TROUBLESHOOTING GUIDE

Ice is forming on the evaporator coil

Possible Cause

Solution

Evaporator coil is dirty

Clean coil with a vacuum brush attachment or blow out with
compressed air

There is something blocking the supply and/or return air

Remove blockage

Evaporator fan is not turning on

Call a service tech to troubleshoot

If unit continues to ice

Observe ice formation pattern. If only part way up the coil face, unit 
could be low on refrigerant. If so, call Customer Service at 
1-800-343-9463. 

Unit does not run/power up

Possible Cause

Solution

Unit is not plugged in

Make sure the unit is plugged into an outlet

Line voltage rating is incorrect for the system

Check line voltage to make sure it is 110V-120V

Room temperature equals the setpoint on the controller

Lower setpoint

Thermostat not calling for cooling

Lower setpoint

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar temperature is too warm

Possible Cause

Solution

The temperature of the room to which the unit is exhausting exceeds 
85°F. Make sure the exhaust area behind the unit is well ventilated. If 
you are unsure about ventilation, call customer service at
1-800-343-9463

Intake temperature must drop below 85°F

The unit is undersized for the room

Order correctly sized unit

There is something blocking the supply and/or return air on 
evaporator or condenser side of the unit

Unit is mounted too low in the room

Relocate unit so the distance from the ceiling and top of the unit is 
no more than 18 inches

One or more of the fans is not turning on

Call Customer Service at 1-800-343-9463

Compressor is not turning on

Call Customer Service at 1-800-343-9463

Compressor keeps cycling on overload

Poor seal around door

Make sure there are no air gaps around the door. If door seal is 
damaged, replace it.

Setpoint too high

Lower the setpoint

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the coil face, 
the unit could be low on refrigerant. If so, contact your installing 
technician to assist with troubleshooting.

System runs constantly

Possible Cause

Solution

Leaky door seal or poorly insulated cellar

Fix leaky door seal and insulate cellar in accordance with this manual 
(page 8)