TROUBLESHOOTING GUIDE

Unit leaks water

Possible Cause

Solution

Unit is not level

Unit should be level in wall to prevent leaking

Drain line clogged or kinked

Drain is clogged, preventing water from escaping

Disconnect drain and clear it out

Drain line does not have a downward slope

Fix drain line so there is a downward slope from the unit to the drain

Melt ice with blow drier. Soak up with a towel.

Unit runs but does not cool

Possible Cause

Solution

Make sure both fans are running and coils are not dirty or blocked by 
foreign objects.

Compressor not running

Contact Customer Service at 1-800-343-9463

System undersized

Contact Customer Service at 1-800-343-9463

Compressor is overheating

clean condenser coil as possible cause of compressor overheating. If 
problem repeats, contact Customer Service at 1-800-343-9463.

Evaporator fan runs but compressor does not

Possible Cause

Solution

Compressor and/or starting components faulty

Contact Customer Service at 1-800-343-9463

Compressor is overheating

clean condenser coil as possible cause of compressor overheating. If 
problem repeats, contact Customer Service at 1-800-343-9463.

Compressor runs but evaporator fan does not

Possible Cause

Solution

Faulty fan motor

Contact Customer Service at 1-800-343-9463

Faulty fan relay

Contact Customer Service at 1-800-343-9463

Compressor short-cycles

Possible Cause

Solution

Evaporator fans blow on bottle probe

Move bottle probe to a more central location

Unit low on refrigerant charge

Call Customer Service at 1-800-343-9463

Condensing fan motor/capacitor faulty

Call Customer Service at 1-800-343-9463

Compressor and/or starting components faulty

Call Customer Service at 1-800-343-9463

Humidity in cellar too high

Possible Cause

Solution

Install proper vapor barrier