Whirlpool WGHP43 Installation Instructions Manual Download Page 5

5

Burying Refrigerant Lines

If burying refrigerant lines cannot be avoided, use the following 
checklist.

1. Insulate liquid and suction lines separately.

2. Enclose all underground portions of the refrigerant lines in 

waterproof material (conduit or pipe) sealing the ends where 
tubing enters/exits the enclosure.

3. If the lines must pass under or through a concrete slab, 

ensure lines are adequately protected and sealed.

Refrigerant Line Connections

IMPORTANT: To avoid overheating the service valve, TXV valve 
or filter dryer while brazing, wrap the component with a wet rag, 
or use a thermal heat trap compound. Be sure to follow the 
manufacturer’s instruction when using the heat trap compound. 

NOTE: Remove Schrader valves from service valves before 
brazing tubes to the valves. Use a brazing alloy of 2% minimum 
silver content. Do not use flux.

Torch heat required to braze tubes of various sizes is proportional 
to the size of the tube. Tubes of smaller size require less heat to 
bring the tube to brazing temperature before adding brazing alloy. 
Applying too much heat to any tube can melt the tube. Service 
personnel must use the appropriate heat level for the size of the 
tube being brazed. 

NOTE: The use of a heat shield when brazing is recommended to 
avoid burning the serial plate or the finish on the unit.

1. The ends of the refrigerant lines must be cut square, deburred, 

cleaned and be round and free from nicks or dents. Any other 
condition increases the chance of a refrigerant leak.

2. “Sweep” the refrigerant line with nitrogen or inert gas during 

brazing to prevent the formation of copper-oxide inside the 
refrigerant lines. The POE oils used in R-410A applications 
will clean any copper-oxide present from the inside of the 
refrigerant lines and spread it throughout the system. This 
may cause a blockage or failure of the metering device.

3. After brazing, quench the joints with water or a wet cloth to 

prevent overheating of the service valve.

4. Ensure the filter dryer paint finish is intact after brazing. If the 

paint of the steel filter dryer has been burned or chipped, 
repaint or treat with a rust preventive. This is especially 
important on suction line filter dryers which are continually 
wet when the unit is operating.

NOTES: 

Be careful not to kink or dent refrigerant lines. Kinked or 
dented lines will cause poor performance or compressor 
damage.

Do not make final refrigerant line connection until plugs are 
removed from refrigerant tubing.

Before brazing, verify indoor piston size by checking the 
piston kit chart packaged with indoor unit.

Leak Testing—Nitrogen or Nitrogen-Traced

Pressure test the system using dry nitrogen and soapy water to 
locate leaks. If you wish to use a leak detector, charge the system 
to 10 psi using the appropriate refrigerant, and then use nitrogen 
to finish charging the system to working pressure. Apply the 
detector to suspect areas. If leaks are found, repair them. After 
repair, repeat the pressure test. If no leaks exist, proceed to 
system evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed to contain 
the charge within the unit. The unit is shipped with the valve 
stems closed and caps installed. 

NOTE: Do not open valves until the system is evacuated.

NOTE: Scroll compressors should never be used to evacuate or 
pump down a heat pump or air conditioning system.

1. Connect the vacuum pump with 250 micron capability to the 

service valves.

2. Evacuate the system to 250 microns or less using suction 

and liquid service valves. Using both valves is necessary as 
some compressors create a mechanical seal separating the 
sides of the system.

3. Close pump valve and hold vacuum for 10 minutes. Typically 

pressure will rise during this period.

Goodman 17

WARNING

To avoid the risk of fire or explosion, never use oxygen, 
high pressure air or flammable gases for leak testing of a 
refrigeration system.

Goodman 18

WARNING

To avoid possible explosion, the line from the nitrogen 
cylinder must include a pressure regulator and a pressure 
relief valve. The pressure relief valve must be set to open at 
no more than 150 psig.

Goodman 19

              REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property 
damage, personal injury or death.

WARNING

Goodman 20

Prolonged operation at suction pressures less than 
20 psig for more than 5 seconds will result in overheating 
of the scrolls and permanent damage to the scroll tips, 
drive bearings and internal seal.

CAUTION

Summary of Contents for WGHP43

Page 1: ...ion 9 Heat Pump Heating Cycle 10 TROUBLESHOOTING INFORMATION 11 ASSISTANCE OR SERVICE 16 Whirlpool and Whirlpool Gold Models WHP43 WHP44 WGHP43 WGHP44 WGHP46 WGHP48 WPIO 259L Placeholder for Bar Code Goodman 1 Hazards or unsafe practices could result in property damage product damage severe personal injury or death Hazards or unsafe practices may result in property damage product damage personal i...

Page 2: ...des or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduction and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local office of the EPA If replacing a condensing unit or air handler the syst...

Page 3: ...ing of refrigerants Goodman 13 WARNING Refrigerants are heavier than air They can push out the oxygen in your lungs or in any enclosed space To avoid possible difficulty in breathing or death Never purge refrigerant into an enclosed room or space By law all refrigerants must be reclaimed If an indoor leak is suspected throughly ventilate the area before beginning work Liquid refrigerant can be ver...

Page 4: ...tributor for assistance Mounting the evaporator coil above the heat pump will require an inverted loop in the suction line adjacent or near the connection to the evaporator coil The top of the loop must be slightly higher than the top of the evaporator coil Mounting the heat pump above the evaporator coil will require an oil trap in the suction line Install one oil trap at the evaporator for a hei...

Page 5: ... This is especially important on suction line filter dryers which are continually wet when the unit is operating NOTES Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do not make final refrigerant line connection until plugs are removed from refrigerant tubing Before brazing verify indoor piston size by checking the piston ki...

Page 6: ...use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerate its load HighVoltageConnections Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover LowVoltageConnections The indoor transformer must supply 24 volt A...

Page 7: ... R G W2 C Heat Pump Conventional Room Thermostat 18 Gauge 7 Wire Indoor Unit Red Green White Blue BU 18 Gauge 5 Wire BU OR See Note 3 Outdoor Thermostat Optional Closed on Temperature Fall 18 Gauge 6 Wire Needed When Outdoor Thermostat Is Used BU W OR Y R See Note 4 BU W G R C W2 O Y R R Y W W 1 2 3 4 G Y O C G R E R W2 BR R G W2 C Red Green White Blue See Note 4 BU W G R W3 Brown BR Heat Pump Con...

Page 8: ... specification to properly seat the sealing surfaces NOTE Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the compressor 1 Break the vacuum by fully opening liquid and suction base valves 2 Set thermostat to call for cooling 3 Check indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 m...

Page 9: ...eat and remove charge to lower the subcooling to 5ºF to 9ºF NOTE Do not adjust the charge based on the suction pressure unless there is a gross undercharge 2 StageApplication 1 Temporarily install the thermometer on both the liquid small and vapor large lines near the service valves Ensure that there is adequate contact Insulate the sensors well for the best possible reading Use the liquid tempera...

Page 10: ...perature Saturated Suction Pressure Temperature Suction Pressure Saturated Suction Temperature ºF Suction Pressure Saturated Suction Temperature ºF PSIG R 410A PSIG R 410A 50 1 78 20 52 3 80 21 54 4 85 24 56 6 90 26 58 7 95 29 60 8 100 31 62 10 110 36 64 11 120 41 66 13 130 45 68 14 140 49 70 15 150 53 72 16 160 56 74 17 170 60 76 19 Saturated Liquid Pressure Temperature Liquid Pressure Saturated ...

Page 11: ... Replace if needed Faulty thermostat Test continuity of thermostat and wiring Replace if needed Faulty transformer Check control circuit with voltmeter Replace if needed Faulty compressor contactor Test continuity of coil and contacts Replace if needed Evaporator fan will not start Blown fuse Inspect fuse size and type Replace if needed Loose connection Inspect connection Tighten if needed Shorted...

Page 12: ...door coil Inspect coil and clean if needed Noncondensibles Recover charge Evacuate and recharge Recirculation of condensing air Remove obstruction to airflow Wrong type of expansion valve Replace valve Expansion valve restricted Remove restriction or replace valve Undersized expansion valve Replace valve Unsatisfactory Cooling Heating System runs continuously little cooling heating Shortage of ref...

Page 13: ...dows doors vent fans etc Airflow unbalanced Readjust air volume dampers Compressor is noisy Overcharge of refrigerant Recover part of charge Broken internal parts Replace compressor Broken valves Test compressor efficiency Replace if needed Expansion valve bulb loose Tighten bulb bracket Loose hold down bolts Tighten bolts Heating Only System runs blows cold air in heating Internal compressor over...

Page 14: ...ace restricted part Too much air across indoor coil heating only Reduce blower speed Broken valves Test compressor efficiency Replace if needed Inefficient compressor Test compressor efficiency Wrong type of expansion valve Replace valve Expansion valve restricted Remove restriction or replace valve Faulty reversing valve heating only Replace valve or solenoid Faulty defrost control heating only T...

Page 15: ...y outdoor coil Inspect coil and clean if needed Noncondensibles Recover charge Evacuate and recharge Recirculation of condensing air Remove obstruction to airflow Wrong type of expansion valve heating only Replace valve Expansion valve restricted Remove restriction or replace valve Oversized expansion valve Replace valve Faulty reversing valve heating only Replace valve or solenoid Faulty defrost ...

Page 16: ... number in your correspondence Or call toll free 1 866 944 7575 WPIO 259L 2010 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida Warranty provided by manufacturer All other trademarks are owned by their respective companies COMFORT COMMITMENT is a trademark of Tradewinds Distributing Compa...

Reviews: