33740-9-1015
Page 29
33740-9-1015
Page 28
FRAMING AND FINISHING
Installing Support Brackets
Install a horizontal pipe support used for each 3 feet of horizontal run
to framing members. Allow 3 inches of clearance to combustibles
above 8 inch diameter pipe and elbows and 1 inches of clearance
on both sides and bottom.
Support vertical runs of this vent systems every 4 feet using wall
brackets attached to the vent pipe and secured with nails or screws
to structural framing.
Note:
Maintain all clearances to combustibles as shown in
Figures
1 and 2
on page 8.
Figure 45
Installing Firestops
Firestops are required for safety whenever the vent system passes
through an interior wall, an exterior wall, or a ceiling. These firestops
act as a firebreak heat shield and as a means to insure that minimum
clearances are maintained to the vent system.
Horizontal Firestops
Horizontal runs in the vent system which pass through either interior
or exterior walls, require the use of wall firestops on both sides of
the wall through which the vent passes.
Position the firestops on both sides of the framed hole, previously
cut. Refer to
Figure 46
for sizing information. Secure firestop with
nails or screws. The heat shields of the firestops MUST BE placed
towards the top of the hole. Continue the vent run through the firestops.
Figure 46
NOTE:
SD58DVAWTEC Wall thimble is necessary to maintain
the required three inches of clearance to combustibles above
the vent. Framed hole dimensions shown above are for this wall
thimble.
FRAMING AND FINISHING (continued)
Vertical Firestops
Vertical runs of this system which pass through ceilings require
ONE ceiling firestop at the hole in each ceiling through which the
vent passes.
Position a plumb bob directly over the center of the vertical vent
component and mark the ceiling to establish the center point of the
vent. Drill a hole or drive a nail through this center point and check
the floor above for any obstructions such as wiring or plumbing
runs. Reposition the appliance and vent system, if necessary, to
accommodate ceiling joists and/or obstructions.
Cut a 10-5/8 inch x 10-5/8 inch hole through the ceiling using the
center point previously marked. Frame the hole with framing lumber
the same size as the ceiling joists.
See Figure 47.
If the area
above the ceiling is NOT an attic, position and secure the ceiling
firestop on the ceiling side of the previously cut and framed hole.
See Figure 48.
If the area above the ceiling is an attic, position
and secure the firestop on top of the previously framed hole.
See
Figure 49.
NOTE:
Remove insulation from the framed area in the attic before
installing the firestop and/or vent pipes.
Figure 47
Figure 48
Figure 49
Finishing
Finish the walls with the material of your choice.
Figure 1 and 2
on
page 8 shows the minimum vertical and corresponding maximum
horizontal dimensions of mantels or other combustible projections
above the top front edge of the fireplace.
Only non-combustible materials may be used to cover the black
fireplace front.
WARNING
When finishing the fireplace never obstruct or modify the gap
around the glass frame in any manner. Provide adequate
clearances around air openings into the combustion chamber.
CAUTION
If the joints between the finished wall and the fireplace surround
(top and sides) are sealed, a 300°F minimum sealant material
must be used. These joints are not required to be sealed. Only
non-combustible material (using 300°F minimum adhesive if
needed) can be applied as facing to the fireplace surround.