15
■
High head pressure.
■
Faulty evaporator fan motor (heating only). Repair or replace.
■
Shorted or grounded fan motor. Test motor windings.
■
Restricted liquid line. Replace restricted part.
■
Dirty air filter (heating only). Inspect filter; clean or replace as needed.
■
Dirty indoor coil (heating only). Inspect coil and clean, if needed.
■
Not enough air across indoor coil (heating only). Check blower speed. Check duct
static pressure and filter.
■
Overcharge of refrigerant. Recover part of charge.
■
Dirty outdoor coil. Inspect coil and clean, if needed.
■
Noncondensibles. Recover charge. Evacuate and recharge.
■
Recirculation of condensing air. Remove obstruction to airflow.
■
Wrong type of expansion valve (heating only). Replace valve.
■
Expansion valve restricted. Remove restriction or replace valve.
■
Oversized expansion valve. Replace valve.
■
Faulty reversing valve (heating only). Replace valve or solenoid.
■
Faulty defrost control (heating only). Test control.
■
Faulty defrost thermostat (heating only). Test defrost thermostat.
Problem
No Cooling/Heating
Cause/Test Method and/or Solution
Goodman 23 Long