OPERATION
16
W-GV4 Scalino outdoor — April 2017 — EN
minimum 70%. Long term running at too low load will
cause the exhaust to be choked by carbon (soot).
WARNING
Never remove the battery while the
engine is running or any electrical cable
while the battery is connected in the
circuit. Only disconnect the battery with
the engine stopped and all switches in
"OFF" position.
STOPPING AFTER LONGER OPERATION
Avoid stopping of the Genverter abruptly after a long period of
operation at high load! Doing so, you avoid unnecessary
thermal load to the engine!
Furthermore, do not stop the engine with the decompression
lever unless in emergency when there is total loss of control.
Act as follows:
1
Prior to switching off the WP-GV4 Scalino, decrease
the load (i.e. turn off most electrical users) and let the
Scalino run at low load for approx. 5 minutes to allow
the engine to get properly cool (the influent coolant
oil must flow through the system in order to cool the
engine).
2
If the Genverter is operating in a hot environment
and you do not act as given above, the excessive heat
in the engine can trip the "high temperature" alarms.
In that case, a restart of the engine is not possible for
some time. It is also recommended to switch off
electrical users prior to stopping the Genverter
because of the voltage drop that occurs as the engine
comes to a halt.
3
Press the STOP button and hold for 2 seconds.
4
Switch to another 230V power source, if available.