instruction. If not in accordance, replace the gas valve.

1.

Verify the electrical connections’ integrity and make sure they are in accordance with the

relevant system wiring diagram. If necessary, replace the wire harness.

2.

Check the pressure at the outlet pressure test point out according the manufacturer’s

instruction. If not in accordance, replace the gas valve.

3.

With the system in the OFF position, connect the voltmeter between the EV2 terminal

(green base) on the valve and the ground on the valve body.
Turn the system ON, let pilot light, and observe the following voltage sequence: once the pilot
flame is proved, the voltage on EV2 should spike to approx. 5 VdC for approx. 2 sec and then
drop to approx. 0.6 VdC continuously.
3.1

If the sequence is followed, replace the gas valve.

3.2

If the sequence is not followed, replace the IFC board.

YES

YES

YES

NO

NO

NO

NO

Main burner

modulates

properly?

1.

Replace the main burner orifice with a new orifice of correct size (partial blockage possible).

Verify that the main burner flame modulates. If it does not modulate, replace the gas valve.

2.

Verify that the gas valve outlet pressure limits are in accordance with the manufacturer

specifications. If not, replace the gas valve.

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR 

EXpLOSION MAY RESULT CAUSING pROpERTY DAMAGE, pERSONAL INjURY, OR 

LOSS OF LIFE.

A.  This appliance must be lighted with the remote control. 

When lighting the pilot, follow these instructions exactly.

B.  BEFORE LIGHTING, smell around the appliance area for 

gas. Be sure to smell next to the floor because some gas 

in heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

•  Do not try to light any appliance.

•  Do not touch any electrical switch.

•  Do not use any phone in your building.

•  Immediately  call  your  gas  supplier  from  a 

neighbor's phone. Follow the gas supplier's 

instructions. If you can not reach your gas 

supplier, call the fire department.

C.  Use only the remote control to operate the valve. Never 

use tools. If valve does not operate, don't try to repair it, 

call  a  qualified  service  technician.  Force  or  attempted 

repair may result in a fire or explosion.

D.  Do not use this appliance if any part has been underwater. 

Immediately call a qualified service technician to inspect 

the appliance and to replace any part of the control system 

and any gas control which has been underwater.

LIGHTING INSTRUCTIONS

TO TURN OFF GAS TO APPLIANCE

1.  Turn off all electric power to the appliance if service is to 

be performed (if applicable).

2.  Locate On/Off gas cock and turn clockwise to 

 

"OFF." Do not force.

LIGHTING INSTRUCTIONS

1.  STOp! Read the safety information above.

2.  Turn OFF electric power to the appliance.

3.  Turn gas cock counterclockwise 

 to "ON" 

position.

4.  Wait ten minutes to clear out any gas. Then smell for gas, 

including near the floor. If you smell gas, STOP! Follow 

"B" in the safety information above on this label. If you 

do not smell gas, go to the next step.

5.  Turn ON electric power to the appliance.

6.  Using the remote control, turn main flame to "ON." Refer 

to the Multifunction Remote Operating Instructions for 

more information. If the pilot does not light within 60 

seconds, stop and go back to Step 4.

7.  Refer to remote control instructions for detailed 

information, control features, and operation. Note: 

Refer to Multifunction Remote operating instructions 

for selection of  continuous standing pilot mode or 

intermittent pilot mode. If the pilot or burner does not stay 

lit (in the standing pilot mode), stop and immediately call 

a qualified service technician or gas supplier.

8.  If the burner or pilot does not operate properly after 

several tries, turn the gas control knob clockwise 

 to "OFF" and call your service technician or 

gas supplier.

9.  Operation of the gas valve, blower, and/or optional light 

must be controlled by using the hand held remote control. 

Refer to remote instructions for detailed operation 

information.

IGNITOR

Summary of Contents for DVTL27FP90N-1

Page 1: ...ult in serious injury death or property damage Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbor s phone Follow the ga...

Page 2: ...1 3 AA Battery R10592 4 4 AAA Battery R10600 3 5 Wall Thimble Spacer 33331 1 6 Cover Plate Battery Box R11783 1 7 Remote R11550 1 TABLE OF CONTENTS INTRODUCTION 4 SPECIFICATIONS 5 ACCESSORIES 6 FIREPLACE DIMENSIONS 7 CLEARANCES 8 9 TERMINATION CLEARANCES 10 VENT TERMINAL CLEARANCES 11 GAS SUPPLY 12 13 LOCATING FIREPLACE 13 ELECTRICAL CONSIDERATIONS 14 INSTALLATION 15 19 VENT SYSTEM IDENTIFICATION ...

Page 3: ...th local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code Available from the American National Standards Institute Inc 11 West 42nd St New York N Y 10036 Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsib...

Page 4: ...ce excluding nailing flanges 37 3 8 C The maximum depth of the firebox 26 D The height of the firebox opening 37 E The width of the firebox opening 28 1 4 F The interior depth of the firebox 20 1 2 G The rear exterior width of the firebox 23 3 4 H The height to the firebox standoffs N A I Width from the left side of the box to the centerline of vent 18 11 16 J Depth from back of box to centerline ...

Page 5: ...PENING TO COMBUSTIBLES BOTH SIDES 2 3 4 3 4 2 3 4 6 NON COMBUSTIBLE FINISH MATERIAL MUST COVER THE SURFACE OF THE FIREPLACE FACE FRAMING HEADER DRYWALL SURFACE OF FACE COMBUSTIBLES ALLOWED CO MB US TIB LE S AL LO WE D CO MB US TIB LE S AL LO WE D 26 FROM SURFACE OF FACE TO COMBUSTIBLES 2 3 4 Figure 2 Mantel Chart MANTEL COMBUSTIBLE TRIM AND MANTELS ALLOWED IN SHADED AREA OPENING OF FIREPLACE G B C...

Page 6: ...anical air supply inlet to building or the combustion air inlet to any other appliance 12 in 30 cm minimum for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 9 in 23 cm minimum for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW C Clearance to perma nently closed window 12 in 30 cm minimum 12 in 30 cm minimum K Clearance to a mechani cal air supply inlet 6 ft 1 83 m minimum 3 ft 91 cm minimu...

Page 7: ...place opening GAS SUPPLY Installing a New Main Gas Cock Check Local Code Each appliance should have its own manual gas cock A manual main gas cock should be located in the vicinity of the unit Where none exists or where its size or location is not adequate contact your local authorized installer for installation or relocation Compounds used on threaded joints of gas piping shall be resistant to th...

Page 8: ...ONENT ACCESS BOX ELECTRICAL POWER TO UNIT JUNCTION BOX CONTROL MODULE Figure 13 Figure 14 A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached with wire nuts to the control module power leads already fed into the junction box Attach black to black and white to white The ground wire should be attached to the green c...

Page 9: ...stibles as shown in Figures 1 and 2 on page 8 For horizontal vent maintain a minimum 1 inch clearance to the bottom and sides of the vent and 3 inches of clearance to combustibles above the vent pipe See Figure 24 INSTALLATION continued Figure 23 HORIZONTAL VENT CLEARANCES Figure 24 Figure 18 Figure 19 Figure 20 Figure 21 ...

Page 10: ...allations through combustible wall Figure 25 vertical 90 elbow with horizontal termination 12 inches minimum vertical rise shown Figure 26 INSTALLATION continued VERTICAL 90 ELBOW TO HORIZONTAL OUT THE WALL 12 inches minimum rise before elbow NOTE A B dimension greater than 18 inches will require a vertical rise before the elbow that is greater than 12 inches See Venting graph on page 22 PIPE LENG...

Page 11: ...GH THE WALL HORIZONTAL INSTALLATIONS WITH 90 ELBOW AND 12 INCH RISE OFF TOP OF FIREPLACE Allowable A2 and E dimensions to be determined by consult ing the venting graph and horizontal venting termination examples on pages 22 and 23 Positioning the Fireplace Determine the exact position of the appliance so the direct vent termination will be centered if possible between two studs This will avoid an...

Page 12: ...mber of 90 elbows in a vent run is three Note On vertical venting the first elbow does not get counted Note Ahorizontalventwiththeminimumrequiredverticalrise using a 12 inch section of vent before the elbow will use a maximum of a 9 inch section of horizontal vent before the termination Acceptable vertical and horizontal vent run 40 maximum vertical and 20 maximum horizontal Unacceptable vertical ...

Page 13: ... in poor draft or down drafting In these cases increasing the vent height may solve this problem General Maintenance Inspect venting system semi annually as follows 1 Check for corrosion areas of the venting system exposed to the elements These will appear as rust spots or streaks and in extreme cases holes Replace damaged components should immediately 2 Remove the cap and shine a flashlight down ...

Page 14: ...lication will require that you first determine the roof pitch and use the appropriate venting components OFFSET CHART RISE OFFSET SIZE 5 X 8 ELBOW DEGREES CHIMNEY SECTION OFFSET INCHES RISE INCHES 45 0 5 5 8 15 3 8 45 6 8 7 8 18 3 8 45 9 10 7 8 20 5 8 45 12 13 22 5 8 45 24 21 3 8 31 1 8 45 36 29 7 8 39 3 8 45 36 28 7 8 39 3 8 45 48 38 1 4 47 7 8 Figure 44 VERTICAL TERMINATION continued VERTICAL TE...

Page 15: ... in each ceiling through which the vent passes Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs Reposition the appliance and vent system if necessary to accommodate ceiling jo...

Page 16: ...upper bracket and screw provided 6 Place Right Panel into position against right side firebox Secure with front upper bracket and screw provided Figure 50 NOTE Install liner before positioning the logs in place 1 Apply a single layer of small dime sized pieces of rock wool glowing embers in the shaded areas shown below NOTE Pieces of glowing embers should be fluffed up prior to placement onto the ...

Page 17: ...lames directly impinging a log turn off fireplace then remove the glowing ember material directly below where the flame impingement occurred This should eliminate sooting on the log and provide a more pleasing flame appearance Replacement of glowing embers must be purchased from Empire Comfort Systems Inc Application of excess glowing embers may adversely affect performance of the appliance WARNIN...

Page 18: ... right side pin on the rear burner TOP VIEW 2 Using right hand hold Right Rear Log A at approximately the angle shown FRONT VIEW LOG PLACEMENT 3 Place Left Rear Log B on left side pin on rear burner and attach the top of the Left Rear Log B to the pin on Right Rear Log A TOP VIEW FRONT VIEW ...

Page 19: ...Page 36 4 Place Right Front Log D on the two pins on the right hand side of the front burner TOP VIEW FRONT VIEW LOG PLACEMENT 5 Place Center Front Log E on tab in center of front burner Orient as shown TOP VIEW FRONT VIEW LOG PLACEMENT ...

Page 20: ...og C onto the two pins on the left hand side of the front burner TOP VIEW FRONT VIEW LOG PLACEMENT 7 Place Right Corner Log F onto pin on Right Front Log D Rest opposite end of Right Corner Log F in the right corner of the firebox TOP VIEW FRONT VIEW LOG PLACEMENT ...

Page 21: ...33740 9 1015 Page 41 33740 9 1015 Page 40 8 Place Center Rear Log G into recess onto the pin on the Left Front Log C TOP VIEW FRONT VIEW LOG PLACEMENT TOP VIEW FRONT VIEW LOG PLACEMENT ...

Page 22: ...E MAIN GAS SUPPLY AND ELECTRICAL SUPPLY TO THE APPLIANCE DURING INSTALLATION AND OR MAINTENANCE OF THE RECEIVER DEVICE WARNING Fire Hazard Can cause severe injury or death The Receiver causes ignition of the appliance The appliance can turn on suddenly Keep away from the appliance burner when operating the remote system or activating manual bypass of the remote system CAUTION Property Damage Hazar...

Page 23: ... to verify that a C or F is visible to the right of the Room Temperature display See Figures 60 and 61 Figure 60 Figure 61 Turn On the Appliance With the system OFF press the ON OFF Button on the Transmit ter The Transmitter display will show some other active Icons on the screen At the same time the Receiver will activate the appli ance A single beep from the Receiver will confirm reception of th...

Page 24: ...late the flame down To activate this function press the Thermostat Button until the word SMART appears to the right of the temperature bulb graphic See Figure 66 To adjust the set temperature press the Up or Down Arrow Buttons until the desired set temperature is displayed on the LCD screen of the Transmitter See Figure 70 Note When Smart Thermostat is activated manual flame height adjustment is d...

Page 25: ...EMOTE OPERATING INSTRUCTIONS Continuous Pilot Intermittent Pilot CPI IPI Selection With the system in OFF position press the Mode Button Figure 56 to index to the CPI mode icon See Figures 79 and 80 Pressing the Up Arrow Button will activate the CPI Pressing the Down Arrow Button will return to IPI A single beep will confirm the reception of the command OFF Figure 79 OFF Figure 80 Button Lock This...

Page 26: ...Low Battery Detection When the backup batteries are low a double beep will be emitted when the module receives an on off command No commands will be accepted until the batteries are replaced or the A C power is restored MULTIFUNCTION REMOTE OPERATING INSTRUCTIONS 1 If the IFC is signaling lock out The board should be unlocked to reinitiate a pilot flame ignition for the correct unlock sequence ref...

Page 27: ...r flame modulates If it does not modulate replace the gas valve 2 Verify that the gas valve outlet pressure limits are in accordance with the manufacturer specifications If not replace the gas valve FOR YOUR SAFETY READ BEFORE LIGHTING WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE A This appliance must...

Page 28: ...T 17 R11591 ACCESS PANEL GASKET 18 30953 ACCESS PANEL 19 P181 ORIFICE 1 90mm NAT FRONT 19 P320 ORIFICE 57 LP FRONT 20 P245 ORIFICE 43 NAT REAR 20 P208 ORIFICE 1 45mm LP REAR 21 R11675 ORIFICE HOLDER 22 R7572 JAMB NUT 23 33633 THERMOCOUPLE SHIELD 24 R11585 PILOT NAT 24 R11586 PILOT LP 25 30947 VALVE BRACKET 26 R11233 VALVE NAT 26 R11234 VALVE LP 27 R11546 SOLENOID 28 R11523 RECEIVER MODULE 29 R1158...

Page 29: ...urn off unit 2 Remove offset frame and glass front See Glass Removal 3 Remove logs and embers 4 Vacuum burner compartment a clean portable shop vac is recommended 5 Replace logs and embers 6 Reinstall glass front and offset frame 7 Ignite unit See Lighting Instructions 8 If flame appears abnormal call a service person Check Vent System The appliance and venting system should be inspected before in...

Page 30: ... Frame 2 Remove the Burner Components Heat Shield See Figure 86 3 Remove logs from firebox 4 Remove the liner bracket on top of the right hand liner panel and remove right hand liner panel 5 Remove the Access Plate See Figure 86 NOTE The control Module is located in the front right hand corner of the cavity To remove it lift up and away from the wall NOTE If it is necessary to remove one of the ga...

Page 31: ...P Gas is heavier than air and may settle in low areas such as basements When you have reason to suspect a gas leak keep out of basements and other low areas Stay out until firefighters declare them to be safe Use your neighbor s phone and call a trained LP Gas service person and the fire department Even though you may not continue to smell gas do not turn on the gas again Do not re enter the build...

Page 32: ...GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirements shall be satisfied by the manufacturer 1 The referenced special venting system instructions shall be included with the appliance or equipment i...

Page 33: ...ed in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts...

Reviews: