11
TROUBLESHOOTING INFORMATION
Problem
No Cooling/Heating
Cause/Test Method and/or Solution
■
System will not start.
■
Power failure. Test voltage.
■
Blown fuse. Inspect fuse size and type. Replace, if needed.
■
Loose connection. Inspect connection. Tighten if needed.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Faulty thermostat. Test continuity of thermostat and wiring. Replace, if needed.
■
Faulty transformer. Check control circuit with voltmeter. Replace, if needed.
■
Compressor will not start—fan runs.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Shorted or open capacitor. Test capacitor.
■
Internal compressor overload open. Test continuity of overload.
■
Shorted or grounded compressor. Test motor windings.
■
Compressor stuck. Use test cord.
■
Low voltage. Test voltage.
■
Compressor and condenser fan will
not start.
■
Blown fuse. Inspect fuse size and type. Replace, if needed.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Faulty thermostat. Test continuity of thermostat and wiring. Replace, if needed.
■
Faulty transformer. Check control circuit with voltmeter. Replace, if needed.
■
Faulty compressor contactor. Test continuity of coil and contacts. Replace, if needed.
■
Evaporator fan will not start.
■
Blown fuse. Inspect fuse size and type. Replace, if needed.
■
Loose connection. Inspect connection. Tighten if needed.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Open fan overload. Test continuity of overloads.
■
Faulty thermostat. Test continuity of thermostat and wiring. Replace, if needed.
■
Shorted or open capacitor. Test capacitor.
■
Faulty fan relay. Test continuity of coil and contacts.
■
Open control circuit. Test control circuit with voltmeter.
■
Faulty evaporator fan motor. Repair or replace.
■
Condenser fan will not start.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Open fan overload. Test continuity of overloads.
■
Shorted or open capacitor. Test capacitor.
■
Faulty compressor contactor. Test continuity of coil and contacts. Replace, if needed.
■
Shorted or grounded fan motor. Test motor windings.
■
Faulty defrost control. Test control.